Plan Review Details - Permit 08050173
Plan Review Stops For Permit 08050173
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-06-09 Cont ID  
Sent By mperson Date 2008-06-09 Time 15:55 Rev Time 0.00
Received By mperson Date 2008-06-09 Time 15:55 Sent To PC
Notes
2008-06-09 15:56:57REVISION #1: "OK" CHANGED PIPING MATERIAL IN TWO
 PLACES.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-05-16 Cont ID  
Sent By mperson Date 2008-05-16 Time 11:10 Rev Time 0.00
Received By mperson Date 2008-05-16 Time 11:10 Sent To PC
Notes
2008-05-16 11:48:25****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-08 Cont ID  
Sent By mperson Date 2008-05-08 Time 10:35 Rev Time 0.00
Received By mperson Date 2008-05-08 Time 10:35 Sent To  
Notes
2008-05-08 10:51:30GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER FBC-2004 FUEL GAS SECTION 401.1
 SCOPE.
 NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED FOR
 ALL CUT SECTIONS OF PIPE. REFERENCE THE RED CIRCLED
 YELLOW HIGH LIGHTED AREAS AND COMPLY.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
 NOTE: NOT ALL MATERIAL TYPES OR PIPE SIZES ARE
 INDICATED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THE TOTAL BTU LOAD IS INCORRECT IT SHOULD BE
 719,000.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: CLEARLY INDICATE THE MAKE OF THE MP REGULATOR ON
 THE RESUBMITTED PLANS.
  
 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 7. PER FS 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2):
 IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF
 NO FURTHER EFFECT.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 15:36 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 15:36 Sent To G
Notes
2008-06-06 15:36:58TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 14:05 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 14:05 Sent To G
Notes
2008-05-15 14:05:32TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-08 Cont ID  
Sent By mperson Date 2008-05-08 Time 10:51 Rev Time 0.00
Received By mperson Date 2008-05-06 Time 10:18 Sent To  
Notes
***NONE***