Plan Review Details - Permit 08050357
Plan Review Stops For Permit 08050357
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-11 Cont ID  
Sent By shill Date 2008-08-11 Time 14:40 Rev Time 0.00
Received By shill Date 2008-08-11 Time 14:40 Sent To  
Notes
2008-08-11 14:40:31REVIEW LETTER OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-18 Cont ID  
Sent By shill Date 2008-07-18 Time 07:56 Rev Time 0.00
Received By shill Date 2008-07-18 Time 07:55 Sent To  
Notes
2008-07-18 08:04:58**PROVISO**
  
 1. BEFORE FIRST INSPECTION, SUBMIT REVIEW BY DESIGNER
 OF RECORD FOR TENANT BUILDOUT (SMITH & MOORE).
  
 2.AT RISK PERMIT (PENDING PROVISO).
  
 3.A CO HOLD HAS BEEN PLACED ON THIS PERMIT PENDING
 RECEIPT OF LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-17 Cont ID  
Sent By shill Date 2008-07-17 Time 13:32 Rev Time 0.00
Received By shill Date 2008-07-17 Time 13:32 Sent To  
Notes
2008-07-17 13:46:41****CORRECTIONS****
 ****REVISED 6/23/8****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.AS THE BASE BUILDING HAS NOT OBTAINED A C.C. OR
 C.O, PLEASE HAVE THE DESIGNER OF THE BASE BUILDING
 (SMITH & MOORE) REVIEW THE PLANS.THIS CAN BE DONE
 WITH A SHOP DRAWING REVIEW STAMP OR A LETTER.
  
 NOT ADDRESSED. PLEASE EITHER SUBMIT THE LETTER OR THE
 PERMIT CAN BE ISSUED WITH THIS PROVISO, AT CONTRACTOR'S
 RISK, BUT PLEASE ADVISE ME IF YOU WISH TO HAVE THIS
 OPTION.
  
 2-4.ADDRESSED.
  
 5.SUITE 100 IS ALREADY IN USE BY ANOTHER TENANT
 (ISSUED PERMIT).PLEASE REVISE SUITE NUMBER ON THE
 PLANS AND ON THE APPLICATION.
  
 2ND REVIEW, THIS MAY BE REVISED BY HAND.NO NEW SHEETS
 ARE REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-03 Cont ID  
Sent By shill Date 2008-06-03 Time 09:44 Rev Time 0.00
Received By shill Date 2008-06-03 Time 09:44 Sent To  
Notes
2008-06-03 09:46:54****CORRECTIONS****
 ****REVISED 6/23/8****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.AS THE BASE BUILDING HAS NOT OBTAINED A C.C. OR
 C.O, PLEASE HAVE THE DESIGNER OF THE BASE BUILDING
 (SMITH & MOORE) REVIEW THE PLANS.THIS CAN BE DONE
 WITH A SHOP DRAWING REVIEW STAMP OR A LETTER.
  
 2.GOVERNING CODE, LS1.0, SHOULD INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 3.ON THE LIFE SAFETY PLAN, PLEASE SHOW FIRE
 RESISTANCE RATING TO THE EXITS ON THE EAST SIDE,
 FBC1002.TRAVEL DISTANCE HAS BEEN MEASURED TO THE
 DOORS TO THE SPACE, BUT IT IS NOT CLEAR WHERE THE EXIT
 DISCHARGE FOR THE NORTH DOOR (FOR THE SPACE, APPARENTLY
 LEADING TO THE EAST EXIT).TRAVEL DISTANCE HAS BEEN
 SHOWN MEASURED TO THE DOOR TO THE SPACE, BUT FIRE
 RESISTANCE RATING TO THE EXIT DISCHARGE HAS NOT BEEN
 SHOWN.
  
 4.PROVIDE A DETAIL FOR THE ACCESSIBLE SINK, FBC
 11-4.24.PLEASE PROVIDE ALL DIMENSIONS AS REQUESTED BY
 THE PLUMBING REVIEWER.
  
 5.SUITE 100 IS ALREADY IN USE BY ANOTHER TENANT
 (ISSUED PERMIT).PLEASE REVISE SUITE NUMBER ON THE
 PLANS AND ON THE APPLICATION.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-07 Cont ID  
Sent By dpalmer Date 2008-10-07 Time 11:05 Rev Time 0.00
Received By dpalmer Date 2008-10-07 Time 10:51 Sent To PC
Notes
2008-10-07 11:08:17REVISED CIRCUITING

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-03 Cont ID  
Sent By dpalmer Date 2008-07-03 Time 14:10 Rev Time 0.00
Received By dpalmer Date 2008-07-03 Time 14:10 Sent To  
Notes
2008-07-03 14:11:35WILL NEED TO REVISE BASE BUILDING PLANS, CALCULATIONS
 AND ENREGY CALCULATIONS WITH ALL KNOWNS BEFORE FINAL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 18:50 Sent To  
Notes
2008-06-03 18:50:27** DENIED**
  
  
 1) NOTE:PLEASE SEE THE LIGHTING WHICH IS BEING SHOWN
 ON ELECTRICAL LIGHTING PLANS NOTED WITH NOTE #4 SHALL
 NOT HAVE PROVISIONS FOR FUTURE LIGHTS. BASED ON THE
 METHOD OF CALCULATIONS SUBMITTED ALONG WITH THE MAXIMUM
 ALLOWED WATTAGE AS SHOWN THESE LIGHT FIXTURES WOULD
 PLACED THE ALLOWANCE WAY OVER THE TABLE ALLOWANCE AND
 PERMITTED WATTAGE CONSUMPTION PER 13-415.2.ABC.1.1,
 .1.2, 13-415.2.C.
 PLEASE ADJUST PLANS AND PLEASE REMOVED FIXTURES. THE
 DESIGN OF FIXTURES, NUMBER OF FIXTURES, WATTAGE OF
 FIXTURES ETC MAY BE REVISED, HOWEVER MAT NOT BE DONE AS
 SHOWN.
 PLEASE ALSO KNOW THE *ALTERNATE LIGHTING* SHOWN ON E0.1
 IS NOT PART OF THE DESIGN AT THIS TIME. IF THIS IS
 GOING TO BE USED THEN PLANS NEED TO BE REVISED
 ACCORDINGLY.
  
 2) NOTE: PLEASE VERIFY ACTUAL ROOM DESIGNATION FOR
 IT/PHONE ROOM #123. IF THIS IS ACTUALLY AN IT ROOM THEN
 PLEASE SHOW COMPLIANCE WITH 645 OF THE NEC. IF THIS NOT
 AN IT ROOM PLEASE REMOVE THE IT DESIGNATION.
  
 3) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS
 COORDINATES WITH THE SUBMITTED PANEL SCHEDULES.
 PLEASE SUBMIT OTHER PANEL SCHEDULES FOR ITEMS LISTED ON
 PLANS, BUT NO SCHEDULE SUBMITTED.
 FOR EXAMPLE:
 PLEASE SEE ROOM 125, CIRCUIT SHOWN TO PANEL HA-7 YET NO
 HA PANEL WAS SUBMITTED.
  
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: REDLINED MDP AS DONE ON BASE BUILDING PLANS AS
 THIS IS SHOWN WITH GFCI PROTECTION WHEN IN FACT THIS IS
 GFP PER 240.13, 230.95.
  
  
 5) NOTE: ELECTRICAL RISER AS SHOWN ON E5.1 IS SHOWN AS
 EXISTING AND IS NOT REVIEWED FOR CODE COMPLIANCE.
 BASE BUILDING IS YET TO RECEIVE CO.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-11 Cont ID  
Sent By mwennerg Date 2008-07-11 Time 14:23 Rev Time 0.00
Received By mwennerg Date 2008-07-11 Time 14:23 Sent To  
Notes
2008-07-11 14:24:35STAMPED SHEETS LS0.1, FA0.1 AND FA2.1

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By mwennerg Date 2008-06-04 Time 10:20 Rev Time 0.00
Received By mwennerg Date 2008-06-04 Time 10:20 Sent To  
Notes
2008-06-04 10:24:33***DENIED***
  
 1) SINCE THE FIRE SPRINKLER SYSTEM WILL BE ALTERED,
 PLEASE ADD NFPA 13, 2002 EDITION TO BUILDING CODE
 CLASSIFICATION.
  
 2) UL LISTED CLOSERS ARE REQUIRED ON FIRE RATED DOORS.
 PLEASE ADD TO DOOR SCHEDULE.
  
 3) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS USING CLASS A,B OR C.
  
 4) SHEET LS1.0 ILLUSTRATES AN EXIT SIGN AT OPEN OFFICE
 117 THAT IS NOT SHOWN ON SHEET E2.1. PLEASE CORRELATE
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-10-01 Cont ID  
Sent By adarroug Date 2008-10-01 Time 10:01 Rev Time 0.00
Received By adarroug Date 2008-10-01 Time 10:01 Sent To M
Notes
2008-10-01 10:01:40TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-10-01 Cont ID  
Sent By adarroug Date 2008-10-01 Time 10:00 Rev Time 0.00
Received By adarroug Date 2008-10-01 Time 10:00 Sent To M
Notes
2008-10-01 10:00:53TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 16:58 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 16:58 Sent To M
Notes
2008-09-29 16:58:31TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 16:55 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 16:55 Sent To E
Notes
2008-09-29 16:55:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-22 Cont ID  
Sent By rregueir Date 2008-08-22 Time 13:02 Rev Time 0.00
Received By rregueir Date 2008-08-22 Time 13:01 Sent To  
Notes
2008-08-22 13:01:39TO RJR DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-31 Cont ID  
Sent By adarroug Date 2008-07-31 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-07-31 Time 10:51 Sent To B
Notes
2008-07-31 10:52:07TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 10:48 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 10:46 Sent To  
Notes
2008-06-16 10:49:01TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-04 Cont ID  
Sent By mwennerg Date 2008-06-04 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2008-05-14 Time 14:57 Sent To  
Notes
2008-05-14 15:02:52TO "COMM" BD#20

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-10-11 Cont ID  
Sent By rregueir Date 2008-10-10 Time 11:07 Rev Time 0.00
Received By rregueir Date 2008-10-10 Time 11:11 Sent To PC
Notes
2008-10-11 11:07:19PAGE M2.2 REV.3; PAGES M0.1 AND M2.1 REV.4.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-08-22 Cont ID  
Sent By rregueir Date 2008-08-22 Time 13:14 Rev Time 0.00
Received By rregueir Date 2008-08-22 Time 13:08 Sent To PC
Notes
2008-08-22 13:13:58REVISED PAGE M2.2 DENIED.
  
 ORIGINAL PERMIT SET OF PLANS WERE SIGNED ANDD SEALED BY
 ROBERT KAMM. THE PRINTED LICENSE # AND NAME OF ROBERT
 KAMM STILL APPEARS IN THE TITLE BLOCK ON THE REVISED
 PLANS, BUT THEY WERE NOT SIGNED OR SEALED BY ROBERT
 KAMM.
  
 PLEASE RESUBMIT REVISED PLANS SIGNED AND SEALED BY THE
 DESIGNER OF RECORD OR FOLLOW THE PROCEDURES FOR
 CHANGING THE DESIGNER OF RECORD IN ACCORDANCE WITH FAC
 RULE 6IG15. ALSO, THE PRINTED NAME AND LICENSE NUMBER
 OF THE PERSON SIGNING AND SEALING THE PLANS SHALL
 APPEAR IN THE TITLE BLOCK IN ACCORDANCE WITH THE SAME
 RULE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-03 Cont ID  
Sent By rregueir Date 2008-07-03 Time 13:29 Rev Time 0.00
Received By rregueir Date 2008-07-03 Time 13:22 Sent To  
Notes
2008-07-03 13:22:50PREVIOUS REVIEW PASSED. ALL NEW SHEETS FOR THIS REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-06-02 Cont ID  
Sent By rregueir Date 2008-06-02 Time 13:36 Rev Time 0.00
Received By rregueir Date 2008-06-02 Time 11:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-14 Cont ID  
Sent By kstevens Date 2008-07-14 Time 15:28 Rev Time 0.00
Received By kstevens Date 2008-07-14 Time 15:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-02 Cont ID  
Sent By kstevens Date 2008-06-02 Time 08:58 Rev Time 0.00
Received By kstevens Date 2008-06-02 Time 08:58 Sent To  
Notes
2008-06-02 09:39:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
  
 1. SHT A3.0, DETAIL 10. SHOW COMPLIANCE WITH THE
 FOLLOWING FOR THE SINK.
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 2. SHT P0.1 THE WATER RISER DIAGRAM DOES NOT RELFECT
 THE FLOOR PLAN. SEE SHT A3.0 DETAIL 10 AS IT SHOWS A
 REFRIGERATOR ON THE RIGHT SIDE OF THE SINK AND AN ICE
 MAKER ON THE LEFT SIDE OF THE SINK. PLEASE SHOW BOTH ON
 THE RISER DIAGRAM. ALSO THE RISER IS SHOWING THE COLD
 SUPPLY ON THE LEFT SIDE OF THE SINK AND THE HOT SUPPLY
 ON THE RIGHT SIDE OF THE SINK. SECTIONS 106.1.1 &
 607.4.--THE HOT WATER TO THE DISHWASHER REQUIRES A
 WATER HAMMER ARRESTOR PER SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  