| 2008-05-13 14:40:02 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE VALUE FOR THE REPLACEMENT OF OLD CAST-IRON |
| | DRAINAGE W/ SCHEDULE 40 PVC PIPE APPEAR LOW. PROVIDE A |
| | SIGNED COPY OF THE CONTRACT BY 24 ST. HOLDINGS, LLC AND |
| | KDN CONSTRUCTION SERVICES, LLC WITH THE CONTRACT |
| | AMOUNT. NOTE: FIRESTOPPING WILL BE REQUIRED FOR ALL PVC |
| | PIPE PENATRATIONS IN FIREWALL AND FLOOR PENATRATIONS |
| | AND NEEDS TO BE INCLUDED IN CONTRACT AS WELL AS WALL |
| | AND FLOOR DEMO. ALSO CLEARLY INDICATE ON THE PLANS IF |
| | THE EXISTING FIXTURES ARE BEING REUSED OR IF NEW |
| | FIXTURES ARE BEING PROVIDED. |
| | PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. |
| | VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | *NOTE: PERMIT #07060772 COM/REMOD FOR SAID ADDRESS |
| | DOES NOT INCLUDE ANY PROVISIONS OF ANY PLUMBING WORK |
| | BEING DONE AND A REVISION MAY BE REQUIRED FOR THIS |
| | ADDED PLUMIBNG WORK. |
| | |
| | 2. THE SUBMITTED FLOOR PLAN IS NOT INDICATING ANY |
| | EXISTING AUTOMATIC CLOTHES WASHER CONNECTIONS. PER |
| | FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF |
| | REQUIRED PLUMBING FIXTURES, OCCUPANCY (R-2), 1 |
| | AUTOMATIC CLOTHES WASHER CONNECTION PER 20 DWELLING |
| | UNITS IS REQUIRED. PLEASE COMPLY ON RESUBMITTAL AND |
| | CLEARLY INDICATE IF THE REQUIRED AUTOMATIC CLOTHES |
| | WASHER CONNECTION IS EXISTING OR NEW. ALSO ADJUST THE |
| | RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM TO INCLUDE |
| | THE REQUIRED WASHER CONNECTION PER THE FOLLOWING.(A) |
| | 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | *NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 |
| | INCH. |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | *NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | LOCATED AT 4' A.F.F. |
| | |
| | 3. CLEANOUTS ARE REQUIRED PER FBC-2004 PLUMBING THE |
| | FOLLOWING SECTIONS. |
| | (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| | SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK |
| | (B) 708.3.5 BUILDING DRAIN AND BUILDING |
| | SEWER JUNCTION. THERE SHALL BE A TWO-WAY |
| | CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | *NOTE: CLEARLY INDICATE A TWO-WAY CLEANOUT BEING USED |
| | AT THIS LOCATION. |
| | |
| | 4. WATER SEAL TRAPS ARE REQUIRED AND NEED TO BE |
| | CLEARLY INDICATED FOR THE FOLLOWING FIXTURES ON THE |
| | RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM. PER |
| | FBC-2004 PLUMBING SECTION 1002.1 FIXTURE TRAPS. |
| | |
| | A} KITCHEN SINK. |
| | B} LAVATORY. |
| | C} SHOWER. |
| | |
| | 5. THE FIRST FLOOR BACK TO BACK BATHROOMS ARE NOT |
| | VENTED DUE TO THE VENT BEING TIED BACK INTO THE |
| | DRAINAGE STACK FOR THE SECOND FLOOR. THE VENT FROM THE |
| | FIRST FLOOR BACK TO BACK BATHROOMS MUST EXTEND THROUGH |
| | THE SECOND FLOOR AND TIE INTO THE SECOND FLOOR VENT 6 |
| | INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR |
| | TRAPPED FIXTURE BEING VENTED (LAVATORY). PER FBC-2004 |
| | PLUMBING SECTION 905.4 VERTICAL RISE OF VENT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |