| 2008-05-19 10:55:51 | BUILDING PLAN REVIEW 1ST |
| | PERMIT: 08050162 |
| | ADD: 1617 N. FLAGLER DR. #903 |
| | CONT: JEFFERY W. LEWIS INC. |
| | TEL: (561)691-1801 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 5-19-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4)PER FLORIDA STATUTES, 481.229 EXEMPTIONS FROM |
| | ARCHITECTURAL LICENSURE ONLY APPLY TO 1FAMILY AND |
| | 2FAMILY RESIDENCES (R3) NOT MULTI-FAMILY (R2) OR |
| | BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE |
| | REQUIRED TO BE DRAWN BY A LICENSED DESIGN |
| | PROFESSIONAL. |
| | |
| | A DESIGN PROFESSIONAL THAT IS REGISTERED TO PRACTICE |
| | UNDER CHAPTER 481 OR 471 OF THE FLORIDA STATUTES SHALL |
| | AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND DATE TO SAID |
| | DRAWINGS AND SPECIFICATION PER 106.1 FBC 2004, THE |
| | EXEMPTION FROM LICENSURE UNDER 481.229 FLORIDA STATUTES |
| | DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR THE |
| | DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS. |
| | |
| | 5) THE PLANS FAIL TO INDICATE THE DIMENSIONS OF THE |
| | ALTERED AREA. IT SEEMS AS IF THERE ARE SOME SOFFIT WORK |
| | IN THE AREA, HOWEVER THERE IS NO CEILING PLANS OR |
| | DETAILS TO SHOW CLEARLY WHERE THE SOFFITS WILL BE |
| | CONSTRUCTED.CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. FBC |
| | 106.1.1 |
| | |
| | 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | 7)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 8)THE PLANS SHALL INDICATE THE HEIGHT, TYPE OF |
| | BUILDING PER CHAPTER 6 AND TABLE 601, THE USE AND |
| | OCCUPANCY CLASSIFICATION PER CHAPTER 3. |
| | |
| | 9)INDICATE THE USE OF EACH ROOM ON THE DRAWINGS. ON |
| | SHEET A-3 THERE ARE THREE DIFFERENT WALL DETAILS, |
| | PROVIDE A LEGEND SHOWING/INDICATING WHERE EACH DETAIL |
| | WILL BE USED ON THE FLOOR PLANS.CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THE CODE. FBC 106.1.1 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |