Plan Review Details - Permit 08050006
Plan Review Stops For Permit 08050006
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-07 Cont ID  
Sent By shill Date 2008-11-07 Time 17:23 Rev Time 0.00
Received By shill Date 2008-11-07 Time 17:23 Sent To  
Notes
2008-11-07 17:24:08REVISION, A2.1, 5.1, 5.2, 6.1
 DATED 9/22/8
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-01 Cont ID  
Sent By shill Date 2008-08-01 Time 12:27 Rev Time 0.00
Received By shill Date 2008-08-01 Time 12:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-29 Cont ID  
Sent By shill Date 2008-07-29 Time 15:26 Rev Time 0.00
Received By shill Date 2008-07-29 Time 15:26 Sent To  
Notes
2008-07-29 15:33:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ALL SHEETS ARE TO INCLUDE THE DATE, FS481,
 FAC61G1-15.23.002.
  
 NOT ADDRESSED.A DATE IS LOCATED ON ANOTHER PART OF
 THE PAGE, BUT THE FLORIDA BOARD OF ARCHITECTS HAS
 STATED THAT THE SEAL ITSELF IS TO INCLUDE A DATE. OTHER
 DATES ON THE PLANS DO NOT COMPLY WITH THE STATUTORY
 REQUIREMENT.THE SEAL IS TO BE DATED. PLEASE COMPLY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-28 Cont ID  
Sent By shill Date 2008-05-28 Time 15:26 Rev Time 0.00
Received By shill Date 2008-05-28 Time 15:26 Sent To  
Notes
2008-05-28 16:05:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ALL SHEETS ARE TO INCLUDE THE DATE, FS481,
 FAC61G1-15.23.002.
  
 2.A9.6, SHIELDING SPECIFICATIONS, PLEASE CLARIFY
 AREAS WHICH SHOW "NONE REQUIRED" FOR SHIELDING
 REQUIREMENTS FOR INSTANCE, EXTERIOR WALL AND THE WALL
 ADJACENT TO CLERICAL AREA.
  
 3.SEE FBC435.5.1.3.1, STRUCTURAL COMPOSITION AND
 OCCUPANCY OF ADJACENT AREA OF EXTERIOR WALL, FLOOR, AND
 CEILING ARE REQUIRED.THE PLAN SHOWS THIS AS FIRST
 FLOOR, BUT WITH AN ADJACENT ROOF AREA.THE SHIELDING
 SPECIFICATION SHOWS WALL A-B AS UNOCCUPIED EXTERIOR
 SPACE, OTHER SHEETS SHOW AN EQUIPMENT ROOM AND STAIR.
 PLEASE CLARIFY COMPLIANCE WITH FBC435.5.1.3, SHIELDING
 REQUIREMENTS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 16:15 Sent To  
Notes
2008-10-28 16:16:45RECEPTS, REVISIONS, LIGHTS REVISIONS LOCATIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-22 Cont ID  
Sent By dpalmer Date 2008-05-22 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2008-05-22 Time 11:54 Sent To  
Notes
2008-05-22 11:54:42** DENIEDREVIEW**
  
  
 1) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW CATH-LAB
 PANEL.
 408.4, 240.4, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 2) NOTE: PLEASE SHOW LOCATION OF NEW CATH LAB PANEL
 COMPARED TO ATS-11. TAPPED CONDUCTOR RULES PER 240.21
 CAN NOT BE VERIFIED AT THIS TIME.
  
 3) NOTE: PLEASE SUBMIT THE LIGHTING PERFORMANCE
 CALCULATION PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
 THE SUBMITTED PHOTO-COPIED FORM IS NOT COMPLETED, NOT
 ORIGINAL, NOT SIGNED AND SEALED ETC.
 FBC 13-103.1
  
 4) NOTE: PLEASE VERIFY COMMENT #2 ABOVE AND VERIFY
 500MCM IN 150AMP BREAKER.
 110.3, 90.7
  
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-24 Cont ID  
Sent By mwennerg Date 2008-10-24 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2008-10-24 Time 13:57 Sent To  
Notes
2008-10-24 13:58:24REVISION DATED 9/18/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By mwennerg Date 2008-07-22 Time 14:15 Rev Time 0.00
Received By mwennerg Date 2008-07-22 Time 14:15 Sent To  
Notes
2008-07-22 14:15:52SHEET F0.1 STAMPED FROM LAST FIRE REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-05-30 Cont ID  
Sent By mwennerg Date 2008-05-30 Time 10:44 Rev Time 0.00
Received By mwennerg Date 2008-05-30 Time 10:44 Sent To  
Notes
2008-05-30 10:52:11***APPROVED***
  
 1) NEW DUCT DETECTOR INSTALLATIONS SHALL INITIATE A
 GENERAL ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 2) FIRE DAMPERS TO BE INSTALLED PER REQUIREMENTS OF UL
 555 AND SHALL BE DROP TESTED PRIOR TO FINAL
 INSPECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-02 Cont ID  
Sent By adarroug Date 2008-12-02 Time 11:12 Rev Time 0.00
Received By adarroug Date 2008-12-02 Time 11:12 Sent To P
Notes
2008-12-02 11:12:36TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 11:02 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 11:02 Sent To  
Notes
2008-10-02 11:02:58TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 11:53 Sent To B
Notes
2008-08-01 11:54:06TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-23 Cont ID  
Sent By adarroug Date 2008-06-23 Time 10:11 Rev Time 0.00
Received By adarroug Date 2008-06-23 Time 10:11 Sent To  
Notes
2008-07-01 16:33:07TO "COMM" BD#37
2008-06-23 10:11:23WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-30 Cont ID  
Sent By mwennerg Date 2008-05-30 Time 13:29 Rev Time 0.00
Received By mwennerg Date 2008-05-05 Time 11:14 Sent To  
Notes
2008-05-12 11:30:26TO "COMM" BD#40

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-25 Cont ID  
Sent By rregueir Date 2008-10-25 Time 15:08 Rev Time 0.00
Received By rregueir Date 2008-10-25 Time 15:08 Sent To  
Notes
2008-10-25 15:08:25REVISED M1.01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-09 Cont ID  
Sent By rregueir Date 2008-07-09 Time 16:24 Rev Time 0.00
Received By rregueir Date 2008-07-09 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-05-20 Cont ID  
Sent By rregueir Date 2008-05-20 Time 13:10 Rev Time 0.00
Received By rregueir Date 2008-05-20 Time 11:38 Sent To  
Notes
2008-05-20 13:09:54*************PROVISO**************
 PROVIDE DETAIL FOR INSTALLATION OF CONDENSING UNIT TO
 ROOF STRUCTURE. SHOW COMPLIANCE WITH FBCB 1509.7 FOR
 CLEARANCE AND FBCM 301.13 FOR WIND RESISTANCE.
  
 ALSO, METHOD C ENERGY CALCULATIONS WERE PROVIDED WITH
 PLANS. THOSE CALCULATIONS WERE NOT REVIEWED FOR
 COMPLIANCE WITH THE MECHANICAL PROVISIONS OF THE ENERGY
 CODE. IN ACCORDANCE WITH FBCM 13-101.6, NEW COMPONENTS
 BEING INSTALLED MEET THE BASIC PRESCRIPTIVE
 REQUIREMENTS AS SHOWN ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2008-10-10 Cont ID  
Sent By kstevens Date 2008-10-10 Time 16:53 Rev Time 0.00
Received By kstevens Date 2008-10-10 Time 16:53 Sent To  
Notes
2008-10-10 16:54:48REVISION OK - SHT P3.01 MED-GAS -- REVISION #1 NOT
 FOUND OR APPROVED.

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2008-05-16 Cont ID  
Sent By kstevens Date 2008-05-16 Time 16:20 Rev Time 0.00
Received By kstevens Date 2008-05-16 Time 16:20 Sent To  
Notes
2008-05-16 16:21:32SEPARATE MED-GAS PERMIT REQUIRED.--CERTIFICATIONS
 REQUIRED FOR PLUMBING CONTRACTOR, INSTALLER & BRAZER
 WITH PICTURE IDENTIFICATION AT TIME OF APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-10-10 Cont ID  
Sent By kstevens Date 2008-10-10 Time 16:55 Rev Time 0.00
Received By kstevens Date 2008-10-10 Time 16:55 Sent To  
Notes
2008-10-10 16:58:04REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P1.01 SANITARY RISER DIAGRAM DOES NOT SHOW A
 VENT THRU ROOF. SECTION 903.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-10 Cont ID  
Sent By kstevens Date 2008-10-10 Time 16:54 Rev Time 0.00
Received By kstevens Date 2008-10-10 Time 16:54 Sent To  
Notes
2008-10-10 16:55:48REVISIONS OK -- SHTS P0.01 & P2.01, (PDI-WH 201)

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-05-16 Cont ID  
Sent By kstevens Date 2008-05-16 Time 16:21 Rev Time 0.00
Received By kstevens Date 2008-05-16 Time 16:21 Sent To  
Notes
2008-05-16 16:22:24PASSED/PROVISO--WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES NOT IN THE CEILING. PDI-WH
 201