Plan Review Details - Permit 08050050
Plan Review Stops For Permit 08050050
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 17:30 Rev Time 0.00
Received By shill Date 2008-05-29 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By shill Date 2008-05-20 Time 14:25 Rev Time 0.00
Received By shill Date 2008-05-20 Time 14:24 Sent To  
Notes
2008-05-20 14:28:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.IT APPEARS THAT THE ENGINEER HAS USED AN IMPORTANCE
 FACTOR OF 1 IN DETERMINING COMPONENT AND CLADDING
 DESIGN PRESSURES.SEE FBC TABLE 1604.5 AND FBC TABLE
 1004.1.2.BASED ON SQUARE FOOT AREA, THIS BUILDING
 APPEARS TO HAVE AN OCCUPANT LOAD OF GREATER THAN 250
 (12,500/20SF PER PERSON, OCCUPANT LOAD OF 625 PEOPLE).
 THIS WOULD REQUIRE AN IMPORTANCE FACTOR OF 1.15. PLEASE
 CLARIFY OR REVISE PRESSURES/FASTENING.
  
 PLEASE NOTE THAT I ATTEMPTED TO REACH THE ENGINEER AND
 CONTRACTOR TO GET THIS MATTER RESOLVED BY TELEPHONE IN
 AN ATTEMPT TO EXPEDITE THIS PERMIT, BUT WAS
 UNSUCCESSFUL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-05 Cont ID  
Sent By shill Date 2008-05-05 Time 15:30 Rev Time 0.00
Received By shill Date 2008-05-05 Time 15:30 Sent To  
Notes
2008-05-05 15:30:26****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE
 INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO
 SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT.
 INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE
 MITIGATION.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 ____4.)FOR THE FLAT ROOF, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 _XX_5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET).
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  