Plan Review Details - Permit 08050523
| Plan Review Stops For Permit 08050523 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-06-11 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-06-11 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2008-06-11 12:07:26 | 2004 FBC W/2007 REVISIONS | | | LEVEL 3 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) SPECIFY THE APPLICABLE BUILDING CODES AND DESIGN | | | CRITERIA ON THE PLANS. SPECIFY WIND SPEED, EXPOSURE | | | CATEGORY, COMPONENT AND CLADDING PRESSURES FOR THE | | | WINDOW AND DOOR OPENINGS, ETC. SEE FBC SECTION R301. | | | | | | 3) ENGINEERS ARE REQUIRED TO LEGIBLY INDICATE THEIR | | | NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET OF | | | PLANS. IF PRACTICING THROUGH A DULY AUTHORIZED | | | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE | | | THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION | | | NUMBER FOR THE ENGINEERING BUSINESS ON EACH SHEET, IN | | | ADDITION TO THEIR NAME AND LICENSE NUMBER. FAC | | | 61G15-23.002 AND FS 471 | | | | | | 4) ON SHEET 3 OF THE PLANS, ITEM #8 SPECIFIES A NEW | | | FRENCH DOOR AT THE LAUNDRY ROOM. PLEASE CORRECT. | | | | | | 5) PROVIDE ALL DIMENSIONS FOR THE NEW WOOD DECK. | | | SPECIFY THE SPACING OF THE SUPPORT POSTS, JOISTS, ETC. | | | SPECIFY THE ATTACHMENT OF THE DECK TO THE RESIDENCE. | | | SPECIFY ALL STRAPS AND CONNECTORS. SHOW COMPLIANCE WITH | | | R301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, | | | SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, | | | INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD | | | LOADS AND WIND LOADS AS PRESCRIBED BY THIS CODE. THE | | | CONSTRUCTION OF BUILDINGS AND STRUCTURES SHALL RESULT | | | IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH CAPABLE | | | OF TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN | | | THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION. | | | VERIFY THAT THE SPECIFIED FOOTERS ARE CAPABLE OF | | | RESISTING THE 140 MPH WIND SPEED. FBC 106.1.2* CITY | | | AMENDMENTS | | | | | | 6) SPECIFY THE HEIGHT OF THE DECK ABOVE GRADE. SHOW | | | COMPLIANCE WITH R312.1 PORCHES, BALCONIES OR RAISED | | | FLOOR SURFACES LOCATED MORE THAN 30 INCHES (762 MM) | | | ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS NOT | | | LESS THAN 36 INCHES (914 MM) IN HEIGHT. OPEN SIDES OF | | | STAIRS WITH A TOTAL RISE OF MORE THAN 30 INCHES (762 | | | MM) ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS | | | NOT LESS THAN 34 INCHES (864 MM) IN HEIGHT MEASURED | | | VERTICALLY FROM THE NOSING OF THE TREADS AND R312.2 | | | REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED | | | FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE | | | INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT | | | ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN | | | DIAMETER. | | | | | | 7) THE FOOTER DETAIL ON SHEET 5 IS REQUIRED TO COMPLY | | | WITH R403.1.4 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT | | | LEAST 12 INCHES (305 MM) BELOW THE UNDISTURBED GROUND | | | SURFACE. | | | | | | 8) SPECIFY THE CONNECTORS THAT WILL BE USED ON THE | | | FRAMING DETAILS ON SHEET 5. SEE R301.1. | | | | | | 9) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR FRENCH | | | DOORS WITH AND WITHOUT SIDE-LITES, FIXED AND CASEMENT | | | WINDOWS AS REQUIRED BY FAC RULE 9B-72. | | | | | | 10) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 11) SPECIFY THE WINDOW TYPES AND SIZES ON THE PLANS FOR | | | ALL OF THE NEW WINDOWS. FBC 106.1.1* CITY AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-05-20 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-05-20 |
Time |
14:24 |
Sent To |
M |
|
| Notes |
| 2008-05-20 14:36:49 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC CHAPTER 1AS AMENDED AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1}A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER | | | 61G15-23.002(2) FAC. IS REQUIRED. | | | | | | 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 | | | RESIDENTIAL FLORIDA BUILDING CODE.LOCATE SAME ON | | | PLANS. | | | | | | 3}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS, | | | PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS | | | PER 106.3.5.4 FBC. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | | | 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND | | | 210.52(A)(2). 2005 NEC. ALL ROOMS. | | | | | | 6} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. | | | SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND | | | 422.31(B) FOR HARDWIRE REQUIREMENTS. | | | | | | 7} SHOW THE LOCATION OF THE A/C CONDENSER ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63. | | | | | | 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. | | | | | | 9} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING | | | AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE | | | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT | | | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE | | | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE | | | DWELLING.NONE IS SHOWN IN THE FRONT AND THE REAR | | | RECEPTACLE HAS A 240 VOLT DESIGNATION. | | | | | | 10} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1).BATHS 1 & 2 DO NOT COMPLY. | | | | | | 11} INDICATE IF THE DEVICES ON THE PLAN ARE NEW OR | | | EXISTING. IF ALL NEW A NOTE WILL SUFFICE. | | | | | | 12} INDICATE THE INTENDED SCOPE OF ELECRICAL WORK. | | | | | | PROVIDE A WRITTEN RESPONSE, REMOVE OLD AND VOIDED | | | SHEETS AND PROVIDE ONE COPY OF THE OLD PLANS WHEN | | | RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-05-19 |
|
|
Cont ID |
|
| Sent By |
swurafti |
Date |
2008-05-19 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
swurafti |
Date |
2008-05-19 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2008-05-19 16:35:20 | HISTORIC APPROVED BY JPAPA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-06-11 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-05-20 |
Time |
10:34 |
Sent To |
Z |
|
| Notes |
| 2008-05-20 10:34:32 | TO "SFR" "E" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-20 |
Time |
16:28 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-05-20 |
Time |
16:28 |
Sent To |
P |
|
| Notes |
| 2008-05-20 16:29:18 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-05-21 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-05-21 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-05-21 |
Time |
10:27 |
Sent To |
B |
|
| Notes |
| 2008-05-21 13:17:17 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. A TITLE BLOCK FOR THE ENGINEER OF RECORD WITH | | | INFORMATION IS REQUIRED ON ALL SHEETS PER | | | 61G15-23.002(2) FAC. | | | | | | 2. SHEET 3 FIRST FLOOR PLAN INDICATES A 40 GAL. LOW | | | BOY WATER HEATER INSTALLED IN THE CORNER UNDER A | | | KITCHEN CABINET. PER FBC-2004 PLUMBING SECTION 501.4 | | | LOCATION. WATER HEATERS AND STORAGE TANKS SHALL BE | | | LOCATED AND CONNECTED SO AS TO PROVIDE ACCESS FOR | | | OBSERVATION, MAINTENANCE, SERVICING AND REPLACEMENT. | | | THE CODE DEFINES ACCESS AS BEING ABLE TO BE REACHED BUT | | | FIRST MAY REQUIRE THE REMOVAL OF A PANEL, DOOR OR | | | SIMILAR OBSTRUCTION. ACCESS TO A WATER HEATER IS NOT | | | ACHIEVED IF IT IS NECESSARY TO REMOVE ANY PORTION OF | | | THE STRUCTURE'S PERMANENT FINNISH MATERIALS SUCH AS THE | | | CORNER OF THE CABINET. CLEARLY INDICATE HOW ACCESS TO | | | THE WATER HEATER WILL BE ACHIEVED ON THE RESUBMITTAL. | | | IT IS SUGGESTED THAT THE WATER HEATER BE MOVED TO THE | | | A/C CLOSET WITH THE A/C PLACED ON A STAND AND THE WATER | | | HEATER BE INSTALLED UNDER THE A/C UNIT. | | | | | | 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 | | | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A | | | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING | | | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT | | | LOCATIONS OF THE PROPOSED PLUMBING. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-11 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-11 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2008-06-11 16:09:16 | ***FAILED*** | | | | | | | | | 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | | | 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | | 94-305(B)(4) OF THE CITY'S ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | 3)INDICATE THE HEIGHT OF PROPOSED DECK FROM GRADE. | | | | | | 4)INDICATE THE HEIGHT OF PROPOSED RAILING FROM | | | GRADE.PURSUANT TO SECTION 94-302 OF THE ZLDRS: | | | MAXIMUM HEIGHT.IN RESIDENTIAL DISTRICTS, NO FENCE OR | | | WALL SHALL EXCEED SIX FEET IN HEIGHT WITHIN REQUIRED | | | SIDE AND REAR SETBACKS.HOWEVER, A FENCE/RAILING THAT | | | EXCEEDS THE MAXIMUM HEIGHT SHALL BE PERMITTED, AS LONG | | | AS IT IS OUTSIDE OF THE REQUIRED SETBACKS. | | | | | | 5)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED DECK | | | TO ALL ADJACENT PROPERTY LINES.PURSUANT TO SECTION | | | 94-305 OF THE ZLDRS:STEPS AND PORCHES.STEPS, OPEN | | | UNCOVERED PORCHES OR STOOPS, AND OPEN TERRACES WHICH | | | ARE THREE FEET OR LESS ABOVE GRADE MAY ENCROACH INTO | | | ANY REQUIRED SETBACK AREA TO A POINT NOT CLOSER THAN | | | TWO FEET TO THE PROPERTY LINE. ANY GRADE DIFFERENTIAL | | | BETWEEN THE ENCROACHING STEP, PORCH, STOOP, OR TERRACE | | | AND ADJACENT PROPERTY SHALL BE STRUCTURALLY RETAINED | | | AND POSITIVELY DRAINED IN A MANNER THAT WILL PREVENT | | | ANY DRAINAGE DISCHARGE TO ANY PROPERTY CONTIGUOUS TO | | | THE SIDE OR REAR PROPERTY LINES.STEPS AND PORCHES ARE | | | PERMITTED TO EXCEED THREE FEET AS LONG AS THEY ARE | | | OUTSIDE OF THE REQUIRED SETBACKS. | | | | | | NOTE:MINIMUM SETBACKS FOR PRINCIPAL BUILDINGS. | | | | | | A.FRONT: 25 FEET; | | | B.CORNER SIDE (IF APPLICABLE): 12.5 FEET; TEN FEET | | | IF LOT IS LESS THAN 60 FEET WIDE; | | | C.REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, | | | WHICHEVER IS LESS; | | | D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | NOTE:ANY NEWLY SUBMITTED PLANS SHALL BE | | | RESTAMPED/APPROVED BY THE CITY'S HISTORIC PRESERVATION | | | DEPARTMENT. | | | | | | NOTE:AS NO RENTAL LICENSE EXISTS FOR THIS PROPERTY | | | UNDER THE CURRENT OWNER'S NAME, A RENTAL LICENSE SHALL | | | BE APPLIED FOR BY THE CURRENT OWNER OR THE EXISTING | | | LICENSE AMENDED FOR CHANGE OF OWNERSHIP. | | | | | | NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|
|