Plan Review Details - Permit 08050082
| Plan Review Stops For Permit 08050082 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-05-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-05-21 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-05-21 |
Time |
15:32 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
|
Date |
2008-05-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-05-07 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-05-07 |
Time |
10:35 |
Sent To |
PC |
|
| Notes |
| 2008-05-07 10:37:23 | ROBERT BROWN APPROVED SHUTTER INSTALLATION SINCE IS A | | | PERMANENT SHUTTER AND NO INSTALLATION PLAN IS | | | REQUIRED. | | | SHUTTER MUST BE INSTALLED FOR CO, SINCE DOOR IS NOT | | | TESTED FOR IMPACT IN "INSWING" POSITION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-05-06 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-05-06 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2008-05-06 16:02:02 | DOOR AND ROLL UP SHUTTER FOR BUSINESS OCCUPANCY, | | | BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR MOUNTING | | | OF ROLL UP SHUTTERS. SEE ATTACHED SAMPLE OF | | | INSTALLATION SCHEDULE AND COMPLETE ALL THE APPLICABLE | | | INFORMATION. | | | ALSO, MARK ON ROLL UP DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED TO | | | VERIFY COMPLIANCE WITH PRODUCT APPROVAL AND PROPOSED | | | INSTALLATION. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 2- APPLICATION FOR SHUTTER PROTECTIONWAS ROUTED TO | | | BUILDING OFFICIAL FOR APPROVAL SINCE THIS PROJECT WAS | | | ORIGINALLY APPROVED USING IMPACT DOORS AS REQUIRED BY | | | CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS | | | IMPACT PROTECTION. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-05-06 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-05-05 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2008-05-05 14:50:28 | TO "MISC" BOX#1 |
|
|
|