Plan Review Details - Permit 08050038
Plan Review Stops For Permit 08050038
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-21 Cont ID  
Sent By jgomez Date 2008-07-21 Time 10:33 Rev Time 0.00
Received By jgomez Date 2008-07-21 Time 08:50 Sent To E
Notes
2008-07-21 10:33:51CONTRACTOR CHANGED GENERATOR MANUFACTURER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-26 Cont ID  
Sent By jgomez Date 2008-06-26 Time 07:52 Rev Time 0.00
Received By jgomez Date 2008-06-26 Time 07:43 Sent To PC
Notes
2008-06-26 08:08:33RESIDENTIAL (R3) GENERATOR BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISION:
  
 1- LETTER SUBMITTED FROM THE MANUFACTURER'S(NORPRO)
 ENGINEERING DEPARTMENT STATES THAT UNIT IS NOT DESIGNED
 TO WITHSTAND 140MPH WIND LOADS.IF THE UNIT IS NOT
 DESIGNED TO WITHSTAND THE WIND LOADS, THEN , WHAT'S THE
 PURPOSE OF THE GENERATOR IF IT MAY NOT BE THERE OR IT
 MAY NOT WORK AFTER A HURRICANE?.IT ALSO HAS SOME
 RECOMMENDATIONS FOR UNIT REINFORCEMENT AND UNIT
 ATTACHMENT TO THE CONCRETE SLAB.THEN. IT REQUIRES
 INSTALLATION PHOTOS FOR APPROVAL.. THE
 MANUFACTURER'S ENGINEERING DEPARTMENT NEEDS TO PROVIDE
 COMPLETE INFORMATION SHOWINGTHAT THE UNIT WILL MEET
 THE 140 MPH WIND LOAD AND PROVIDE COMPLETE
 SPECIFICATIONS SHOWING UNIT ATTACHMENT TO THE CONCRETE
 SLAB. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH THE WIND LOADS OF SEC. R301 OF
 2004 FLORIDA RESIDENTIAL CODE. ALL INFORMATION NEEDS TO
 BE PROPERLY SIGNED AND SEALED AND WITH COMPLETE
 ENGINEER'S INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED WHEN PICKING UP THE
 PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-03 Cont ID  
Sent By jgomez Date 2008-06-03 Time 16:55 Rev Time 0.00
Received By jgomez Date 2008-06-03 Time 16:55 Sent To PC
Notes
2008-06-03 17:00:48RESIDENTIAL (R3) GENERATOR INSTALLATION, BUILDING
 REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-NEED TO PROVIDE INFORMATION SHOWING ATTACHMENT OF
 GENERATOR TO THE SLAB TO RESIST THE 140 MPH WIND LOADS
 INEXPOSURE "C" AS REQUIRED BY SEC. R301.2.1.4 OF 2004
 FLORIDA RESIDENTIAL CODE.INFORMATION SUBMITTED IS A
 DETAIL FOR A CONCRETE SLAB, BUT THERE ARE NO
 DETAIL/SPECIFICATIONS FOR EQUIPMENT ATTACHMENT TO
 RESIST THE ABOVE LOADS.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 2- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY SEC. 713.13 FLORIDA STATUTES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By btrobaug Date 2008-07-22 Time 10:45 Rev Time 0.00
Received By btrobaug Date 2008-07-22 Time 10:44 Sent To M
Notes
2008-07-22 10:45:31 
  
 CHANGED TO BRIGGS AND STRATTON, SAME OUTPUT AND
 SETBACKS./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-05-12 Cont ID  
Sent By btrobaug Date 2008-05-12 Time 13:23 Rev Time 0.00
Received By btrobaug Date 2008-05-12 Time 12:12 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2008-07-24 Cont ID  
Sent By mperson Date 2008-07-24 Time 13:54 Rev Time 0.00
Received By mperson Date 2008-07-24 Time 13:54 Sent To  
Notes
2008-07-24 13:56:39NOTE: CONTRACTOR CHANGED GENERATOR MAKE, GAS PLANS OK.
 **MRPERSON

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-06-23 Cont ID  
Sent By mperson Date 2008-06-23 Time 16:14 Rev Time 0.00
Received By mperson Date 2008-06-23 Time 16:14 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-12 Cont ID  
Sent By mperson Date 2008-05-12 Time 14:44 Rev Time 0.00
Received By mperson Date 2008-05-12 Time 14:44 Sent To B
Notes
2008-05-12 15:33:14GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED. PLEASE REFERENCE THE RED CIRCLED
 YELLOW HIGH LIGHTED AREAS INDICATING THIS AND COMPLY ON
 THE RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
 *NOTE: NOT ALL PIPING MATERIALS OR PIPE SIZES ARE
 BEING INDICATED FOR ALL CUT SECTIONS OF PIPE. PLEASE
 REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED AREAS
 INDICATING THIS AND COMPLY ON THE RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE REFERENCE COMMENT #1 AND COMPLY.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 *NOTE: THE SUBMITTED MANUFACTURE SHEETS FOR THE
 GENERATOR, BBQ AND WATER HEATER ARE NOT INDICATING A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY. PLEASE COMPLY ON THE RESUBMITTAL FOR THESE
 ITEMS AND CLEARLY INDICATE THE MAKE AND MODEL NUMBER
 FOR ALL INDICATED MP REGULATORS ON THE RESUBMITTED
 ISOMETRIC. THE ONLY MP REGULATOR BEING INDICATED ON THE
 ISOMETRIC IS AN AMERICAN METER 1813 FOR THE POOL HEATER
 (TYP), HOWEVER THERE IS ALSO A MAXITROL 325 MP
 REGULATOR SUBMITTAL IN THIS PERMIT APPLICATION. PLEASE
 CLARIFY THIS ON THE RESUBMITTAL.
  
 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE CLEARLY
 INDICATE THE REQUIRED SHUT OFF VALVE FOR THE MP
 REQULATOR BEING INDICATED FOR THE GAS LIGHTS ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 14:34 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 14:34 Sent To B
Notes
2008-07-18 14:34:56TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 10:03 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 10:02 Sent To Z
Notes
2008-06-19 10:03:496/19/08--PLANS SUBMITTED ON 6/18/08,--TO "Z" BOX
2008-05-02 14:42:09TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By tgordon Date 2008-07-22 Time 15:34 Rev Time 0.25
Received By tgordon Date 2008-07-22 Time 15:34 Sent To G
Notes
2008-07-22 15:35:44REVIEWED AND STAMPED ON 5-7-08.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-05-07 Cont ID  
Sent By tgordon Date 2008-05-07 Time 10:34 Rev Time 0.25
Received By tgordon Date 2008-05-07 Time 10:34 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-19 Cont ID  
Sent By choops Date 2008-06-19 Time 14:50 Rev Time 0.00
Received By choops Date 2008-06-19 Time 14:50 Sent To G
Notes
2008-06-19 14:51:42***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "G" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-06 Cont ID  
Sent By choops Date 2008-05-06 Time 15:24 Rev Time 0.00
Received By choops Date 2008-05-06 Time 15:24 Sent To E
Notes
2008-05-06 15:26:02***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - GENRES. BOX