Plan Review Details - Permit 08050423
Plan Review Stops For Permit 08050423
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-16 Cont ID  
Sent By rmcdouga Date 2008-05-16 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2008-05-16 Time 10:27 Sent To  
Notes
2008-05-16 10:50:472004 FBC W/2007 REVISIONS
 REMOVE AND REINSTALL CHILLER ON NEW STAND
  
 DENIED BY BUILDING
  
 1) SPECIFY THE EXISTING ATTACHMENT OF THE CHILLER UNIT
 TO THE 6 X 6 STEEL FRAME. FBC 1609.1.3 REQUIRES THE
 UNIT TO BE ANCHORED TO RESIST OVERTURNING, UPLIFT AND
 SLIDING.
  
 2) IF THE POINT LOADING OF THE NEW STAND WILL BE
 GREATER THAN THE GRAVITY LOADS IMPOSED BY THE ORIGINAL
 INSTALLATION, SUBMIT AN ANALYSIS FROM AN ENGINEER
 SHOWING THAT THE ROOF CAN SUPPORT THE NEW CONCENTRATED
 LOADS.
  
 3) A GENERAL CONTRACTOR WILL BE REQUIRED TO PULL THE
 PERMIT TO INSTALL THE STAND FOR THE CHILLER. FS 489.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-16 Cont ID  
Sent By rmcdouga Date 2008-05-16 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2008-05-15 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-05-15 Cont ID  
Sent By tgordon Date 2008-05-15 Time 15:06 Rev Time 0.20
Received By tgordon Date 2008-05-15 Time 15:06 Sent To B
Notes
2008-05-15 15:08:5750 TON CHILLER (600,000 BTU'S).