Plan Review Details - Permit 08050355
Plan Review Stops For Permit 08050355
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-05-16 Cont ID  
Sent By rbrown Date 2008-05-16 Time 09:55 Rev Time 0.00
Received By rbrown Date 2008-05-16 Time 09:55 Sent To  
Notes
2008-05-16 09:57:07STRUCTURAL SHOP DRAWINGS FOR WATER FEATURE.STAMPED AS
 APPROVED BY STRUCTURAL ENGINEER OF RECORD.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-15 Cont ID  
Sent By jleahy Date 2008-05-15 Time 11:00 Rev Time 1.00
Received By jleahy Date 2008-05-15 Time 10:53 Sent To B
Notes
2008-05-15 11:00:131. PANEL SCHEDULE SHOWS SINGLE POLE 30 BREAKER, BUT
 PUMP IS LISTED AS 208V WHICH REQUIRES A TWO POLE
 BREAKER.
  
 2. PANEL SCHEDULE ALSO SHOWS A SINGLE POLE 20A BREAKER
 FOR PUMP?
  
 3. NO CIRCUIT SHOWN FOR QUAD RECP. AND FOR TIME CLOCK.
  
 4. A THREE PHASE PUMP IS SHOWN BUT BREAKER IS SHON FOR
 IT.
  
 PLEASE INDICATE ON DRAWINGS THE CIRCUIT THAT FEEDS EACH
 PIECE OF EQUIPMENT. PUMPS, RELAYS TIME CLOCK, ECT ECT,
 AT THE EQUIPMENT ON PLAN
  
 THANKS
  
 JAKE LEAHY644-7291

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-14 Cont ID  
Sent By kstevens Date 2008-05-14 Time 15:28 Rev Time 0.00
Received By kstevens Date 2008-05-13 Time 14:31 Sent To  
Notes
2008-05-13 14:31:34TO "JLEECH" DESK/PER "RBROWN"

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-05-14 Cont ID  
Sent By kstevens Date 2008-05-14 Time 16:05 Rev Time 0.00
Received By kstevens Date 2008-05-14 Time 16:05 Sent To B
Notes
***NONE***