Plan Review Details - Permit 08050211
Plan Review Stops For Permit 08050211
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-30 Cont ID  
Sent By jwitmer Date 2008-09-30 Time 13:11 Rev Time 0.77
Received By jwitmer Date 2008-09-30 Time 13:11 Sent To  
Notes
2008-09-30 13:12:38REVISION "C" SHEETS A8, A9 & A10

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-09 Cont ID  
Sent By jwitmer Date 2008-07-09 Time 07:26 Rev Time 0.77
Received By jwitmer Date 2008-07-09 Time 07:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-29 Cont ID  
Sent By jwitmer Date 2008-05-29 Time 09:05 Rev Time 1.33
Received By jwitmer Date 2008-05-29 Time 08:30 Sent To PC
Notes
2008-05-29 09:32:13BUILDING PLAN REVIEW
 PERMIT: 08050211
 ADD: 1450 CENTREPARK BLVD SUITES 150-155
 CONT: ANDERSON-MOORE
 TEL: (561)753-7400 / CELL(ROSE) 662-1819
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) SHEET A2 INDICATES WORK BEING COMPLETED WITHIN
 CORRIDOR 107 ADDING WALLS, GLAZED WALL PANEL (SIDE
 LIGHT) AND A DOORWAY.THE FIRST ISSUE IS THE PLAN WILL
 NEED TO IDENTIFY THE HEIGTH OF THE BUILDING
 THIS PACTULAR STAIRWAY IS SERVING. THE CORRIDOE 107 IS
 IN ACTUALLITY A CONTINUATION OF THE VERTICAL STAIRWELL
 IT IS CONTECTED TO CREATING AN EXIT PASSAGEWAY. IF THE
 VERTICAL EXIT IS 4 STORIES OR MORE THAN THIS
 EXIT PASSAGEWAY WOULD REQUIRE 2 HR WALLS, IF LESS THAN
 4 STORIES IT WOULD ONLY REQUIRE 1 HR WALLS. WITH THIS
 UNKNOWN THE NEW DOORWAY B MAYREQUIRE A 45 MINUTE DOOR
 FOR LESS THAN 4 STORIES OR A 1 1/2 HR DOOR IF THE
 STAIRWELL SERVES 4 STORIES OR MORE. 707.4 SHAFT
 ENCLOSURES/ TABLE 715.3.
  
 3) SHEET A2 CORRIDOR 107 DOORWAY B AND THE NEW SIDE
 LIGHT. DEPENDING ON THE HEIGTH OF THE BUILDING AND
 STAIRWELL THE REQUIRMENTS FOR THE SIDELIGHT WILL NEED
 TO MEET THE REQUIREMENTS OF
 TABLE 715.4.TABLE 715.4 PRESCRIBES THE MINIMUM FIRE
 PROTECTION RATINGS FOR FIRE WINDOWS, WHICH ARE NOT TO
 BE CONFUSED WITH THE RATINGS FOR FIRE DOORS PROVIDED IN
 TABLE 715.3 RELATIVE TOTHE NATURE AND FIRE-RESISTANCE
 RATING OF THE WALL.
  
 4) SHEET A-5 PLEASE NOTE THE REQUIREMENTS FOR REACH
 RANGES FOR THE MICROWAVE PLEASE REVIEW SECTION
 11-4.27.3 ,11-4.2.5 & 11-4.2.6.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-08 Cont ID  
Sent By dpalmer Date 2008-07-08 Time 16:05 Rev Time 0.00
Received By dpalmer Date 2008-07-08 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-27 Cont ID  
Sent By dpalmer Date 2008-05-27 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2008-05-27 Time 11:15 Sent To  
Notes
2008-05-27 11:15:45** DENIED REVIEW **
  
 1) NOTE: PLEASE LABEL SUITE/UNITS ON RISER TENANT
 MAINS.
 230.2E.
  
 2) NOTE: PLEASE VERIFY HOW METHOD *C* IS BEING USED
 WHEN NOT PLACING ALL INFORMATION IN THE INPUT DATA
 REPORT FOR ALL AREAS OF SPACES.
 FOR EXAMPLE:
 PLANS SHOW TWO SUITES/UNITS AND YET THE IDR DOES NOT
 CONTAIN ALL AREAS ROOMS FROM THE PLANS?
 PLEASE SEE SQUARE FEET ON THE CALCULATIONS INDICATE
 BOTH SPACES YET THE LIGHTING ON THE IDR DOES NOT
 INCLUDE BOTH.
 BASED ON THE LIGHTING ON PLANS THE MAXIMUM WATTAGE
 APPEARS IT WILL EXCEED TABLE *C*.
 PLEASE ALSO SEE ONE ROOM FOR EXAMPLE IN SUITE #150:
 OFFICE 104, WELL EXCEEDS THE ALLOWANCES OF TABLE
 13-415.2.C FOR OFFICE AREAS.
 ** PLEASE ADJUST FIXTURE TYPES, WATTAGES ETC IN ORDER
 TO BE BELOW. PLEASE KNOW IN ORDER TO ADD OR CONTAIN
 LIGHTING IN ADDITION TO OTHER EXISTING AREAS, IT MAY BE
 REQUIRED TO CHANGE OTHER FIXTURES OR PERHAPS MINIMUM
 FOR SPACE BY SPACE.
 13-415.2.ABC.1.1, .1.2
 ** PLEASE BE SURE THE OWNER AGENT IS FILLED OUT ON THE
 CERTIFICATION SHEET.
  
 3) NOTE: PLEASE LIST THE MAXIMUM TIMES ON OCCUPANCY
 SENSOR DEVICES.
 13-415.1.ABC.1.1,.1.2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 13:36 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 13:36 Sent To  
Notes
2008-07-21 13:37:38PLANS PREVIOUSLY APPROVED AND STAMPED. NEW SHEET A-2
 STAMPED. SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-05-28 Cont ID  
Sent By mwennerg Date 2008-05-28 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2008-05-28 Time 15:30 Sent To  
Notes
2008-05-28 15:38:45***PROVISO***
  
 1) EXIT SIGNS LEAD PERSONS TO LOBBY 100, HOWEVER NO
 EXIT SIGN IS SHOWN AT EXIT DOOR TO CORRIDOR. PLEASE ADD
 EXIT SIGN UNLESS EXISTING OR ALREADY PROVIDED.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-11 Cont ID  
Sent By adarroug Date 2008-09-11 Time 11:06 Rev Time 0.00
Received By adarroug Date 2008-09-11 Time 11:06 Sent To B
Notes
2008-09-11 11:07:15TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-20 Cont ID  
Sent By shill Date 2008-06-20 Time 16:01 Rev Time 0.00
Received By shill Date 2008-06-20 Time 16:01 Sent To  
Notes
2008-06-23 10:24:02TO "COMM" BD#34
2008-06-20 16:05:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-29 Cont ID  
Sent By jwitmer Date 2008-05-29 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2008-05-08 Time 11:00 Sent To  
Notes
2008-05-08 11:12:07TO "COMM" BD#3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-08 Cont ID  
Sent By rregueir Date 2008-07-08 Time 14:54 Rev Time 0.00
Received By rregueir Date 2008-07-08 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-23 Cont ID  
Sent By rregueir Date 2008-05-23 Time 15:20 Rev Time 0.00
Received By rregueir Date 2008-05-23 Time 14:20 Sent To  
Notes
2008-05-23 15:20:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENTS:
 1. PG A-2 AND M-2: SUITE #155 IS BEING SEPARATED FROM
 THE CENTRALIZED RETURN AIR INTAKE BY FULL-HEIGHT RATED
 PARTITIONS. NO PROVISIONS ARE SHOWN ON PLANS FOR THE
 FLOW OF RETURN AIR ABOVE THE CEILING PLENUM BACK TO THE
 A/C SYSTEM SHOW HOW BALANCED RETURN IS TO BE ACHIEVED
 IN THIS AREA IN ACCORDANCE WITH FBCM 601.4.
  
 2. SEVERAL SPACES IN THE WORK AREA ARE BEING
 RECONFIGURED. ALL RECONFIGURED SPACES INTENDED FOR
 OCCUPANCY IN ANY WORK AREA SHALL BE PROVIDED WITH
 NATURAL OR MECHANICAL VENTILATION IN ACCORDANCE WITH
 FBCEB 609.1 AND FBCM 401.2. PROVIDE OUTSIDE AIR
 CALCULATIONS SHOWING REQUIRED VENTILATION RATES FOR
 SPACES. VERIFY EXISTING SYSTEM IS CAPABLE OF PROVIDING
 THE REQUIRED VENTILATION AND PROVIDE INFORMATION ON HOW
 SYSTEMS IS TO BE REBALANCED, IF REQUIRED, TO
 DEMONSTRATE COMPLIANCE WITH THESE SECTIONS.
 NOTE: THE LOBBY/RECEPTION AREA IN SUITE #155 MAY HAVE
 HIGHER VENTILATION RATE REQUIREMENTS THAN THE
 PREVIOUSLY EXISTING OPEN WORK AREAS AT THE SAME
 LOCATION IN ACCORDANCE WITH FBCM TABLE 403.3.
  
 NOTE: ENERGY CALCULATIONS WERE NOT REVIEWED FOR THE
 MECHANICAL PROVISIONS OF THE FLORIDA ENERGY EFFICIENCY
 CODE AS THERE ARE NO NEW AIR CONDITIONING SYSTEMS BEING
 INSTALLED. ONLY COMPLIANCE WITH FBCB 13-101.6 IS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-05-20 Cont ID  
Sent By kstevens Date 2008-05-20 Time 12:59 Rev Time 0.00
Received By kstevens Date 2008-05-20 Time 12:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2008-05-09 Cont ID  
Sent By choops Date 2008-05-09 Time 11:21 Rev Time 0.00
Received By choops Date 2008-05-09 Time 11:21 Sent To  
Notes
2008-05-09 11:22:24*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
  
  
  
 SENT BACK TO COMMERCIAL BOARD #3