Plan Review Details - Permit 08050446
Plan Review Stops For Permit 08050446
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 11:43 Rev Time 0.00
Received By shill Date 2008-07-01 Time 11:43 Sent To  
Notes
2008-07-01 11:51:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.AS DISCUSSED, THE MANUFACTURER WAS CONTACTED AND
 HAS SEND ENGINEERING TO SHOW COMPLIANCE WITH THE 140MPH
 REQUIREMENT.HOWEVER, THE ENGINEERING SUBMITTED IS
 LACKING THE CERTIFICATE OF AUTHORIZATION FOR THE
 ENGINEER.THE ENGINEER DISAGREES WITH THIS
 REQUIREMENT.I HAVE ASKED FOR THE ENGINEER, DON
 MCGINNIS (314-469-6460) TO CONTACT FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.IF THEY AGREE THAT A
 CERTIFICATE OF AUTHORIZATION IS NOT REQUIRED, HE IS TO
 INFORM OF THE NAME OF THE PERSON HE HAS SPOKEN WITH (AT
 FBPE).OTHERWISE, HE CAN CERTIFY THE PLANS
 INDIVIDUALLY WHILE A CERTIFICATE OF AUTHORIZATION
 APPLICATION IS PENDING.
  
 THE ORIGINAL ENGINEERING AND LOCAL PRODUCT APPROVAL IS
 ON MY DESK PENDING A RESPONSE FROM THE ENGINEER.HE
 CALLED THE ENGINEER ON 6/27 AND 6/30, AND THE
 MANUFACTURER WAS EMAILED ON 6/30.ONCE THIS ISSUE IS
 ADDRESSED, THE LOCAL PRODUCT APPROVAL CAN BE ISSUED AND
 THEN THE SHED PERMIT ISSUED.
  
 ALTERNATIVELY, PROVIDE PRODUCT APPROVAL, DCA APPROVAL
 (MANUFACTURED BUILDING), OR ENGINEERING FOR A SHED
 DESIGNED FOR 140MPH.
 .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-30 Cont ID  
Sent By shill Date 2008-05-30 Time 10:49 Rev Time 0.00
Received By shill Date 2008-05-30 Time 10:49 Sent To  
Notes
2008-05-30 11:28:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE SHEET S1 OF THE MIAMIDADE NOA SUBMITTED.THIS
 PRODUCT HAS BEEN DESIGNED TO 75MPH.THE CITY OF WEST
 PALM BEACH IS IN THE 140MPH WIND ZONE, FBC R 301.
 THERE IS AN EXCEPTION IN THE HIGH VELOCITY HURRICANE
 ZONE REGARDING UTILITY SHED DESIGN; I WAS UNABLE TO
 LOCATE A SIMILAR EXCEPTION IN THE NON-HVHZ CODE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-26 Cont ID  
Sent By shill Date 2008-06-26 Time 12:40 Rev Time 0.00
Received By shill Date 2008-06-26 Time 12:40 Sent To Z
Notes
2008-06-26 12:40:43TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-30 Cont ID  
Sent By shill Date 2008-05-30 Time 11:28 Rev Time 0.00
Received By shill Date 2008-05-19 Time 08:40 Sent To  
Notes
2008-05-19 08:40:34TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-27 Cont ID  
Sent By choops Date 2008-06-27 Time 10:43 Rev Time 0.00
Received By choops Date 2008-06-27 Time 10:43 Sent To B
Notes
2008-06-27 10:44:00***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-20 Cont ID  
Sent By choops Date 2008-05-20 Time 14:36 Rev Time 0.00
Received By choops Date 2008-05-20 Time 14:36 Sent To B
Notes
2008-05-20 14:39:20***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM ALL ADJACENT
 PROPERTY LINES TO THE PROPOSED SHED.
  
 NOTE:MINIMUM REQUIRED REAR SETBACK OF 5 FEET,
 HOWEVER, PROPOSED SHED MAY NOT ENCROACH THE EXISTING 6
 FOOT UTILITY EASEMENT.
  
 2)INDICATE THE HEIGHT OF THE PROPOSED SHED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - MISC. 2