| Plan Review Stops For Permit 08050488 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-07-24 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-07-24 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-07-24 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2008-07-24 14:35:30 | FRONT ENTRY REVISIONOKLM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-06-17 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-06-17 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2008-06-17 16:47:25 | ***PROVISO*** | | | PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT PERMANENTLY | | | INSTALLED EQUIPMENT POWERED BY INTERNALCOMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE WITH | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION | | | ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS) | | | LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS | | | IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING | | | COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED | | | WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF | | | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, | | | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 | | | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES | | | OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION | | | INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS | | | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE | | | TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF | | | STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL | | | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, | | | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED | | | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. | | | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES | | | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | LUIS MARTINEZ | | | 805-6710 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-06-04 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-06-04 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2008-06-04 11:40:06 | BUILDING REVIEW COMMENTS | | | | | | | | | PLEASE PROVIDE A CODE ANALYSIS REFERENCING ALL | | | APPLICABLE CODES FOR BOTH THE ARCHITECT AND ENGINEER'S | | | DRAWINGS. | | | | | | PLEASE CLARIFY DISCREPANCIES WITH THE SQUARE FOOTAGES | | | PROVIDED ON THE ENERGY CALCULATIONS AND THE PERMIT | | | APPLICATION. | | | | | | HAVE PLANS REVIEWED AND STAMPED BY PALM BEACH COUNTY | | | IMPACT FEE OFFICE. | | | | | | | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-02-18 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-02-18 |
Time |
06:49 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-07-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-23 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-23 |
Time |
11:49 |
Sent To |
B |
|
| Notes |
| 2008-07-23 12:35:32 | | | | | | | | | | REVISION TO EXTEND ENTRY AND ENTRY LIGHTING./WRT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-16 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-16 |
Time |
08:24 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-05-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-05-21 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-05-20 |
Time |
15:27 |
Sent To |
M |
|
| Notes |
| 2008-05-20 16:53:53 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | | FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET MEP-1, UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1}THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL | | | "A" ON THE RISER DIAGRAM CREATES A PARALLEL PATH TO | | | GROUND WITH THE NEUTRAL AND MUST BE REMOVED. 250.6.2005 | | | NEC. | | | | | | 2} PANEL "A" MUST BE SERVICE RATED AND HAVE A MAIN | | | BREAKER, OR A DISCONNECT IS REQUIRED OUTSIDE BETWEEN | | | THE METER AND PANEL. 230.70 | | | | | | 3} THE RISER INDICATES 3# 6CU FEEDERS FOR PANEL "B", | | | THE PANEL SCHEDULE INDICATES # 8. | | | | | | 4} THE 30 AMP OCP FOR PANEL "B" IS NOT LARGE ENOUGH FOR | | | THE 48 AMP LOAD CALCULATED FOR THAT PANEL. 310.16. | | | | | | 5} #4 FEEDERS FROM THE METER TO THE 133 AMP LOAD ON | | | PANEL "A" (RATED AT 200 AMPS) IS IN VIOLATION OF | | | 310.15(B)(6). MINIMUM OF 2/0 CU CONDUCTORS. | | | | | | 6} THE AHU OCP, CIRCUIT 28,30 PANEL "A" IS NOT LARGE | | | ENOUGH FOR THE 8500 WATT LOAD @ 125%. SEE 424.3(B), | | | 310.16, 240.6.(44 AMPS). | | | | | | 7} CIRCUITS 36,38 FOR AHU #2, THE OCP IS TOO LARGE, SEE | | | REFERENCES, COMMENT #6. (28 AMPS@ 125%). | | | | | | 8} THE WASHER CIRCUIT #23 PANEL "A" (LAUNDRY) MUST BE | | | CALCULATED AT 1500 WATTS PER 210.11(C)(2). | | | | | | NOTE: THE 3/0 GROUNDING ELECTRODE CONDUCTOR ON THE | | | RISER IS NOT A VIOLATION OF 250.66, BUT A #2 IS ALL | | | THAT'S REQUIRED. WHAT IS SHOWN ON THE PERMIT SET OF | | | PLANS MUST BE INSTALLED OR A REVISION SUBMITTED TO | | | CHANGE THAT SIZE AT A LATTER DATE. | | | | | | COMMENTS FROM SHEET E-1. | | | | | | 9} R313.1 SMOKE ALARMS. | | | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | 1. IN EACH SLEEPING ROOM. | | | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | TWO ALARMS NEED TO BE ADDED IN THE HALL OUTSIDE OF | | | BEDROOM #4 AND THE GUEST BEDROOM TO MEET THE INTENT OF | | | R 313.1.2 . ALSO SEE THE DEFINITION OF "SMOKE | | | DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS | | | OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING | | | DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING | | | DEVICES. | | | | | | 10} AT LEAST ONE GFI RECEPTACLE MUST BE INSTALLED IN | | | THE GARAGE FOR COMPLIANCE WITH 210.52(G). | | | | | | 11} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEVERAL ARE | | | MISSING ALONG THE COUNTER. | | | | | | 12} A RECEPTACLE MUST BE ADDED TO THE BATH ADJACENT TO | | | THE FOYER TO COMPLY WITH 210.52(D), MUST BE GFI PER | | | 210.8(A)(1). | | | | | | 13} THE WHIRLPOOL PUMP RECEPTACLE MUST BE GFI PROTECTED | | | PER 680.43(A)(3). | | | | | | 14} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2009-02-17 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2009-02-17 |
Time |
16:11 |
Sent To |
E |
|
| Notes |
| 2009-02-17 16:31:15 | ************PROVISO************** | | | FUTURE GENERATOR PIPING AT OWN RISK. | | | SEPARATE GEN/RES PERMIT REQUIRED WITH ZONING | | | APPROVAL OF GENERATOR PLACEMENT. | | | NOTE: PER FBC-2004 FUEL GAS SECTION - 404.12 | | | OUTLET CLOSURES. GAS OUTLETS THAT DO NOT CONNECT | | | TO APPLIANCES SHALL BE CAPPED GAS TIGHT. | | | MP REGULATORS SHALL BE CONNECTED BEFORE | | | FINAL INSPECTION. | | | | | | REVIEW BY LARRY WAGNER | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-17 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-17 |
Time |
13:16 |
Sent To |
B |
|
| Notes |
| 2008-06-17 13:18:10 | ****************PROVISO**************** | | | FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | | GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF | | | GENERATOR PLACEMENT. | | | NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET | | | CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES | | | SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS | | | 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR | | | TO FINAL INSPECTION. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-05-27 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-05-27 |
Time |
10:12 |
Sent To |
B |
|
| Notes |
| 2008-05-27 11:17:49 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET MEP-1 GAS LINE ISOMETRIC PLEASE CORRECT THE | | | FOLLOWING PER FBC-2004 FUEL GAS: | | | | | | A} THE SUBMITTED GAS ISOMETRIC IS NOT INDICATING | | | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. A | | | GAS PLAN REVIEW CAN NOT BE DONE UNTIL AN ACCURATE | | | LONGEST LENGTH OF THE GAS SYSTEM HAS BEEN ESTABLISED. | | | PLEASE REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED | | | CUT SECTIONS WITH NO CORRESPONDING LENGTHS INDICATED. | | | PER SECTION 401.1 SCOPE. | | | | | | B} PLEASE CORRELATE BTU LOAD CALCULATIONS FOR THE | | | WATER HEATER. THE GAS ISOMTRIC IS INDICATING A BUT LOAD | | | OF 100,000 HOWEVER THE GAS LOAD CALCULATIONS ARE | | | INDICATING THE BTU LOAD FOR THE WATER HEATER AS | | | 250,000. PER SECTION 401.1 SCOPE. | | | | | | C} CLEARLY INDICATE THE GENERATOR AS BEING "FUTURE" | | | AND THAT THE GAS PIPING TO THE GENERATOR SHALL BE | | | CAPPED GAS TIGHT. SECTION 401.1 SCOPE AND SECTION | | | 404.12 OUTLET CLOSURERS. NOTE: PIPING TO A FUTURE | | | GENERATOR SHALL BE AT OWN RISK UNTIL A RESIDENTIAL | | | GENERATOR APPLICATION HAS BEEN APPLIED FOR AND THE | | | GENERATORS LOCATION HAS BEEN APPROVED BY ZONING. | | | | | | D} SHEET MEP-1 "GAS NOTES"#7 STATES THAT THE | | | INTERIOR MAY BE PIPED WITH CORRUGATED STAINLESS STEEL | | | TUBING. PLEASE KNOW THAT YOU ARE CIRCUMVENTING YOUR | | | NOTE #5 BY PUTTING THIS IN THE GAS NOTES DUE TO THE | | | DIFFERENCE IN PIPING MATERIAL BTU LOAD CAPACITIES. CSST | | | HAS LESS BTU LOAD CAPACITY AS SCH. 40 METALLIC PIPE. IF | | | IT IS THE INTENT TO USE CSST THEN THE GAS ISOMETRIC | | | SHALL CLEARLY INDICATE WHICH CUT SECTIONS ARE TO BE | | | CSST AND SIZED ACCORDINGLY PER TABLE 402.4(14) OR | | | DELETE NOTE #7 FROM RESUBMITTED PLANS. | | | NOTE: THE CALCULATED LONGEST LENGTH WITH THE INDICATED | | | CORRESPONING LENGTHS IS 97' (REFERENCE COMMENT A). THE | | | GAS PLAN REVIEW WAS DONE WITH THE LONGEST LENGTH AS | | | 100'. PLEASE REFERENCE THE RED LINE CORRECTIONS TO THE | | | GAS ISOMETRIC USING FBC-2004 FUEL GAS TABLES 402.4 (2) | | | AND 402.4(20). PLEASE REFERENCE THESE GAS TABLES AS | | | WELL AS THE CSST TABLE 402.4(14) ATTACHED TO THESE | | | COMMENTS FOR REFERENCE FOR THE RESUBMITTAL. | | | | | | 2. SHEET A-1 FLOOR PLAN INDICATES AN 80 GAL. GAS WATER | | | HEATER IN THE GARAGE HOWEVER THERE IS NO PROTECTION | | | BEING INDICATED FOR THE WATER HEATER. PLEASE INDICATE | | | THE REQUIRED PROTECTION FOR THE WATER HEATER. PER | | | FBC-2004 FUEL GAS SECTION 303.4 PROTECTION FROM | | | PHYSICAL DAMAGE. | | | | | | 3. SHEET A-1 PLEASE CLEARLY INDICATE THE GAS METER | | | LOCATION. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. | | | | | | 4. PLEASE REFERENCE MECHANICAL COMMENTS #1 AND #4 AND | | | COMPLY. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-06-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-10 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-10 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2008-06-10 16:21:21 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-06-04 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-05-20 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2008-05-20 10:25:45 | TO "SFR" "E" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-02-17 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-02-17 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-16 |
Time |
12:09 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-06-16 |
Time |
12:09 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-05-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-22 |
Time |
08:03 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2008-05-22 |
Time |
08:03 |
Sent To |
P |
|
| Notes |
| 2008-05-22 08:11:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 2) ENERGY CALCULATIONS ARE MISSING THE JOB ADDRESS, | | | JURISDICTION NUMBER, ETC. PLEASE CORRECT. | | | | | | 3) COOLING LOAD CALCULATIONS MAY NOT BE DONE BY A WORSE | | | CASE SCENARIO, BUT MUST BE DONE TO THE SPECIFIC | | | BUILDINGS ORIENTATION, PER FLORIDA BUILDING COMMISSION | | | DECLARATORY STATEMENT DCA06-DEC-130. PLEASE CORRECT. | | | | | | 4) THE GAS CLOTHES DRYERS ARE IN A CONFINED SPACE | | | PLEASE PROVIDE FOR COMBUSTION AIR AND MAKE UP AIR, PER | | | 2004 FBC/R G2407.1, G2407.4, AND G2407.5.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-17 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-17 |
Time |
13:16 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-05-27 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-05-27 |
Time |
08:36 |
Sent To |
G |
|
| Notes |
| 2008-05-27 09:00:33 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET D-1 PLEASE ADD THE FOLLOWING TO GENERAL | | | DEMOLITION NOTES: | | | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE | | | INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING | | | PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF | | | PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH | | | FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS. | | | | | | 2. SHEET MEP-1 SANITARY RISER DIAGRAM: PLEASE CORRECT | | | THE FOLLOWING ITEMS PER FBC-2004 PLUMBING. | | | | | | A} THE WASHING MACHNE AND LAUNDRY TRAY MUST DRAIN | | | DOWNSTREAM OF WET VENTED BATHROOM #4. PER SECTION 909.1 | | | WET VENT PERMITTED. | | | | | | B} A THREE INCH CLEANOUT IS REQUIRED FOR THE WASHING | | | MACHINE STACK AND IT SHALL BE LOCATED AT FOUR FEET | | | ABOVE FINNISH FLOOR. PER SECTION 708.7 MINIMUM SIZE AND | | | SECTION 708.9 ACCESS. | | | | | | C} THE BIDET IN THE MASTER BATH REQUIRES A WATER SEAL | | | TRAP. PER SECTION 1002.1 TRAP REQUIRED. | | | | | | D} CLEARLY INDICATE THAT THE CLEANOUTS AT THE JUNCTION | | | OF THE BUILDING DRAIN AND BUILDING SEWER WILL BE | | | TWO-WAY CLEANOUTS. PER SECTION 708.3.5. | | | | | | E} CLEARLY SIZE ALL TRAPS OR PROVIDE A FIXTURE TRAP | | | SIZING SCHEDULE. PER SECTION 701.1 SCOPE AND (W.P.B. AS | | | AMENDED) SECTION 106.3.5.4 RESIDENTIAL (9) PLUMBING. | | | | | | F} THE ICE MAKER BY THE BAR SINK MAY REQUIRE A DRAIN. | | | PLEASE SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR | | | THE ICE MAKER AND DESIGN ACCORDINGLY IF APPLICABLE. PER | | | SECTION 701.1 SCOPE. | | | | | | 3. SHEET MEP-1 PLUMBING NOTES #11: INDICATES APPROVED | | | AIR CHAMBER. AIR CHAMBERS ARE NOT APPROVED UNLESS | | | INSTALLED PER STANDARD PDI-WH-201 A RECHARGEABLE TYPE | | | OF AIR CHAMBER. (DETAIL REQUIRED OR DELETE AIR CHAMBERS | | | ON THE RESUBMITTAL) | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-06-04 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-06-04 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2008-06-04 11:47:58 | FIRST REVIEW , FAILED STATUS WAS IN ERROR, NO REVIEW | | | REQUIRED. L.MARTINEZ |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-07-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-07-23 |
Time |
17:00 |
Sent To |
B |
|
| Notes |
|
|