| 2008-06-05 08:32:34 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE VALUE OF THE PROJECT SPECIFIED ON THE |
| | APPLICATION IS LOW. THE VALUE HAS BEEN ADJUSTED TO |
| | $54,154.00. ADDITIONAL PERMIT FEES OF $ 740.87 ARE DUE. |
| | SEE FBC 108.3* CITY AMENDMENTS. |
| | |
| | 4) SUBMIT DETAILS FOR THE ATTACHMENT OF THE EXISTING |
| | FOUNDATION, WALLS AND TIE BEAM TO THE NEW ADDITION. FBC |
| | 106.1.2* CITY AMENDMENTS |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R806.1 VENTILATION |
| | REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| | 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. R806.2 MINIMUM AREA. |
| | THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS |
| | THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED |
| | EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED |
| | TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE |
| | THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS |
| | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| | THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| | ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE |
| | REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| | AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA |
| | MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING |
| | A TRANSMISSION RATE NOT EXCEEDING 1 PERM IS INSTALLED |
| | ON THE WARM SIDE OF THE CEILING. SPECIFY THE SIZE AND |
| | SPACING OF SOFFIT VENTS. |
| | |
| | 6) THE ENERGY CALCULATION FORM IS NOT FILLED OUT |
| | PROPERLY. THE INFORMATION ON FORM 600C-04R APPLIES ONLY |
| | TO THE ADDITION. THE INFORMATION THAT WAS ENTERED IS |
| | FOR THE WHOLE HOUSE. ALSO, THE CEILING INSULATION IS |
| | SPECIFIED ON THE PLANS AS R-30 NOT R-19. PLEASE |
| | CORRECT. SEE FBC 13-600 METHOD C. |
| | |
| | 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 8) THE PRODUCT APPROVAL NOA FOR THE FRENCH DOORS HAS |
| | BEEN REVISED BY NOA 05-1116.06. PLEASE SUBMIT THE NEW |
| | NOA. |
| | |
| | 9) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION |
| | SCHEDULE INDICATING THE MOUNT TYPE, SPANS, ANCHOR TYPE |
| | AND SPACING, EDGE DISTANCE, ETC. SEE ATTACHED SAMPLE |
| | SCHEDULE. FBC 106.1.2* CITY AMENDMENTS |
| | |