Plan Review Details - Permit 08050460
Plan Review Stops For Permit 08050460
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 14:46 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 14:46 Sent To P
Notes
2008-05-22 14:46:35TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-19 Cont ID  
Sent By mperson Date 2008-05-19 Time 10:57 Rev Time 0.00
Received By mperson Date 2008-05-16 Time 16:39 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-29 Cont ID  
Sent By mperson Date 2008-05-29 Time 11:08 Rev Time 0.00
Received By mperson Date 2008-05-29 Time 11:08 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-19 Cont ID  
Sent By mperson Date 2008-05-19 Time 08:36 Rev Time 0.00
Received By mperson Date 2008-05-19 Time 08:36 Sent To I
Notes
2008-05-19 10:56:57PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW.
 THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE
 TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL
 CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS,
 ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND
 PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR
 PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES
 (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT
 APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
  
 2. THE PERMIT APPLICATION INDICATES "REMOVE BATHTUB
 INSTALL WALK-IN BATHTUB", HOWEVER THE SUBMITTED PLANS
 ARE NOT CLEARLY INDICATING THE BATHTUB TO BE REMOVED.
 PLANS ONLY INDICATE AN EXISTING BATHTUB AND THE
 PROPOSED WALK-IN BATHTUB. PLEASE PROVIDE AN EXISTING
 FLOOR PLAN OF UNIT #903 AND CLEARLY INDICATE WHERE THE
 PROPSED WORK IS TO DONE AND THE LOCATION OF THE BATHTUB
 TO BE REMOVED. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE DETAILS OF HOW THE DEMOED BATHTUB AND THE
 PROPOSED WALK-IN BATHTUB ARE TO BE FIRESTOPPED
 COMPLIANT WITH FBC-2004 BUILDING CHAPTER 7,
 FIRE-RESISTANCE-RATED CONSTRUCTION.
  
 4. CLEARLY INDICATE WHICH MODEL TSANGKUO INDUSTRIAL
 CO.LTD, CHROME PLATED, DECK MOUNT, SINGLE HANDLE,
 TUB/SHOWER FAUCET WITH HAND SHOWER IS BEING USED ON THE
 RESUBMITTAL. THE SUBMITTAL IS INDICATING SIX (6) MODEL
 NUMBERS. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. THE RELIANCE WATER CONTROL, HEATGUARD TMV2 DOES NOT
 CONFORM TO ASSE 1016-96. PLEASE REMOVE THIS SUBMITTAL
 ON THE RESUBMITTAL OR PROVE COMPLIANCE. PER FBC-2004
 PLUMBING SECTION 424.3 SHOWER VALVES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]