Plan Review Details - Permit 08050084
Plan Review Stops For Permit 08050084
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-30 Cont ID  
Sent By mjacobs Date 2008-06-30 Time 13:15 Rev Time 0.00
Received By mjacobs Date 2008-06-30 Time 13:08 Sent To PC
Notes
2008-06-30 13:05:44PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-27 Cont ID  
Sent By mjacobs Date 2008-06-27 Time 10:49 Rev Time 0.00
Received By mjacobs Date 2008-06-27 Time 09:10 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-19 Cont ID  
Sent By mjacobs Date 2008-06-19 Time 08:02 Rev Time 0.00
Received By mjacobs Date 2008-06-19 Time 06:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-19 Cont ID  
Sent By mjacobs Date 2008-05-19 Time 07:50 Rev Time 0.00
Received By mjacobs Date 2008-05-16 Time 11:27 Sent To  
Notes
2008-05-19 07:50:45 
 BUILDING PLAN REVIEW
 PERMIT: 08050084
 ADD: 1901 S. FLAGLER DR.
 CONT: PRETI CONSTRUACTION
 TEL: (561)840-9949
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST 5-16-08
 REVIEW
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)THE PLANS SHALL REFERENCE THE FOLLOWING INFORMATION
 IN CONFORMANCE WITH THE 2004 FBC A) THE TYPE OF
 CONSTRUCTION PER CHAPTER 6 AND TABLE 601. B)THE USE
 AND OCCUPANCY PER CHAPTER 3. C) THE OCCUPANT LOAD PER
 TABLE 1004.1.2.CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS.
  
 5)WHY THERE ARE NO DOORS FOR THE REVISED TOILET
 ROOMS?INDICATE THE WALL FINISH FOR THE NEW MOP SINK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-25 Cont ID  
Sent By btrobaug Date 2008-06-25 Time 15:37 Rev Time 0.00
Received By btrobaug Date 2008-06-25 Time 15:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 15:14 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 14:47 Sent To  
Notes
2008-06-11 15:03:50 
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-19 Cont ID  
Sent By btrobaug Date 2008-05-19 Time 12:15 Rev Time 0.00
Received By btrobaug Date 2008-05-19 Time 12:05 Sent To  
Notes
2008-05-19 12:15:06 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 2} NOTE #3 SHEET A1.1 AND A1.2 INDICATES ADDING
 FIXTURES "AS CALLED FOR ON THE PLANS." THERE ARE NO
 FIXTURES SHOWN ON THE PLAN. SHOW ALL WORK TO BE DONE
 UNDER THIS APPLICATION. IF NO ELECTRICAL WORK IS BEING
 DONE, REMOVE THE NOTE AND STATE SAME ON THE PLAN.IF
 FIXTURES ARE BEING ADDED, COMPLY WITH CHAPTER 13 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-30 Cont ID  
Sent By mawillia Date 2008-06-30 Time 11:07 Rev Time 0.00
Received By mawillia Date 2008-06-30 Time 11:00 Sent To  
Notes
2008-06-30 11:06:59*****APPROVED*****
  
  
 PLAN SHEET A1.1 & A1.2 WERE RE-STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By mawillia Date 2008-06-16 Time 15:20 Rev Time 0.00
Received By mawillia Date 2008-06-16 Time 15:00 Sent To  
Notes
2008-06-16 15:18:11*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSSED;PLAN SHEET A1.1 & A1.2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-20 Cont ID  
Sent By mwennerg Date 2008-05-20 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2008-05-20 Time 15:01 Sent To  
Notes
2008-05-20 15:06:42***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) WILL WORK IMPACT FIRE PROTECTION EQUIPMENT? SEPARATE
 SHOP DRAWINGS AND PERMITS MAY BE REQUIRED FOR EQUIPMENT
 REMODEL.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED AND
 SHALL BE MOUNTED AT LOCATIONS TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 08:34 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 08:34 Sent To P
Notes
2008-07-22 08:35:14TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 16:27 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 16:26 Sent To  
Notes
2008-06-26 08:20:246/26/08--PLANS TAKEN FROM "BOB"#15, AND ROUTED TO
 "MPERSON" DESK, PER "RBROWN"
2008-06-24 16:32:57TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 13:40 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 13:40 Sent To  
Notes
2008-06-05 13:43:54TO "BOB" #15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-21 Cont ID  
Sent By tgordon Date 2008-05-21 Time 09:40 Rev Time 0.00
Received By tgordon Date 2008-05-05 Time 12:25 Sent To  
Notes
2008-05-13 10:00:035/13/08 --TO "BOB"#6
2008-05-05 12:26:31TO "P" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-06-06 Cont ID  
Sent By tgordon Date 2008-06-06 Time 11:50 Rev Time 0.20
Received By tgordon Date 2008-06-06 Time 11:50 Sent To  
Notes
2008-06-06 11:51:47NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-21 Cont ID  
Sent By tgordon Date 2008-05-21 Time 09:30 Rev Time 0.20
Received By tgordon Date 2008-05-21 Time 09:30 Sent To  
Notes
2008-05-21 09:38:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE A1.1 DEMO NOTE #7 STATES, REMOVE EXISTING
 HVAC SYSTEM, ETC. PLEASE SUBMIT AN A/C PLAN SHOWING
 WERE THE A/C SYSTEM IS TO BE RELOCATED AND ANY DUCK
 WORK TO BE ALTERED. IF THE SPACE IS NOT TO BE
 CONDITIONED STATE SO ON PLAN, PER 2004 FBC 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-07-30 Cont ID  
Sent By mperson Date 2008-07-30 Time 14:21 Rev Time 0.00
Received By mperson Date 2008-07-30 Time 14:21 Sent To PC
Notes
2008-07-30 14:22:50REVISION SHEET A1.1: "OK" DELETED 2ND FLOOR DRINKING
 FOUNTAIN.

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-07-23 Cont ID  
Sent By mperson Date 2008-07-23 Time 11:11 Rev Time 0.00
Received By mperson Date 2008-07-23 Time 11:11 Sent To PC
Notes
2008-07-23 11:37:05PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET A1.1, RELOCATED MOP SINK: PLEASE REVISE THE
 SECOND FLOOR SANITARY RISER TO REFLECT THE NEW SECOND
 FLOOR PLAN. THE NEW SECOND FLOOR PLAN INDICATES THE
 DRINKING FOUNTAIN BEING DELETED. THE SANITARY RISER
 DIAGRAM NEEDS TO REFLECT THIS CHANGE. PER FBC-2004
 PLUMBING SECTION 701.1 SCOPE.
 NOTE: ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION
 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-27 Cont ID  
Sent By mperson Date 2008-06-27 Time 08:36 Rev Time 0.00
Received By mperson Date 2008-06-27 Time 08:36 Sent To B
Notes
2008-06-27 08:43:31****************PROVISO****************
 A} ADA LAV FAUCETS SHALL COMPLY WITH 11-4.19.5.
  
 B} ADA SINK SHALL COMPLY WITH 11-4.24.2 HEIGHT (MAX
 34"), 11-4.24.4 DEPTH (6-1/2"), AND 11-4.24.7 FAUCETS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
 ****************PROVISO****************
 THE ADDED DRINKING FOUNTAIN ON THE SECOND FLOOR SHALL
 COMPLY WITH 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING
 FOUNTAIN IS PROVIDED ON A FLOOR, THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO INDIVIDUALS
 WHO USE WHEELCHAIRS IN ACCORDANCE WITH SECTION 11-4.15
 AND ONE ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY BENDING
 OR STOOPING.(THIS CAN BE ACCOMMODATED BY THE USE OF A
 HI-LO FOUNTAIN OR BY SUCH OTHER MEANS AS WOULD ACHIEVE
 THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR
 SUCH AS A DRINK CUP HOLDER).
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-17 Cont ID  
Sent By mperson Date 2008-06-17 Time 11:16 Rev Time 0.00
Received By mperson Date 2008-06-17 Time 11:16 Sent To  
Notes
2008-06-17 14:01:09PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING ARE NUMBERED TO CORRESPOND WITH THE
 PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. "OK" COMMENT ADDRESSED.
  
 2."OK" COMMENT ADDRESSED.
  
 3. PER FS 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2):
 IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF
 NO FURTHER EFFECT.
  
 **RESPONSE NOTED, HOWEVER COMMENT SHALL REMAIN.
  
 4. PLEASE PROVIDE ELEVATION DETAILS FOR THE FOLLOWING
 FIXTURES COMPLIANT WITH CHAPTER 11 FLORIDA
 ACCESSIBILITY CODE. PLANS ARE INDICATING CLASSROOMS FOR
 3-4 YR. OLD IT IS SUGGESTED THAT FIXTURES BE PER "ADA
 ACCESSIBILITY GUIDELINES FOR BUILDING ELEMENTS DESIGNED
 FOR CHILDREN'S USE" AND IF THOSE GUIDELINES ARE USED TO
 CLEARLY INDICATE ON THE PLANS THAT THEY WERE USED IN
 THE DESIGN. PLEASE CLEARLY INDICATE THAT ALL PLUMBING
 FIXTURES ON SHEET A1.1 ARE FOR 3-4 YR.OLD.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).NOTE:
 PLANS ARE NOT INDICATING ANY EXISTING OR NEW DRINKING
 FOUNTAINS HOWEVER PER FBC-2004 PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES FOR A
 CLASSIFICATION EDUCATIONAL E/D, 1 PER 100 IS REQUIRED.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
 NOTE: SHEET A1.1 DETAIL 02 FIRST FLOOR PLAN IS
 INDICATING IN PLAN KEY NOTES "M" AS A NEW 3 COMPARTMENT
 S.S. SINK. IS THIS SINK FOR CLASSROOM USE OR IS THIS A
 LOUNGE AREA? PLEASE CLEARLY INDICATE THE USE OF THIS
 SINK.
  
 **RESPONSE NOTED, HOWEVER PER SHEET A1.1 INDICATING
 OCCUPANCY LOAD AS 105 TWO DRINKING FOUNTAINS ARE
 REQUIRED. THE HIGH/LOW DRINKING FOUNTAIN IS CONSIDERED
 ONE FIXTURE DUE TO HAVING ONLY ON WATER SEAL TRAP AND
 WATER SUPPLY. WHERE ARE THE DRINKING FOUNTAINS FOR THE
 SECOND FLOOR? THERE IS NO INDICATION OF EXISTING OR
 PROPOSED DRINKING FOUNTAINS FOR THE SECOND FLOOR. THEY
 ARE REQUIRED AND SHALL BE ACCESSIBLE PER THE ABOVE
 SECTIONS 11-4.15. PER FBC- PLUMBING SECTION 606.2
 LOCATION OF SHUT OFF VALVES AND SECTION 1002.1 FIXTURE
 TRAPS. THE NEW (3) COMPARTMENT SINK (IDENTFIED AS "M"
 ON SHEET A1.1) ON FIRST FLOOR PLAN SHALL BE ACCESSIBLE
 PER THE ABOVE 11-4.24 SECTIONS.
  
  
 5. SHEET A1.1 FIRST AND SECOND FLOOR WATER
 ISOMETRIC'S: WHAT IS AN SA? ARE THEY WATER-HAMMER
 ARRESTORS? PLEASE CLARIFY THIS ON THE RESUBMITTAL.
 PER FBC-2004 PLUMBING SECTION 604.9 WATER HAMMER. A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. NOTE: IF A SA IS AN
 AIR CHAMBER THEY SHALL BE PER "STANDARD PDI-WH-201" A
 RECHARGEABLE TYPE OF AIR CHAMBER AND A DETAIL IS
 REQUIRED.
  
 **RESPONSE NOTED, HOWEVER A WATER HAMMER ARRESTOR AND
 A RECHARGEABLE TYPE AIR CHAMBER ARE TWO DIFFERENT ITEMS
 NOT ONE IN THE SAME AS INDICATED ON THE REVISED PLAN
 SHEET A1.1. PLEASE REFERENCE THE DETAIL OF A
 RECHARGEABLE TYPE AIR CHAMBER ATTACHED TO THESE
 COMMENTS INDICATING THIS. IF IT IS THE INTENT TO USE
 ONLY WATER HAMMER ARRESTORS PLEASE DELETE THE FOLLOWING
 "AND INCLUDE A RECHARGEABLE TYPE AIR CHAMBER INSTALL
 PER MANUF. REQUIREMENTS & PER CODE".
  
 6. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-13 Cont ID  
Sent By mperson Date 2008-05-13 Time 08:23 Rev Time 0.00
Received By mperson Date 2008-05-13 Time 08:23 Sent To I
Notes
2008-05-13 09:47:27PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED
 BELOW.
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS
 F-1 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2,
 AND I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP
 U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS"
  
 3. PER FS 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2):
 IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF
 NO FURTHER EFFECT.
  
 4. PLEASE PROVIDE ELEVATION DETAILS FOR THE FOLLOWING
 FIXTURES COMPLIANT WITH CHAPTER 11 FLORIDA
 ACCESSIBILITY CODE. PLANS ARE INDICATING CLASSROOMS FOR
 3-4 YR. OLD IT IS SUGGESTED THAT FIXTURES BE PER "ADA
 ACCESSIBILITY GUIDELINES FOR BUILDING ELEMENTS DESIGNED
 FOR CHILDREN'S USE" AND IF THOSE GUIDELINES ARE USED TO
 CLEARLY INDICATE ON THE PLANS THAT THEY WERE USED IN
 THE DESIGN. PLEASE CLEARLY INDICATE THAT ALL PLUMBING
 FIXTURES ON SHEET A1.1 ARE FOR 3-4 YR.OLD.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).NOTE:
 PLANS ARE NOT INDICATING ANY EXISTING OR NEW DRINKING
 FOUNTAINS HOWEVER PER FBC-2004 PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES FOR A
 CLASSIFICATION EDUCATIONAL E/D, 1 PER 100 IS REQUIRED.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
 NOTE: SHEET A1.1 DETAIL 02 FIRST FLOOR PLAN IS
 INDICATING IN PLAN KEY NOTES "M" AS A NEW 3 COMPARTMENT
 S.S. SINK. IS THIS SINK FOR CLASSROOM USE OR IS THIS A
 LOUNGE AREA? PLEASE CLEARLY INDICATE THE USE OF THIS
 SINK.
  
 5. SHEET A1.1 FIRST AND SECOND FLOOR WATER
 ISOMETRIC'S: WHAT IS AN SA? ARE THEY WATER-HAMMER
 ARRESTORS? PLEASE CLARIFY THIS ON THE RESUBMITTAL.
 PER FBC-2004 PLUMBING SECTION 604.9 WATER HAMMER. A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. NOTE: IF A SA IS AN
 AIR CHAMBER THEY SHALL BE PER "STANDARD PDI-WH-201" A
 RECHARGEABLE TYPE OF AIR CHAMBER AND A DETAIL IS
 REQUIRED.
  
 6. SHEET A1.1 DETAIL 02 FIRST FLOOR PLAN THE NEW LAV
 IS NOT BEING INDICATED IN THE NEW ADA COMPLIANT
 BATHROOM. PLEASE CLEARLY IDENTIFY THIS LAV AS "P" AS
 INDICATED IN "PLAN KEY NOTES".
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-05-14 Cont ID  
Sent By choops Date 2008-05-14 Time 15:32 Rev Time 0.00
Received By choops Date 2008-05-14 Time 15:32 Sent To  
Notes
2008-05-14 15:32:25*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.