Plan Review Details - Permit 08050294
Plan Review Stops For Permit 08050294
Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2008-05-12 Cont ID  
Sent By swurafti Date 2008-05-12 Time 11:10 Rev Time 0.00
Received By swurafti Date 2008-05-12 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-11 Cont ID  
Sent By adarroug Date 2008-06-11 Time 11:22 Rev Time 0.00
Received By adarroug Date 2008-06-11 Time 11:22 Sent To P
Notes
2008-06-11 11:22:46TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-21 Cont ID  
Sent By mperson Date 2008-05-21 Time 16:40 Rev Time 0.00
Received By mperson Date 2008-05-20 Time 13:39 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-13 Cont ID  
Sent By mperson Date 2008-05-13 Time 14:40 Rev Time 0.00
Received By mperson Date 2008-05-12 Time 16:38 Sent To PC
Notes
2008-05-12 16:39:04SENT TO "P" MRP.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-12 Cont ID  
Sent By mperson Date 2008-06-12 Time 09:09 Rev Time 0.00
Received By mperson Date 2008-06-12 Time 09:09 Sent To PC
Notes
2008-06-12 09:11:39RESTAMP PLANS AND DUPLICATE PERMIT "OK"

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-21 Cont ID  
Sent By mperson Date 2008-05-22 Time 08:24 Rev Time 0.00
Received By mperson Date 2008-05-21 Time 16:23 Sent To I
Notes
2008-05-21 16:39:59****************PROVISO****************
 NOTE: FIRE STOPPING FOR PVC PIPE PENATRATIONS PER
 APPROVED MASTER PERMIT #07060772 SHEET A-5 DETAILS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-13 Cont ID  
Sent By mperson Date 2008-05-13 Time 11:21 Rev Time 0.00
Received By mperson Date 2008-05-13 Time 11:20 Sent To I
Notes
2008-05-13 14:40:02PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE VALUE FOR THE REPLACEMENT OF OLD CAST-IRON
 DRAINAGE W/ SCHEDULE 40 PVC PIPE APPEAR LOW. PROVIDE A
 SIGNED COPY OF THE CONTRACT BY 24 ST. HOLDINGS, LLC AND
 KDN CONSTRUCTION SERVICES, LLC WITH THE CONTRACT
 AMOUNT. NOTE: FIRESTOPPING WILL BE REQUIRED FOR ALL PVC
 PIPE PENATRATIONS IN FIREWALL AND FLOOR PENATRATIONS
 AND NEEDS TO BE INCLUDED IN CONTRACT AS WELL AS WALL
 AND FLOOR DEMO. ALSO CLEARLY INDICATE ON THE PLANS IF
 THE EXISTING FIXTURES ARE BEING REUSED OR IF NEW
 FIXTURES ARE BEING PROVIDED.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED.
 VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 *NOTE: PERMIT #07060772 COM/REMOD FOR SAID ADDRESS
 DOES NOT INCLUDE ANY PROVISIONS OF ANY PLUMBING WORK
 BEING DONE AND A REVISION MAY BE REQUIRED FOR THIS
 ADDED PLUMIBNG WORK.
  
 2. THE SUBMITTED FLOOR PLAN IS NOT INDICATING ANY
 EXISTING AUTOMATIC CLOTHES WASHER CONNECTIONS. PER
 FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES, OCCUPANCY (R-2), 1
 AUTOMATIC CLOTHES WASHER CONNECTION PER 20 DWELLING
 UNITS IS REQUIRED. PLEASE COMPLY ON RESUBMITTAL AND
 CLEARLY INDICATE IF THE REQUIRED AUTOMATIC CLOTHES
 WASHER CONNECTION IS EXISTING OR NEW. ALSO ADJUST THE
 RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM TO INCLUDE
 THE REQUIRED WASHER CONNECTION PER THE FOLLOWING.(A)
 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 *NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE 3
 INCH.
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 *NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT 4' A.F.F.
  
 3. CLEANOUTS ARE REQUIRED PER FBC-2004 PLUMBING THE
 FOLLOWING SECTIONS.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 *NOTE: CLEARLY INDICATE A TWO-WAY CLEANOUT BEING USED
 AT THIS LOCATION.
  
 4. WATER SEAL TRAPS ARE REQUIRED AND NEED TO BE
 CLEARLY INDICATED FOR THE FOLLOWING FIXTURES ON THE
 RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM. PER
 FBC-2004 PLUMBING SECTION 1002.1 FIXTURE TRAPS.
  
 A} KITCHEN SINK.
 B} LAVATORY.
 C} SHOWER.
  
 5. THE FIRST FLOOR BACK TO BACK BATHROOMS ARE NOT
 VENTED DUE TO THE VENT BEING TIED BACK INTO THE
 DRAINAGE STACK FOR THE SECOND FLOOR. THE VENT FROM THE
 FIRST FLOOR BACK TO BACK BATHROOMS MUST EXTEND THROUGH
 THE SECOND FLOOR AND TIE INTO THE SECOND FLOOR VENT 6
 INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR
 TRAPPED FIXTURE BEING VENTED (LAVATORY). PER FBC-2004
 PLUMBING SECTION 905.4 VERTICAL RISE OF VENT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]