Plan Review Details - Permit 08050003
Plan Review Stops For Permit 08050003
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-21 Cont ID  
Sent By jgomez Date 2008-07-21 Time 11:20 Rev Time 0.00
Received By jgomez Date 2008-07-21 Time 10:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-29 Cont ID  
Sent By jgomez Date 2008-05-29 Time 15:54 Rev Time 0.00
Received By jgomez Date 2008-05-29 Time 15:53 Sent To PC
Notes
2008-05-29 16:28:25NEW STREET LIGHT POLES, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENTDESCRIBING
 THIS SCOPE OF WORK AS REQUIRED BY SEC. 713.13 FLORIDA
 STATUTE.
  
 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 NEED TO UPDATE VALUE TO INCLUDEREMOVAL OF EXISTING
 POLES, ENGINEERING,SPECIFIC LIGHT POLE AND LIGHT
 FIXTURE TO BE USED AND CONTRACTOR'S OVERHEAD AND
 PROFIT. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 3- PROVIDE COMPLETE ENGINEERING CALCULATIONS TO SHOW
 COMPLIANCE WITH SEC.1604,1609.1.1AND 1609.1.3 FBC
 2004.
 NOTE: ALSO, SEE NOTE #4OF LIGHT POLE DETAIL ON SHEET
 E-2 SUBMITTED ( NOTE: INFORMATION ON LIGHT POLE DETAIL
 NOTE #4 AND DESIGN INFORMATION ON FOUNDATION NOTES ON
 SHEET E-2 DOESN'T MATCH. REVISE AS REQUIRED).
  
 4- PROVIDE SPECIFICATIONS/CUT SHEETS FOR LIGHT POLE AND
 LIGHT FIXTURE TO SHOW COMPLIANCE WITH THE CALCULATED
 DESIGN CRITERIA. SEC. 106.1.2 CITY A MENDMENTS TO FBC
 2004 TO VERIFY COMPLIANCE WITH PROPOSED STRUCTURE AND
 THE CALCULATED WIND LOADS OF SEC. 1609 FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-08-29 Cont ID  
Sent By btrobaug Date 2008-08-29 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2008-08-29 Time 12:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-22 Cont ID  
Sent By btrobaug Date 2008-08-22 Time 14:20 Rev Time 0.00
Received By btrobaug Date 2008-08-22 Time 13:43 Sent To PC
Notes
2008-08-22 14:20:33 
  
  
  
 REVISION DENIED
 1} THE REVISION SUBMITTED ON SHEET E-1 DOES NOT INCLUDE
 THE ORIGINAL SCOPE OF WORK ON THE PERMITTED E-1 SET.
 REASSIGN THIS SHEET ANOTHER NUMBER (UNLESS THE ORIGINAL
 WORK IS NOT BEING DONE AND THIS SHEET REPLACES THE
 ORIGINAL) OR SHOW THE ENTIRE SCOPE OF WORK ON ONE SHEET
 (REVISIONS CLOUDED WITH THE REVISION NUMBER WITH A
 DELTA).
  
 2} ADJUST THE VALUE TO INCLUDE THE LABOR AND MATERIAL
 FOR THE ADDITIONAL WORK,AT THE PERMIT CLERK?S DESK,
 AND PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-17 Cont ID  
Sent By btrobaug Date 2008-07-17 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2008-07-17 Time 16:09 Sent To ENG
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-19 Cont ID  
Sent By btrobaug Date 2008-05-19 Time 09:24 Rev Time 0.00
Received By btrobaug Date 2008-05-16 Time 16:03 Sent To ENG
Notes
2008-05-16 16:59:40 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} VERIFY THAT THESE LUMINAIRES ARE FED FROM FPL. IF
 FED FROM BUILDING POWER SUBMIT THE PANEL DESIGNATION
 AND CIRCUIT NUMBER(S)
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-07-18 Cont ID  
Sent By rchokshi Date 2008-07-18 Time 12:58 Rev Time 0.00
Received By rchokshi Date 2008-07-18 Time 12:58 Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-07-18 Cont ID  
Sent By rchokshi Date 2008-07-18 Time 08:52 Rev Time 0.00
Received By rchokshi Date 2008-07-18 Time 08:49 Sent To  
Notes
2008-07-18 08:52:39FAILED FOR FOLLOWING REASONS:
  
 1.YOU ARE PUTTING AN ELECTRICK LIGHT POLES IN CITY'S
 RIGHT OF WAY. THEREFORE, YOU NEED CITY'S RIGHT OF WAY
 APPROVAL FROM WINDEL PALMER 494-1040, 1000 45TH STREET,
 ENG DEPT.ONCE WE HAVE AN APPROVAL FROM WINDEL
 PALMER, WE WILL REVIEW YOUR DRAWINGS.
  
 2. MUST MEET CITY'S STANDARDS FORLIGHT POLES
 INSTALLATION IN CITY'S RIGHT OF WAY .YOU CAN GET FROM
 MANNY GONZALEZ,1000 45TH STREET ENG DEPT.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-05-21 Cont ID  
Sent By rchokshi Date 2008-05-21 Time 13:52 Rev Time 0.00
Received By rchokshi Date 2008-05-21 Time 13:44 Sent To B
Notes
2008-05-21 13:51:24FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A DETAIL DRAWING SHOWING ALL THE
 DIMENSIONS FOR THE LIGHT POLE LOCATIONS AND THE LITE
 POLES.
  
 2. YOU ARE PUTTING AN ELECTRICK LIGHT POLES IN CITY'S
 RIGHT OF WAY. THEREFORE, YOU NEED CITY'S RIGHT OF WAY
 APPROVAL FROM WINDEL PALMER 494-1040, 1000 45TH STREET,
 ENG DEPT.ONCE WE HAVE AN APPROVAL FROM WINDEL
 PALMER, WE WILL REVIEW YOUR DRAWINGS.
  
 3. MUST MEET CITY'S STANDARDS FORLIGHT POLES.YOU
 CAN GET FROM MANNY GONZALEZ,1000 45TH STREET ENG
 DEPT.
  
 RASIK CHOKSHI 805-6723

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 11:05 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 11:05 Sent To E
Notes
2008-08-27 11:06:08TO "ELECT" BILL T.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 11:30 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 11:30 Sent To  
Notes
2008-08-14 11:30:45TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 11:14 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 11:14 Sent To E
Notes
2008-07-17 11:15:04TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-29 Cont ID  
Sent By jgomez Date 2008-05-29 Time 16:28 Rev Time 0.00
Received By jgomez Date 2008-05-01 Time 15:12 Sent To  
Notes
2008-05-01 15:12:49TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2008-05-14 Cont ID  
Sent By btrobaug Date 2008-05-19 Time 09:30 Rev Time 0.00
Received By mflis Date 2008-05-14 Time 14:48 Sent To  
Notes
***NONE***