Plan Review Details - Permit 08050430
Plan Review Stops For Permit 08050430
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-26 Cont ID  
Sent By rmcdouga Date 2008-06-26 Time 09:49 Rev Time 0.00
Received By rmcdouga Date 2008-06-26 Time 09:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-06-03 Cont ID  
Sent By mperson Date 2008-05-22 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2008-06-03 Time 07:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-19 Cont ID  
Sent By btrobaug Date 2008-06-19 Time 15:34 Rev Time 0.00
Received By btrobaug Date 2008-06-19 Time 15:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-05-21 Cont ID  
Sent By btrobaug Date 2008-05-21 Time 10:53 Rev Time 0.00
Received By btrobaug Date 2008-05-21 Time 10:48 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-06-25 Cont ID  
Sent By mperson Date 2008-06-25 Time 11:16 Rev Time 0.00
Received By mperson Date 2008-06-25 Time 11:16 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-22 Cont ID  
Sent By mperson Date 2008-05-22 Time 14:22 Rev Time 0.00
Received By mperson Date 2008-05-22 Time 14:22 Sent To B
Notes
2008-05-22 14:27:53GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS (CHAPTER 41 SWIMMING POOLS), CITY OF
 WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.),
 FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA
 STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. REFERENCE PLUMBING COMMENT #3 AND COMPLY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 10:36 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 10:36 Sent To E
Notes
2008-06-19 10:36:38TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-03 Cont ID  
Sent By rmcdouga Date 2008-06-03 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2008-05-16 Time 11:30 Sent To  
Notes
2008-05-16 11:30:21TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-25 Cont ID  
Sent By mperson Date 2008-06-25 Time 11:16 Rev Time 0.00
Received By mperson Date 2008-06-25 Time 11:16 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-22 Cont ID  
Sent By mperson Date 2008-05-22 Time 13:31 Rev Time 0.00
Received By mperson Date 2008-05-22 Time 13:31 Sent To G
Notes
2008-05-22 14:16:40PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS (CHAPTER 41, SWIMMING POOLS), CITY OF
 WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.),
 FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA
 STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE PLAN DOES NOT REFLECT THE POOL SPECIFICATIONS.
 PER (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 A} THE LOCATION OF THE AUTO-FILL IS MISSING. CLEARLY
 INDICATE THE AUTO-FILL LOCATION AND ADD A NOTE THAT THE
 POTABLE WATER SUPPLY TIE-IN FOR THE AUTO-FILL SHALL BE
 BY A LICENSED PLUMBING CONTRACTOR. PER FS 489.105(3)(M)
 PLUMBING CONTRACTOR.
  
 B} CLEARLY INDICATE THE LOCATION OF THE OVERFLOW ON
 THE POOL PLAN.
  
 2. CLEARLY INDICATE THE LOCATION OF THE AQUALINK RS-6
 SYSTEM AND AQUA PURE SALT SYSTEM ON THE EQUIPMENT
 LAYOUT. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 NOTE: THE SUBMITTED MANUFACTURER'S SPECIFICATION SHEET
 FOR THE GAS POOL HEATER DOES NOT INDICATE A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY (THE
 FOLLOWING ARE EXAMPLES CSA, AGA, UL). PLEASE SUBMIT A
 SPEC. SHEET WITH A LISTING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-05-19 Cont ID  
Sent By choops Date 2008-05-19 Time 14:36 Rev Time 0.00
Received By choops Date 2008-05-19 Time 14:36 Sent To E
Notes
2008-05-19 14:37:37***APPROVED***
  
 PROVISO:
  
 FENCE ENCLOSURE MUST COMPLY WITH:
  
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.