| Plan Review Stops For Permit 08050216 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-09-15 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-09-15 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-09-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-09-03 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-09-03 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2008-09-03 14:18:55 | 2004 FBC W/2007 REVISIONS | | | METAL SHELTER | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE METAL | | | ROOF COVERING WITH ADEQUATE DESIGN PRESSURES. TWO | | | COPIES OF THE EVALUATION REPORT WITH DESIGN PRESSURE | | | SPECIFIED AND INSTALLATION INSTRUCTIONS ARE REQUIRED. | | | SEE FAC RULE 9B-72 AND FBC 106.1* CITY AMENDMENTS. THE | | | STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND HAS A | | | 4:12 ROOF SLOPE, WHICH REQUIRES A ROOFING PRODUCT WITH | | | A DESIGN PRESSURE CAPABLE OF RESISTING AN UPLIFT OF | | | 100.5 PSF AT ROOF ZONE 3. SEE FBC TABLES 1609.6.2.1(2) | | | AND 1609.6.2.1(4). REPEAT COMMENT. | | | | | | 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | REPEAT COMMENT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-07-28 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-07-28 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2008-07-28 14:35:06 | 2004 FBC W/2007 REVISIONS | | | METAL SHELTER | | | | | | DENIED BY BUILDING | | | | | | 1) THE SET-UP INSTRUCTIONS SPECIFY THE ROOF PANELS AS | | | 24 GA. MEDALLION-LOK STEEL PANELS MANUFACTURED BY | | | MCELROY METAL, INC. THERE WERE NO PRODUCT APPROVALS FOR | | | THE ROOF PANELS SUBMITTED AS REQUESTED IN ITEM #4 OF | | | THE PREVIOUS PLAN REVIEW. THEREFORE, THE MIAMI-DADE | | | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FOR | | | THIS PRODUCT (NOA NO. 08-0225.03) WAS USED TO DETERMINE | | | THE DESIGN PRESSURES FOR THE METAL ROOF. THE MAXIMUM | | | DESIGN PRESSURE FROM THE NOA IS -71.25 PSF, WITH NO | | | EXTRAPOLATION ALLOWED. THIS DESIGN PRESSURE IS NOT | | | ADEQUATE TO RESIST THE REQUIRED UPLIFT FOR COMPONENT | | | AND CLADDING FOR A 4:12 SLOPE ROOF IN EXPOSURE CATEGORY | | | C. SEE FBC TABLE 1609.6.2.1(2) AND ADJUSTMENT FACTORS | | | TABLE 1609.6.2.1(4). PLEASE PROVIDE PRODUCT APPROVALS | | | FOR ROOF COVERING WITH ADEQUATE DESIGN PRESSURES. SEE | | | DCA RULE 9B-72. | | | | | | 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | SEE PREVIOUS REVIEW COMMENT # 5. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-05-15 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-05-15 |
Time |
10:25 |
Sent To |
Z |
|
| Notes |
| 2008-05-15 11:19:53 | 2004 FBC W/2007 REVISIONS | | | STEEL SHELTER | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) SUBMIT SIGNED AND SEALED SOIL REPORTS. FBC 1802.1 | | | | | | 3) SUBMIT SIGNED AND SEALED FOUNDATION, STRUCTURAL, | | | ETC. PLANS FOR THE STEEL BUILDING FROM A DESIGN | | | PROFESSIONAL. SEE FBC 106.1* AND 106.3.5* CITY | | | AMENDMENTS. | | | | | | 4) SUBMIT PRODUCT APPROVALS FOR STRUCTURAL COMPONENTS | | | AND SYSTEMS THAT COMPRISE THE BUILDING ENVELOPE AS | | | REQUIRED BY FAC RULE 9B-72. | | | | | | 5) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-09-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-12 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-12 |
Time |
11:13 |
Sent To |
B |
|
| Notes |
| 2008-09-12 11:14:05 | TO "RMCDOUGAL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-28 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-08-28 |
Time |
13:51 |
Sent To |
B |
|
| Notes |
| 2008-08-28 13:52:22 | TO "BUILD"ROBERT M. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-22 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-22 |
Time |
09:44 |
Sent To |
Z |
|
| Notes |
| 2008-07-22 09:44:41 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-05-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-08 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2008-05-08 11:23:40 | TO "Z" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-07-24 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-07-24 |
Time |
23:10 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-07-24 |
Time |
23:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-05-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-05-30 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-05-30 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2008-05-30 11:34:27 | ***FAILED*** | | | | | | 1) ELEVATIONS SHALL BE PROVIDED SHOWING THE PROPOSED | | | SHELTER, BUILDING HEIGHT, ETC.NO ARCHITECTURAL | | | DRAWINGS WERE INCLUDED WITHIN THE PERMIT PACKAGE. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|