| 2008-05-30 16:48:05 | 2004 FBC W/2007 REVISIONS |
| | CONSTRUCT ACCESSORY STRUCTURES (R-3) |
| | |
| | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) ON SHEET #8 THERE ARE LINES ON THE ROOF FRAMING |
| | PLANS THAT APPEAR TO INDICATE A HIP ROOF. PLEASE |
| | CLARIFY. |
| | |
| | 3) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE 2 X 4 OUTLOOKERS TO THE GABLE TRUSS AND THE TIE |
| | BACK TRUSS AT THE GABLE END OVERHANGS. FBC 106.1.1* |
| | CITY AMENDMENTS. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R SECTION 704 INSPECTION |
| | FOR TERMITES |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | SPECIFY THE DISTANCE FROM FINISH GRADE TO THE WALL |
| | COVERING. |
| | |
| | 5) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE. |
| | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| | ELSEWHERE. |
| | |
| | 6) ASTM C 926 REQUIRES STUCCO APPLIED VERTICALLY OVER A |
| | METAL PLASTER BASE TO BE 7/8" THICK. PLEASE CORRECT. |
| | |
| | 7) SPECIFY THE INTERIOR WALL COVERING THAT WILL BE USED |
| | AT THE COVERED PORCH. FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 8) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1/8 |
| | INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | R806.2 MINIMUM AREA. |
| | THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS |
| | THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED |
| | EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED |
| | TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE |
| | THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS |
| | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| | THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| | ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE |
| | REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE |
| | VENTS. |
| | |
| | |
| | 9) SPECIFY THE MATERIAL THAT WILL BE USED TO COVER THE |
| | ROOF SOFFIT OVERHANGS AT CARPORT AND COVERED PATIO. FBC |
| | 106.1.1* CITY AMENDMENTS. |
| | |
| | 10) SPECIFY THE WALL COVERING MATERIAL FOR THE GABLE |
| | ENDS AT THE CARPORT. FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 11) PROVIDE A BEAM PLAN FOR THE POOL ENCLOSURE |
| | STRUCTURE. SPECIFY THE LOCATION OF THE BEAMS AND HOW |
| | THEY WILL BE ATTACHED TO THE COVERED PATIO AND EXISTING |
| | GARAGE. FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 12) SPECIFY THE ELEVATION OF THE POOL ENCLOSURE BEAMS |
| | FROM GRADE AND FINISH FLOOR. FBC 106.1.1* CITY |
| | AMENDMENTS. |
| | |
| | 13) SUBMIT PRODUCT APPROVALS FOR THE SIMPSON ECC66 |
| | CONNECTORS. DCA RULE 9B-72. |
| | |
| | IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE |
| | BEEN ADDRESSED. |
| | |