Plan Review Details - Permit 08050488
Plan Review Stops For Permit 08050488
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-24 Cont ID  
Sent By lmartine Date 2008-07-24 Time 14:35 Rev Time 0.00
Received By lmartine Date 2008-07-24 Time 14:34 Sent To  
Notes
2008-07-24 14:35:30FRONT ENTRY REVISIONOKLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-17 Cont ID  
Sent By lmartine Date 2008-06-17 Time 16:35 Rev Time 0.00
Received By lmartine Date 2008-06-17 Time 16:35 Sent To  
Notes
2008-06-17 16:47:25***PROVISO***
 PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT PERMANENTLY
 INSTALLED EQUIPMENT POWERED BY INTERNALCOMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE WITH
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING
 COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED
 WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 LUIS MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By lmartine Date 2008-06-04 Time 11:40 Rev Time 0.00
Received By lmartine Date 2008-06-04 Time 11:04 Sent To  
Notes
2008-06-04 11:40:06BUILDING REVIEW COMMENTS
  
  
 PLEASE PROVIDE A CODE ANALYSIS REFERENCING ALL
 APPLICABLE CODES FOR BOTH THE ARCHITECT AND ENGINEER'S
 DRAWINGS.
  
 PLEASE CLARIFY DISCREPANCIES WITH THE SQUARE FOOTAGES
 PROVIDED ON THE ENERGY CALCULATIONS AND THE PERMIT
 APPLICATION.
  
 HAVE PLANS REVIEWED AND STAMPED BY PALM BEACH COUNTY
 IMPACT FEE OFFICE.
  
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-02-18 Cont ID  
Sent By btrobaug Date 2009-02-18 Time 07:59 Rev Time 0.00
Received By btrobaug Date 2009-02-18 Time 06:49 Sent To PC
Notes
2009-02-18 07:59:06 
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-23 Cont ID  
Sent By btrobaug Date 2008-07-23 Time 12:34 Rev Time 0.00
Received By btrobaug Date 2008-07-23 Time 11:49 Sent To B
Notes
2008-07-23 12:35:32 
  
  
 REVISION TO EXTEND ENTRY AND ENTRY LIGHTING./WRT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By btrobaug Date 2008-06-16 Time 08:59 Rev Time 0.00
Received By btrobaug Date 2008-06-16 Time 08:24 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-21 Cont ID  
Sent By btrobaug Date 2008-05-21 Time 09:35 Rev Time 0.00
Received By btrobaug Date 2008-05-20 Time 15:27 Sent To M
Notes
2008-05-20 16:53:53 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET MEP-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1}THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL
 "A" ON THE RISER DIAGRAM CREATES A PARALLEL PATH TO
 GROUND WITH THE NEUTRAL AND MUST BE REMOVED. 250.6.2005
 NEC.
  
 2} PANEL "A" MUST BE SERVICE RATED AND HAVE A MAIN
 BREAKER, OR A DISCONNECT IS REQUIRED OUTSIDE BETWEEN
 THE METER AND PANEL. 230.70
  
 3} THE RISER INDICATES 3# 6CU FEEDERS FOR PANEL "B",
 THE PANEL SCHEDULE INDICATES # 8.
  
 4} THE 30 AMP OCP FOR PANEL "B" IS NOT LARGE ENOUGH FOR
 THE 48 AMP LOAD CALCULATED FOR THAT PANEL. 310.16.
  
 5} #4 FEEDERS FROM THE METER TO THE 133 AMP LOAD ON
 PANEL "A" (RATED AT 200 AMPS) IS IN VIOLATION OF
 310.15(B)(6). MINIMUM OF 2/0 CU CONDUCTORS.
  
 6} THE AHU OCP, CIRCUIT 28,30 PANEL "A" IS NOT LARGE
 ENOUGH FOR THE 8500 WATT LOAD @ 125%. SEE 424.3(B),
 310.16, 240.6.(44 AMPS).
  
 7} CIRCUITS 36,38 FOR AHU #2, THE OCP IS TOO LARGE, SEE
 REFERENCES, COMMENT #6. (28 AMPS@ 125%).
  
 8} THE WASHER CIRCUIT #23 PANEL "A" (LAUNDRY) MUST BE
 CALCULATED AT 1500 WATTS PER 210.11(C)(2).
  
 NOTE: THE 3/0 GROUNDING ELECTRODE CONDUCTOR ON THE
 RISER IS NOT A VIOLATION OF 250.66, BUT A #2 IS ALL
 THAT'S REQUIRED. WHAT IS SHOWN ON THE PERMIT SET OF
 PLANS MUST BE INSTALLED OR A REVISION SUBMITTED TO
 CHANGE THAT SIZE AT A LATTER DATE.
  
 COMMENTS FROM SHEET E-1.
  
 9} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 TWO ALARMS NEED TO BE ADDED IN THE HALL OUTSIDE OF
 BEDROOM #4 AND THE GUEST BEDROOM TO MEET THE INTENT OF
 R 313.1.2 . ALSO SEE THE DEFINITION OF "SMOKE
 DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS
 OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING
 DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING
 DEVICES.
  
 10} AT LEAST ONE GFI RECEPTACLE MUST BE INSTALLED IN
 THE GARAGE FOR COMPLIANCE WITH 210.52(G).
  
 11} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEVERAL ARE
 MISSING ALONG THE COUNTER.
  
 12} A RECEPTACLE MUST BE ADDED TO THE BATH ADJACENT TO
 THE FOYER TO COMPLY WITH 210.52(D), MUST BE GFI PER
 210.8(A)(1).
  
 13} THE WHIRLPOOL PUMP RECEPTACLE MUST BE GFI PROTECTED
 PER 680.43(A)(3).
  
 14} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-02-17 Cont ID  
Sent By lwagner Date 2009-02-17 Time 16:40 Rev Time 0.00
Received By lwagner Date 2009-02-17 Time 16:11 Sent To E
Notes
2009-02-17 16:31:15************PROVISO**************
 FUTURE GENERATOR PIPING AT OWN RISK.
 SEPARATE GEN/RES PERMIT REQUIRED WITH ZONING
 APPROVAL OF GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION - 404.12
 OUTLET CLOSURES. GAS OUTLETS THAT DO NOT CONNECT
 TO APPLIANCES SHALL BE CAPPED GAS TIGHT.
 MP REGULATORS SHALL BE CONNECTED BEFORE
 FINAL INSPECTION.
  
 REVIEW BY LARRY WAGNER
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-06-17 Cont ID  
Sent By mperson Date 2008-06-17 Time 13:16 Rev Time 0.00
Received By mperson Date 2008-06-17 Time 13:16 Sent To B
Notes
2008-06-17 13:18:10****************PROVISO****************
 FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-27 Cont ID  
Sent By mperson Date 2008-05-27 Time 10:12 Rev Time 0.00
Received By mperson Date 2008-05-27 Time 10:12 Sent To B
Notes
2008-05-27 11:17:49GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET MEP-1 GAS LINE ISOMETRIC PLEASE CORRECT THE
 FOLLOWING PER FBC-2004 FUEL GAS:
  
 A} THE SUBMITTED GAS ISOMETRIC IS NOT INDICATING
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. A
 GAS PLAN REVIEW CAN NOT BE DONE UNTIL AN ACCURATE
 LONGEST LENGTH OF THE GAS SYSTEM HAS BEEN ESTABLISED.
 PLEASE REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED
 CUT SECTIONS WITH NO CORRESPONDING LENGTHS INDICATED.
 PER SECTION 401.1 SCOPE.
  
 B} PLEASE CORRELATE BTU LOAD CALCULATIONS FOR THE
 WATER HEATER. THE GAS ISOMTRIC IS INDICATING A BUT LOAD
 OF 100,000 HOWEVER THE GAS LOAD CALCULATIONS ARE
 INDICATING THE BTU LOAD FOR THE WATER HEATER AS
 250,000. PER SECTION 401.1 SCOPE.
  
 C} CLEARLY INDICATE THE GENERATOR AS BEING "FUTURE"
 AND THAT THE GAS PIPING TO THE GENERATOR SHALL BE
 CAPPED GAS TIGHT. SECTION 401.1 SCOPE AND SECTION
 404.12 OUTLET CLOSURERS. NOTE: PIPING TO A FUTURE
 GENERATOR SHALL BE AT OWN RISK UNTIL A RESIDENTIAL
 GENERATOR APPLICATION HAS BEEN APPLIED FOR AND THE
 GENERATORS LOCATION HAS BEEN APPROVED BY ZONING.
  
 D} SHEET MEP-1 "GAS NOTES"#7 STATES THAT THE
 INTERIOR MAY BE PIPED WITH CORRUGATED STAINLESS STEEL
 TUBING. PLEASE KNOW THAT YOU ARE CIRCUMVENTING YOUR
 NOTE #5 BY PUTTING THIS IN THE GAS NOTES DUE TO THE
 DIFFERENCE IN PIPING MATERIAL BTU LOAD CAPACITIES. CSST
 HAS LESS BTU LOAD CAPACITY AS SCH. 40 METALLIC PIPE. IF
 IT IS THE INTENT TO USE CSST THEN THE GAS ISOMETRIC
 SHALL CLEARLY INDICATE WHICH CUT SECTIONS ARE TO BE
 CSST AND SIZED ACCORDINGLY PER TABLE 402.4(14) OR
 DELETE NOTE #7 FROM RESUBMITTED PLANS.
 NOTE: THE CALCULATED LONGEST LENGTH WITH THE INDICATED
 CORRESPONING LENGTHS IS 97' (REFERENCE COMMENT A). THE
 GAS PLAN REVIEW WAS DONE WITH THE LONGEST LENGTH AS
 100'. PLEASE REFERENCE THE RED LINE CORRECTIONS TO THE
 GAS ISOMETRIC USING FBC-2004 FUEL GAS TABLES 402.4 (2)
 AND 402.4(20). PLEASE REFERENCE THESE GAS TABLES AS
 WELL AS THE CSST TABLE 402.4(14) ATTACHED TO THESE
 COMMENTS FOR REFERENCE FOR THE RESUBMITTAL.
  
 2. SHEET A-1 FLOOR PLAN INDICATES AN 80 GAL. GAS WATER
 HEATER IN THE GARAGE HOWEVER THERE IS NO PROTECTION
 BEING INDICATED FOR THE WATER HEATER. PLEASE INDICATE
 THE REQUIRED PROTECTION FOR THE WATER HEATER. PER
 FBC-2004 FUEL GAS SECTION 303.4 PROTECTION FROM
 PHYSICAL DAMAGE.
  
 3. SHEET A-1 PLEASE CLEARLY INDICATE THE GAS METER
 LOCATION. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. PLEASE REFERENCE MECHANICAL COMMENTS #1 AND #4 AND
 COMPLY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 16:21 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 16:21 Sent To  
Notes
2008-06-10 16:21:21TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-04 Cont ID  
Sent By lmartine Date 2008-06-04 Time 11:42 Rev Time 0.00
Received By lmartine Date 2008-05-20 Time 10:25 Sent To  
Notes
2008-05-20 10:25:45TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-02-17 Cont ID  
Sent By hmoser Date 2009-02-17 Time 16:20 Rev Time 0.00
Received By hmoser Date 2009-02-17 Time 16:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By tgordon Date 2008-06-16 Time 12:09 Rev Time 0.30
Received By tgordon Date 2008-06-16 Time 12:09 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-22 Cont ID  
Sent By tgordon Date 2008-05-22 Time 08:03 Rev Time 1.00
Received By tgordon Date 2008-05-22 Time 08:03 Sent To P
Notes
2008-05-22 08:11:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) ENERGY CALCULATIONS ARE MISSING THE JOB ADDRESS,
 JURISDICTION NUMBER, ETC. PLEASE CORRECT.
  
 3) COOLING LOAD CALCULATIONS MAY NOT BE DONE BY A WORSE
 CASE SCENARIO, BUT MUST BE DONE TO THE SPECIFIC
 BUILDINGS ORIENTATION, PER FLORIDA BUILDING COMMISSION
 DECLARATORY STATEMENT DCA06-DEC-130. PLEASE CORRECT.
  
 4) THE GAS CLOTHES DRYERS ARE IN A CONFINED SPACE
 PLEASE PROVIDE FOR COMBUSTION AIR AND MAKE UP AIR, PER
 2004 FBC/R G2407.1, G2407.4, AND G2407.5.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-17 Cont ID  
Sent By mperson Date 2008-06-17 Time 13:16 Rev Time 0.00
Received By mperson Date 2008-06-17 Time 13:16 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-27 Cont ID  
Sent By mperson Date 2008-05-27 Time 08:36 Rev Time 0.00
Received By mperson Date 2008-05-27 Time 08:36 Sent To G
Notes
2008-05-27 09:00:33PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET D-1 PLEASE ADD THE FOLLOWING TO GENERAL
 DEMOLITION NOTES:
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
  
 2. SHEET MEP-1 SANITARY RISER DIAGRAM: PLEASE CORRECT
 THE FOLLOWING ITEMS PER FBC-2004 PLUMBING.
  
 A} THE WASHING MACHNE AND LAUNDRY TRAY MUST DRAIN
 DOWNSTREAM OF WET VENTED BATHROOM #4. PER SECTION 909.1
 WET VENT PERMITTED.
  
 B} A THREE INCH CLEANOUT IS REQUIRED FOR THE WASHING
 MACHINE STACK AND IT SHALL BE LOCATED AT FOUR FEET
 ABOVE FINNISH FLOOR. PER SECTION 708.7 MINIMUM SIZE AND
 SECTION 708.9 ACCESS.
  
 C} THE BIDET IN THE MASTER BATH REQUIRES A WATER SEAL
 TRAP. PER SECTION 1002.1 TRAP REQUIRED.
  
 D} CLEARLY INDICATE THAT THE CLEANOUTS AT THE JUNCTION
 OF THE BUILDING DRAIN AND BUILDING SEWER WILL BE
 TWO-WAY CLEANOUTS. PER SECTION 708.3.5.
  
 E} CLEARLY SIZE ALL TRAPS OR PROVIDE A FIXTURE TRAP
 SIZING SCHEDULE. PER SECTION 701.1 SCOPE AND (W.P.B. AS
 AMENDED) SECTION 106.3.5.4 RESIDENTIAL (9) PLUMBING.
  
 F} THE ICE MAKER BY THE BAR SINK MAY REQUIRE A DRAIN.
 PLEASE SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR
 THE ICE MAKER AND DESIGN ACCORDINGLY IF APPLICABLE. PER
 SECTION 701.1 SCOPE.
  
 3. SHEET MEP-1 PLUMBING NOTES #11: INDICATES APPROVED
 AIR CHAMBER. AIR CHAMBERS ARE NOT APPROVED UNLESS
 INSTALLED PER STANDARD PDI-WH-201 A RECHARGEABLE TYPE
 OF AIR CHAMBER. (DETAIL REQUIRED OR DELETE AIR CHAMBERS
 ON THE RESUBMITTAL)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2008-06-04 Cont ID  
Sent By lmartine Date 2008-06-04 Time 11:46 Rev Time 0.00
Received By lmartine Date 2008-06-04 Time 11:46 Sent To  
Notes
2008-06-04 11:47:58FIRST REVIEW , FAILED STATUS WAS IN ERROR, NO REVIEW
 REQUIRED. L.MARTINEZ

Review Stop Z ZONING
Rev No 1 Status P Date 2008-06-04 Cont ID  
Sent By mcruz Date 2008-07-23 Time   Rev Time 0.00
Received By mcruz Date 2008-07-23 Time 17:00 Sent To B
Notes
***NONE***