| Plan Review Stops For Permit 08050444 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
tmoore |
Date |
2008-05-23 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2008-05-29 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2008-05-29 14:30:37 | OAKY PER TOM MOORE | | 2008-05-23 13:12:41 | RECEIVEDAFFIDAVIT FROM D.K.W. ELECTRICAL CONTRACTOR | | | CONFIRMINGCIRCUITS IN QUESTION ARE NO LONGER | | | ENERGIZED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
tmoore |
Date |
2008-05-16 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2008-05-29 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2008-05-29 14:30:19 | FAILED PER TOM MOORE | | 2008-05-16 15:06:17 | 1) WALL "E" IS WEAKENED WITH VERTICAL CRACKING AS NOTED | | | ON DETAIL "F". ENGINEER WILL NEED TO CERTIFY PLANS AND | | | TO ASSURE THAT WALL "E" WILL BE ABLE TO SAFELY | | | WITHSTAND ANY LATERAL WIND FORCESIT MAY INCUR ONCE | | | THE NORTH WALL,DETAIL "C", IS REMOVED. | | | | | | 2) ELECTRICAL IS PRESENT ON THE SOUTH AND WEST WALLS OF | | | SITE PLAN. THESE CIRCUITS WILL NEED TO BE DEAD BEFORE | | | DEMOLITION. THIS CAN BE ACCOMPLISHED WITH AN ELECTRICAL | | | PERMIT, AND VERIFIED BY INSPECTION. | | | |
|
|
|