| 2008-05-14 09:03:33 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.SEE THE DOCUMENTS SUBMITTED.AS DISCUSSED WITH |
| | BOTH CONTRACTOR AND MANUFACTURER, THIS IS A ROOF |
| | MEMBRANE.ROOFING WORK IS NOT WITHIN THE SCOPE OF A |
| | GENERAL CONTRACTOR LICENSE, FS489.I CALLED THE STATE |
| | OF FLORIDA, DBPR, AND THEY WERE ABSOLUTELY ADAMANT THAT |
| | THIS WAS NOT WITHIN THE SCOPE OF A GC LICENSE.AS |
| | DISCUSSED WITH MR. NORDINE, PLEASE PROVIDE A LETTER |
| | FROM THE STATE STATING THAT A GENERAL CONTRACTOR CAN DO |
| | THIS WORK.OTHERWISE, HAVE A CONTRACTOR LICENSED TO DO |
| | THIS WORK APPLY FOR THE PERMIT.THE LETTER PROVIDED BY |
| | THE CONTRACTOR IS A LETTER FROM THE MANUFACTURER |
| | STATING THAT ALL INSPECTIONS BY THE MANUFACTURER WILL |
| | BE DONE BY A LICENSED ROOFING CONTRACTOR.ANY LETTER |
| | REGARDING THIS ISSUE MUST BE PROVIDED BY AN ENTITY |
| | WHICH HAS DECISION MAKING AUTHORITY REGARDING THIS |
| | ISSUE (ROOFING MEMBRANE INSTALLATIONS PERFORMED BY |
| | GENERAL CONTRACTOR). |
| | |
| | 2.FBC*108.3 BUILDING PERMIT VALUATION. A VALUE |
| | ADJUSTMENT HAS BEEN DONE AS PER MARSHALL & SWIFT, |
| | AVERAGE OF $5.50/SF, ELASTOMERIC SYSTEM. |
| | |
| | 3.IN ORDER TO CLARIFY SCOPE OF WORK FOR THIS PERMIT |
| | FOR DOCUMENTATION PURPOSES, PLEASE PROVIDE A COPY OF |
| | THE SURVEY AND SHOW LOCATION OF WORK TO BE DONE. |
| | PROPERTY APPRAISER RECORDS SHOW TWO STRUCTURES ON THIS |
| | PARCEL AND SQUARE FOOT AREA IS NOT CLEAR. |