Plan Review Details - Permit 08040824
Plan Review Stops For Permit 08040824
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-11-03 Cont ID  
Sent By jwitmer Date 2008-11-03 Time 09:55 Rev Time 0.55
Received By jwitmer Date 2008-11-03 Time 09:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-10-08 Cont ID  
Sent By jwitmer Date 2008-10-08 Time 09:44 Rev Time 0.77
Received By jwitmer Date 2008-10-08 Time 09:44 Sent To PC
Notes
2008-10-08 09:51:18BUILDING PLAN REVIEW
 PERMIT: 08040824
 ADD: 223 CLEMATIS ST
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
 1) SUBMITEED 2 SETS OF PLANS WILL REQUIRE THREE SETS OF
 PLANS SINCE THIS IS A THRESHOLD BUILDING.
 FL S S 553.71(7)/ 109.3.6 OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-29 Cont ID  
Sent By jwitmer Date 2008-08-29 Time 13:41 Rev Time 0.77
Received By jwitmer Date 2008-08-29 Time 13:41 Sent To  
Notes
2008-08-29 13:54:14BUILDING PLAN REVIEW
 PERMIT: 08040824
 ADD: 223 CLEMATIS ST
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 9-29-08
 REVIEW
 ACTION:REVIEWED
  
 BUILDING PROVISO:
 A COPY OF THE THRESHOLD INSPECTION PLAN SUBMITTED,
 RAISED SEAL TO BE OVERNIGHTED AND SUBMITTED TUESDAY
 9-02-08.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-08-21 Cont ID  
Sent By jwitmer Date 2008-08-21 Time 07:11 Rev Time 2.22
Received By jwitmer Date 2008-08-21 Time 07:11 Sent To PC
Notes
2008-08-29 13:40:398-29-08 THRESHOLD INSPECTION PLAN SUBMITTED (COPIED)
 ORIGINAL TO BE SUBMITED TUESDAY 9-02-08
2008-08-21 07:22:13BUILDING PLAN REVIEW
 PERMIT: 08040824
 ADD: 223 CLEMATIS ST
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2-3) COMPLIED.
  
 4) SHEET A5.0
  
 4A)BUILDING PROVISO: IN RESTROOMS WET WALLS TILE
 WAINSCOAT A MINIMUM OF 4'-0". WET WALL AREAS. PLEASE
 SEE 1210.2 NON-ABSORBANT SURFACES.
  
 4B-4C) COMPLIED.
  
 5-10) COMPLIED.
  
 11) NOTE, AGAIN THIS IS A FOUR STORY BUILDING, REQUIRES
 A THRESHOLD INSPECTOR, A THRESHOLD INSPECTION REPORT:
 11A)THRESHOLD INSPECTION PLANFL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 11B) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 11C) THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG,REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE. ED ADDITIONAL COMMENTS MAY APPEAR THAT
 WERE NOT PART OF THIS REVIEW.
  
 12) COMPLIED, SCOPE OF WORK REMOVED FROM PROJECT.
  
 13) NEW COMMENT, PRODUCT APPROVALS FOR FRONT DOORS
 SWING & SLIDDING WERE NOT SUBMITTED THIS REVIEW.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 3COPIES OF PRODUCT APPROVALS FOR THRESHOLDINSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 13A) PAIR OF FRONT ENTRY DOORS
 13B) PAIR OF FRONT ENTRY SLIDDING GLASS DOORS
  
 14)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 15)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-09 Cont ID  
Sent By jwitmer Date 2008-07-09 Time 15:52 Rev Time 0.77
Received By jwitmer Date 2008-07-09 Time 15:52 Sent To  
Notes
2008-07-09 15:52:50BUILDING PLAN REVIEW
 PERMIT: 08040824
 ADD: 223 CLEMATIS ST
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2-3) COMPLIED.
  
 4) SHEET A5.0
  
 4A) WOMENS RESTROOM 105 ANF MENS RESTROOM 107 BOTH
 INDICATE THE USE OFPAINTED WALLS ON THE WET WALL
 AREAS. PLEASE SEE 1210.2 NON-ABSORBANT SURFACES.
  
 4B-4C) COMPLIED.
  
 5-10) COMPLIED.
  
 11) NOTE, AGAIN THIS IS A FOUR STORY BUILDING, REQUIRES
 A THRESHOLD INSPECTOR, A THRESHOLD INSPECTION REPORT:
 11A)THRESHOLD INSPECTION PLANFL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 11B) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 11C) THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG,REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE. ED ADDITIONAL COMMENTS MAY APPEAR THAT
 WERE NOT PART OF THIS REVIEW.
  
 12) NEW COMMENT: INDEX SHEET INDICATES A S-2 & S-3 AS
 WELL ASM-3 & M-4 ALL MISSING.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 08:25 Rev Time 4.40
Received By jwitmer Date 2008-06-02 Time 08:25 Sent To PC
Notes
2008-06-02 08:26:27BUILDING PLAN REVIEW
 PERMIT: 08040824
 ADD: 223 CLEMATIS ST
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2-3) COMPLIED.
  
 4) SHEET A5.0
  
 4A) WOMENS RESTROOM 105 ANF MENS RESTROOM 107 BOTH
 INDICATE THE USE OF PAINTED WALLS ON THE WET WALL
 AREAS. PLEASE SEE 1210.2 NON-ABSORBANT SURFACES.
  
 4B-4C) COMPLIED.
  
 5-10) COMPLIED.
  
 11) NOTE, AGAIN THIS IS A FOUR STORY BUILDING, REQUIRES
 A THRESHOLD INSPECTOR, A THRESHOLD INSPECTION REPORT:
 11A)THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 11B) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 11C) THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE. ED ADDITIONAL COMMENTS MAY APPEAR THAT
 WERE NOT PART OF THIS REVIEW.
  
 12) NEW COMMENT: INDEX SHEET INDICATES A S-2 & S-3 AS
 WELL AS M-3 & M-4 ALL MISSING.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 09:41 Sent To  
Notes
2008-09-04 09:42:47NEW SHEETS BROUGTH IN BY MARK FROM ARCHITECT'S OFFICE.
 E-1,4 AND E5. ALSO NEW CALCULATIONS.
 OK.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-09-02 Cont ID  
Sent By dpalmer Date 2008-09-02 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2008-09-02 Time 16:02 Sent To  
Notes
2008-09-02 16:17:52** DENIED/TEMPORARY FAILED **
  
 1) NOTE: LIGHTING PERFORMACE CALCULATIONS LOCATED IN
 THE PLUMBING SUBMITTALS FOR KITCHEN EQUIPMENT.
 CALCULATIONS WERE REVIEWED. MINOR CORRECTION NEEDED.
 SPOKE TO ENGINEER AND WILL SEND NEW SHEETS ALONG WITH
 SHEETS E-1, E-4 AND E-5 BEING REVISED.
 ALSO PER MECHANICAL COMMENTS NEED NEW SHEET M-4. SPOKE
 TO DAVIS PUGA AS SHEETS IN BOTH SETS ARE NOT SIGNED,
 DATED OR SEALED. THEY CONTAIN A DIGITAL SEAL AND COLOR
 DIGITAL SIGNATURE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-02 Cont ID  
Sent By dpalmer Date 2008-09-02 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2008-09-02 Time 10:36 Sent To  
Notes
2008-09-02 10:36:41 
  
  
  
  
 ** DENIED 4TH REVIEW **
  
  
 **** PLEASE SEE COMMENTS BELOW WHICH ARE THE SAME AS
 PREVIOUS REVIEWS.
  
  
 1) NOTE: PLANS STILL DO NOT STATE ANY MAXIMUM OVER RIDE
 TIMES OR MAXIMUM OCCUPANCY SENSOR TIMES. THE NEW *KP*
 KEY PAD AS NOTED ON SHEET E-4 AND ON SYMBOL LEGEND DOES
 NOT CONTAIN ANY TIMES. THE OCCUPANCY SENSORS AS NOTED
 ON SYMBOL LEGEND DOES NOT CONTAIN ANY TIMES.
 PLEASE STATE THE REQUIRED *MAXIMUM* OVER RIDE TIMES PER
 THE SAME SECTIONS.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3.
 (( IF TIMED OVER RIDE, MUST BE A MAXIMUM OF FOUR HOURS
 OR LESS) (IF AN OCCUPANCY SENSOR IS USED FOR OVER RIDE,
 TIME IS A MAXIMUM OF 30MINUTES OR LESS)
  
 2) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2, 13-415.2.B,
 13-415.2, 13-415.2, 13-415.2.ABC.1, 13-415.2.C ETC. THE
 ENTIRE SECTION OF 13-415.2 APPLIES.
 PLEASE KNOW ON PREVIOUS CORRESPONDENCE THE LIGHTING
 PERFORMANCE CALCULATIONS GOING TO BE PLACED ON PLANS
 HOWEVER SHEETS E-1-E-6 AND ELP-1 DO NOT CONTAIN ANY
 LIGHTING CALCULATIONS TO REVIEW AND COMPARE TO THE
 LIGHTING AS SHOWN ON PLANS.
 PLEASE BE SURE TO SEE THE TRACK LIGHTING SECTIONS OF
 THE CODE.
 PLEASE SEE SPACE BY SPACE METHOD FOR DINING ALLOWANCES,
 OTHER SPACES, DECORATIVE ETC.
 CALLED AND SPOKE TO ELECTRICAL ENGINEER AND MECHANICAL
 ENGINEER. CALCULATIONS ARE REQUIRED TO MEET
 PRESCRIPTIVE REQUIREMENTS.
 BASED ON THE PLANS SUBMITTED THE LIGHTING AS SHOWN DOES
 NOT PROVIDE THE MINIMUM INFORMATION WHICH IS REQUIRED.
 PLEASE BE SURE TO SEE 13-415.2.ABC.1.1, AND .1.2 AS
 NOTED ABOVE FOR TRACK LIGHTING AND THE VA RATINGS FOR
 FIXTURES AND VA RATINGS FOR TRACK TO BE USED.
 *** PLEASE KEEP IN MIND LINE VOLTAGE TRACK VA WATTAGE
 IS BASED ON VA PER FIXTURE TIMES THE NUMBER OF FIXTURES
 ON PLANS OR 30VA PER FOOT OF TRACK,,,,,, (WHICH EVER IS
 GREATER).
 *** PLEASE SEE LOW VOLTAGE TRACK VA IS BASED ON THE
 REMOTE TYPE TRANSFORMER RATING.
 ** PLEASE BE SURE TO COMPLETE THE FIXTURE SCHEDULE WITH
 THE TRACK LIGHTING AS NOTED ON SYMBOL LEGEND.
  
 3) NOTE: PLEASE KNOW AS REQUIRED BY FLORIDA STATUTES
 553.80(2)(B) A FEE IS NOW ASSESSED BASED ON REPEAT
 COMMENTS FOR CODE COMPLIANCE. THIS IS A *STATUTORY*
 REQUIRED FEE AND IS NOT A LOCAL ENFORCEMENT RULING. THE
 FEE AMOUNT IS BASED ON 4X THE PLAN REVIEW PORTION OF
 THE BASE PERMIT FEE. IN THIS CASE THE BASE PERMIT FEE
 IS $7,300.00. THE PLAN REVIEW PORTION OF THIS FEE IS 30
 PERCENT WHICH IS $2,190.00. THAT IS THE FEE TIMES FOUR.
 THIS COMES TO $9,300.00 WHICH IS REQUIRED TO BE PAID.
 ONCE AGAIN THIS IS A *STATE* REQUIRED FEE AND IS NOT A
 LOCAL REQUIREMENT. THE SECTION OF THE FLORIDA STATUTES
 IS ATTACHED TO THE PLAN REVIEW NOTES.
 ** ONE SET OF ELECTRICAL PLANS ARE RETAINED ONCE AGAIN
 FOR FILE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-12 Cont ID  
Sent By dpalmer Date 2008-08-12 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2008-08-12 Time 16:53 Sent To  
Notes
2008-08-12 16:53:58 
 ** DENIED PLANS. **
  
  
 1) NOTE: NEW *KP* KEY PAD AS NOTED FOR
 13-415.1.ABC.1.1, .1.2. PLEASE STATE THE REQUIRED
 *MAXIMUM* OVER RIDE TIMES PER THE SAME SECTIONS.
 (( IF TIMED OVER RIDE, MUST BE A MAXIMUM OF FOUR HOURS)
 (IF AN OCCUPANCY SENSOR IS USED FOR OVER RIDE, TIME IS
 A MAXIMUM OF 30MINUTES)
  
 2) NOTE: PLEASE SEE 13-415.2.ABC.2.1, .1.2, 13-415.2.B,
 13-415.2, 13-415.2, 13-415.2.ABC.1. PLEASE SEE SECTIONS
 AS NOTED MAY NOT USE THE EXCEPTION IN THE CODE FOR THIS
 OCCUPANCY. PLEASE SEE SPACE BY SPACE METHOD FOR DINING
 ALLOWANCES, OTHER SPACES, DECORATIVE ETC.
 CALLED AND SPOKE TO ELECTRICAL ENGINEER AND MECHANICAL
 ENGINEER. THEY WILL BE REFIGURING CALCULATIONS TO MEET
 PRESCRIPTIVE REQUIREMENTS.
 BASED ON THE CALCULATIONS SUBMITTED THE DESIGN WATTAGE
 EXCEEDS THE ALLOWANCES BASED ON THIS OCCUPANCY.
 PLEASE BE SURE TO SEE 13-415.2.ABC.1.1, AND .1.2 AS
 NOTED ABOVE FOR TRACK LIGHTING AND THE VA RATINGS FOR
 FIXTURES AND VA RATINGS FOR TRACK TO BE USED.
 *** PLEASE KEEP IN MIND LINE VOLTAGE TRACK VA WATTAGE
 IS BASED ON VA PER FIXTURE TIMES THE NUMBER OF FIXTURES
 ON PLANS OR 30VA PER FOOT OF TRACK,,,,,, (WHICH EVER IS
 GREATER).
 *** PLEASE SEE LOW VOLTAGE TRACK VA IS BASED ON THE
 REMOTE TYPE TRANSFORMER RATING.
 ** PLEASE BE SURE TO COMPLETE THE FIXTURE SCHEDULE WITH
 THE TRACK LIGHTING AS NOTED ON SYMBOL LEGEND.
  
 ENGINEER WILL SEND PDF TO MAKE SURE CALCULATIONS ARE
 SET UP FOR SPACE BY SPACE AREAS. THE E-MAILING OF THE
 PDF WILL NOT CONSTITUTE AS A TECHNICAL REVIEW OF CODE
 LIGHTING CALCULATIONS FOR THE ENERGY CODE. THIS WILL BE
 TO HELP WITH A SET UP OF PERFORMANCE CALCULATIONS.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-25 Cont ID  
Sent By dpalmer Date 2008-07-25 Time 16:42 Rev Time 0.00
Received By dpalmer Date 2008-07-25 Time 16:42 Sent To PC
Notes
2008-07-25 16:42:30 
 ** DENIED2ND REVIEW **
  
 *** PLEASE KNOW IT IS IMPORTANT TO KNOW THERE ARE
 SEVERAL ITEMS WHICH ARE FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NOTES BELOW AS THERE ARE ALSO NEW
 COMMENTS AS THERE HAVE BEEN REVISIONS MADE TO PLANS
 WHICH WERE NOT PART OF THE PREVIOUS REVIEWED PLANS.
  
 ** THERE IS INFORMATION STILL NOT YET SUBMITTED
 THEREFORE A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT
 POSSIBLY BE DONE.
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3. THE ADA
 LEVELS FOR STROBES WERE SHOWN HOWEVER WHERE IS THE
 AUDIBLE LEVELS?
 FBC 11-4.28.1, .2 AN D.3(4).
  
 2) NOTE: PLEASE SEEPREVIOUS REVIEW NOTE #4. NOW A
 SUBMITTED FLA COM METHOD *B* IS BEING SUBMITTED. THE
 SECTIONS OF THE CODE WERE GIVEN ON PREVIOUS REVIEW FOR
 DEFINITIONS OF THE SCOPE OF WORK. THIS TENANT
 RENOVATION DOES NOT APPEAR TO QUALIFY AS A RENOVATION
 TO THE BUILDING. THE LIGHTING PERFORMANCE PARTOF
 TABLE *B* AND SECTIONS 13-415.2.ABC.1.1,.1.2 AND .1.3
 NEED TO BE MET. THIS IS NOT YET DONE.
 PLEASE ALSO SEE THE METHOD OF CONTROLS IS STILL SHOWN
 AS MANUAL ON OFF AND CONTINUOUS DIMMING. THIS IS NOT
 POSSIBLE.
 .
 PLEASE SEE 13-101.1.1, 13-101.1.2,13-101.3,
 13-400.0.A,13-400.0.B, 13-400.0.C,ETC.
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 MINIMUM REQUIREMENTS REQUIRED.
 THIS COMMENT IS GIVEN FOR INFORMATION FOR ALL OTHER
 TRADES HOWEVER ELECTRICAL COMPLIANCE WITH SECTIONS
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 NEED TO BE
 MET.
 THE INPUT DATA REPORT IS REQUIRED TO COORDINATE WITH
 PLANS. HOW IS THIS POSSIBLE WHEN THERE ARE SEVERAL
 ITEMS IN THE IDR WHICH ARE BLANK OR SHOWING OTHER
 INFORMATION THAN WHAT IS ON PLANS. IDR SHOWS ONLY ONE
 WALL, HOW IS THIS POSSIBLE? IDR SHOWS NO DOORS FROM
 CONDITIONED TO UNCONDITIONED SPACE, HOW IS THIS
 POSSIBLE. THE IDR SHOWS NO FLOORS, HOW IS THIS
 POSSIBLE?THERE IS HOT WATER SYSTEMS YET THE PIPING
 INSULATION IS BLANK, HOW IS THIS POSSIBLE. THESE ARE A
 FEW EXAMPLES.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORTS IS
 REQUIRED TO COORDINATE WITH PLANS COMPLETELY.
  
 3) NOTE: PLEASE SEEPREVIOUS NOTES AND
 SECTIONS13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4.
 PLANS DO NOT SHOW ENOUGH INFORMATION FOR ANY TIMED
 SCHEDULING SYSTEM. PLANS STILL SHOW NUMEROUS LOCATIONS
 WHERE STANDARD SINGLE POLE SWITCHES ARE STILL BEING
 SHOWN. HOW DO THESE STANDARD DINGLE POLE DEVICES MEET
 THE *MINIMUM* REQUIRED BY CODE WHEN THEY DO NOT MEET
 THE SECTIONS NOTED?
 SOME EXAMPLES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW NOTES.
  
 A) PLEASE VERIFY ALL OVER RIDE LOCATIONS REQUIRED.
 PLEASE SEE THAT AN OCCUPANT MUST BE ABLE TO OVER RIDE
 ANY TIME OF DAY SCHEDULING AT THE POINT OF ENTRANCE
 INTO ANY ONE SPACE. THE OCCUPANT MUST BE ABLE TO SEE
 ALL LIGHTING WHICH IS BEING CONTROLLED OR NEEDS TO MEET
 EXCEPTIONS.
  
 B) PLEASE SEE SOME LIGHTING CONTROLS SHOWN ON PLANS ARE
 STANDARD SWITCHES. HOW IS THIS POSSIBLE WHEN AUTOMATED
 CONTROLS ARE REQUIRED?
 SOME LOCATION EXAMPLES ARE HALL, ACCENT LIGHTS, LIQUOR
 STORAGE, CLOSET ETC
 ** THIS IS NOT ALL LOCATIONS AS THERE ARE OTHERS. ONLY
 SOME ARE GIVEN AS EXAMPLES.
  
 C) PLEASE SEE PLANS ARE MISSING REQUIRED SEPARATE SPACE
 CONTROLS. THESE ARE REQUIRED TO BE AUTOMATED OR PART OF
 A SYSTEM WITH OVER RIDES.
  
 D) PLEASE PROVIDE A COMPLETE SYSTEM/ETC FOR MINIMUM
 LIGHTING CONTROLS AS REQUIRED PER SECTIONS ABOVE.
 PLEASE PROVIDE COMPLETE SCHEDULE OF SYSTEM, SCHEDULE
 FOR ALL ITEMS ON THE DIMMING PANEL.
 AS NO SCHEDULE WAS SUBMITTED THERE ARE SEVERAL ITEMS
 WHICH CAN NOT BE DETERMINED FOR CODE COMPLIANCE WITH
 REQUIRED LIGHTING CONTROLS AS WELL AS OTHER COMMENTS.
 PLEASE SEE THE FOLLOWING COMMENT.
 PLEASE KNOW COMPLETE COMPLIANCE FOR AUTOMATED LIGHTING
 CONTROLS IS REQUIRED.THIS IS A BUILDING OVER 5000 SQ
 FT.
  
  
 4) NOTE: PLEASE KNOW AS PLANS CLEARLY INDICATE NORMAL
 LIGHTING BEING CONTROLLED THROUGH A DIMMING PANEL OF
 SOME KIND PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS FOR MINIMUM LIGHTING LEVELS.
 PLEASE KNOW THE MINIMUM LEVELS FOR LIGHTING SHALL NOT
 BE PERMITTED TO DIM BELOW THE 1FT CANDLE REQUIRED BY
 THE LIFE SAFETY CODE, NFPA-101 7.8, 7.9. 7.8.1.3
 PLEASE PROVIDE MORE INFORMATION. THIS WAS NOT
 SUBMITTED. THE PLANS NOW INDICATE A NOTE WHICH STATES
 LIGHTING LEVELS MUST MEET CODE HOWEVER IF THE DIMMING
 SYSTEM IS NOT DESIGNED TO BE SPECIFIC THE LIGHTING
 LEVELS MAY VERY WELL BE DIMMED TO A LIGHTING LEVEL OF
 *0* WHEN OCCUPIED UNDER NORMAL CONDITIONS. PLEASE
 DESIGN/SPECIFY THE DEVICE SET LEVELS ETC
 FBC 106.1.2.
 FAC 61G15-33.004
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON
 THE EXISTING 1000AMP MAIN IN WHICH THE PROPOSED
 SERVICE. PLEASE SEE THE NEXT FEW NOTES AS THE RISER HAS
 BEEN COMPLETELY REVISED AND THERE WILL BE COMMENTS
 BELOW WHICH WILL AFFECT SERVICE LOADS CALCULATIONS..
 PLEASE OBTAIN ALL RECENT LOADS WHICH HAVE BEEN ADDED TO
 BUILDING AND POSSIBLY THIS SERVICE.
 PLEASE SEE 220.87. A LOAD STUDY MAY NOT BE ACCURATE AS
 NEW LOADS HAVE CONTINUALLY BEEN ADDED AND SOME LOADS
 HAVE NOT BEEN COMPLETED ON SERVICE.
 PLEASE SEE CODES REFLECTED ON THE CALCULATIONS NEED TO
 COORDINATE WITH CODE. PLEASE VERIFY 220.44 AS NOTED FOR
 ALL OTHER LOADS. HOW ARE LIGHTING LOADS UNDER THIS SAME
 CODE SECTION?
 PLEASE SEE 220.42 AND 220.43.
  
 6) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #9. TRACK
 LIGHTING LOADS ARE STILL NOT SHOWN.
 PLEASE SEE NOTE #5 ABOVE IN WHICH SECTION 220.43 WAS
 BRIEFLY SATED FOR LOAD CALCULATIONS. PLEASE SHOW ALL
 TRACK LIGHTING LOADS AND HOW THEY ARE DERIVED. AS THESE
 ARE SPECIFIED AT THIS TIME COMPLIANCE CAN NOT BE
 VERIFIED. THIS WILL AFFECT THE DIMMER PANELS.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #10. PLEASE SEE THESE
 WERE NOT REVISED. TO MEET THE EXCEPTION IN THE CODE
 ONLY A SPECIFIC BREAKER MAY BE USED. A SNAP ON TYPE
 DEVICE IS NOT LISTED FOR PERMANENT INSTALLATION. PLEASE
 SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS. THESE
 SHALL BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN ANY
 ONE AREA.
  
 8) NOTE: PLEASE SEE NEW RISER AS TENANT IS NOW SHOWN
 BEING FED FROM TWO COMPLETELY SEPARATE SERVICES WHICH
 IS NOT PERMITTED.
 THERE ARE NO SEPARATE VOLTAGES ETC WHICH WOULD REQUIRE
 THE ELECTRICAL TO BE FED FROM SEPARATE SERVICES. THERE
 ARE NO OTHER EXCEPTIONS SHOWN TO JUSTIFY.
 PLEASE KNOW THE FIRE MARSHAL ALSO HAS CONCERN OVER
 MULTIPLE MAIN DISCONNECTS FOR ONE TENANT. NO SIGNAGE,
 NO NOTES, NO INFORMATION OF LABELING ETC IS SHOWN. AS
 NOTED ABOVE NO LOAD CALCULATIONS ETC WERE SUBMITTED. AS
 THIS IS NO COMPLETE AT THIS TIME THERE ARE MANY
 UNANSWERED QUESTIONS.
 230, 240, 220 ET
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE KNOW ONE
 SET OF ELECTRICAL PLANS HAVE BEEN RETAINED BY THIS
 OFFICE/REVIEWER.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 07:43 Rev Time 0.00
Received By dpalmer Date 2008-05-05 Time 07:43 Sent To  
Notes
2008-05-05 07:43:26** DENIED**
  
 *** PLEASE KNOW IT IS IMPORTANT TO KNOW THERE ARE
 SEVERAL ITEMS NOT YET SUBMITTED FOR CODE COMPLIANCE IN
 DESIGN. IT IS IMPORTANT TO UNDERSTAND THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES AT A
 MINIMUM FOR THE REVIEWER ARE STATED ON ELECTRICAL PLANS
 AS WELL AS COVER SHEET.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** SOME CODES ARE ALREADY STATED HOWEVER NOT ALL
 RELEVANT AS STATED ABOVE. THIS IS ONLY FOR ELECTRICAL
 REVIEW AND OTHER CODES FROM OTHER TRADES MAY CERTAINLY
 BE REQUIRED.
  
 2) NOTE: PLEASE SEE FIRE REVIEW AND BUILDING REVIEW
 COMMENTS AS THIS BUILDING IS CONSIDERED MORE THAN THREE
 STORIES.
 SHEET A1.0 CLEARLY STATES THIS IS A *2-STORY* BUILDING
 HOWEVER THIS IS NOT THE CASE. THE BUILDING BY
 DEFINITION IS AT MINIMUM 4-STORY. PLEASE SEE COMMENTS
 FROM BUILDING REVIEW.
 FOR INFORMATION: THE ORIGINAL FIRE WALLS WHICH USED TO
 SEPARATE PARTS OF THIS STRUCTURE ARE NO LONGER FIRE
 WALLS BY DEFINITION.
  
 3) NOTE: PLEASE SEE SOME LOCATIONS ARE MISSING
 HORN/STROBE FOR ADA COMPLIANCE PER FBC 11-4.28.1, .2 AN
 D.3(4).
 PLEASE SEE ONE LOCATION FOR EXAMPLE IS THE BATHROOMS.
 NOTE #9 ON PLANS MENTIONS TO INSTALL NEW DEVICES TO
 MATCH EXISTING. IT IS NOT POSSIBLE TO MATCH EXISTING
 WHEN THERE ARE NOT EXISTING DEVICES. THIS SPACE HAS
 BEEN COMPLETELY GUTTED.
 PLEASE SHOW DEVICES FOR COMPLIANCE.
  
 4) NOTE: PLEASE SEE THE SUBMITTED METHOD *A* ENERGY
 CALCULATIONS MAY NOT BE USED. THIS IS FOR A TENANT
 BUILD OUT ONLY, THIS IS NOT FOR A WHOLE BUILDING.
 PLEASE SEE THE DEFINITIONS. METHOD *A* MAY BE USED ON
 ADDITIONS AND WHOLE BUILDINGS OR WHEN *ALL BUILDING
 COMPONENTS* ARE KNOWN. THIS SCENARIO AS SUBMITTED WOULD
 NOT FALL UNDER THIS CRITERIA.
 PLEASE SEE 13-101.1.1, 13-101.1.2,13-101.3,
 13-400.0.A,13-400.0.B, 13-400.0.C,ETC.
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 MINIMUM REQUIREMENTS REQUIRED.
 THIS COMMENT IS GIVEN FOR INFORMATION FOR ALL OTHER
 TRADES HOWEVER ELECTRICAL COMPLIANCE WITH SECTIONS
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 NEED TO BE
 MET.
 AS THE CALCULATIONS SUBMITTED ARE NOT VALID PLEASE
 SUBMIT COMPLETE LIGHTING PERFORMANCE CALCULATIONS UNDER
 METHOD PERMITTED.
 PLEASE CALL TO GO OVER THIS.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORTS IS
 REQUIRED TO COORDINATE WITH PLANS COMPLETELY.
  
 A) PLEASE SEE ONE EXAMPLE IS THAT THE METHOD OF
 CONTROLS FOR LIGHTING IS SHOWN AS *MANUAL ON/OFF*. HOW
 IS THIS POSSIBLE WHEN ALL LIGHTING IS REQUIRED TO
 CONTAIN AUTOMATED CONTROLS?
 PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO
 LIGHTING CONTROLS.
  
 B) PLEASE SEE ANOTHER EXAMPLE OF ITEMS ON THE IDR WHICH
 DO NOT COORDINATE WITH PLANS IS THE NUMBER OF LIGHT
 FIXTURES SHOWN. PLEASE SEE THE TOTAL NUMBER OF FIXTURES
 SHOWN ON THE IDR FOR INTERIOR IS *8*. THIS IS NOT
 POSSIBLE WHEN THERE IS CLEARLY DOZENS OF FIXTURES ON
 PLANS.
  
 C) PLEASE SEE ANOTHER EXAMPLE OF ITEMS ON PLANS WHICH
 DO NOT COORDINATE WITH THE IDR IS THE EXTERIOR
 FIXTURES. PLEASE SEE THIS IS ACTUALLY BLANK ON THE IDR
 YET THERE ARE CLEARLY EXTERIOR LIGHT FIXTURES ON PLANS.
 PLEASE SEE 13-415.2.ABC.1.3 AS NOTED ABOVE FOR EXTERIOR
 LIGHTING PERFORMANCE.
  
 D) PLEASE BE SURE TO SEE THE SECTIONS OF CODE AS NOTED
 ABOVE SPECIFICALLY FOR TRACK LIGHTING.
 BASED ON THE PLANS THE FIXTURE LEGEND IS NOT COMPLETE.
 ALL FIXTURES MUST BE LABELED. ALL FIXTURES MUST BE
 FIGURED INTO THE PERFORMANCE CALCULATIONS OF SPACE.
  
 ** IMPORTANT**
 THESE EXAMPLES ABOVE ARE NOT IN ANYWAY AN EXHAUSTED
 LIST OF ALL ITEMS ON PLANS WHICH DO NOT COORDINATE WITH
 THE SUBMITTED CALCULATIONS. THESE ARE GIVEN AS A
 BENEFIT ONLY AS CODE COMPLIANCE HAS NOT BEEN ACHIEVED.
 PLEASE BE SURE TO GO OVER COMMENTS AND COORDINATE ALL.
  
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
  
 A) PLEASE VERIFY ALL OVER RIDE LOCATIONS REQUIRED.
 PLEASE SEE THAT AN OCCUPANT MUST BE ABLE TO OVER RIDE
 ANY TIME OF DAY SCHEDULING AT THE POINT OF ENTRANCE
 INTO ANY ONE SPACE. THE OCCUPANT MUST BE ABLE TO SEE
 ALL LIGHTING WHICH IS BEING CONTROLLED OR NEEDS TO MEET
 EXCEPTIONS.
  
 B) PLEASE SEE SOME LIGHTING CONTROLS SHOWN ON PLANS ARE
 STANDARD SWITCHES. HOW IS THIS POSSIBLE WHEN AUTOMATED
 CONTROLS ARE REQUIRED?
 SOME LOCATION EXAMPLES ARE HALL, ACCENT LIGHTS, LIQUOR
 STORAGE, CLOSET ETC
 ** THIS IS NOT ALL LOCATIONS AS THERE ARE OTHERS. ONLY
 SOME ARE GIVEN AS EXAMPLES.
  
 C) PLEASE SEE PLANS ARE MISSING REQUIRED SEPARATE SPACE
 CONTROLS. THESE ARE REQUIRED TO BE AUTOMATED OR PART OF
 A SYSTEM WITH OVER RIDES.
  
 D) PLEASE PROVIDE A COMPLETE SYSTEM/ETC FOR MINIMUM
 LIGHTING CONTROLS AS REQUIRED PER SECTIONS ABOVE.
 PLEASE PROVIDE COMPLETE SCHEDULE OF SYSTEM, SCHEDULE
 FOR ALL ITEMS ON THE DIMMING PANEL.
 AS NO SCHEDULE WAS SUBMITTED THERE ARE SEVERAL ITEMS
 WHICH CAN NOT BE DETERMINED FOR CODE COMPLIANCE WITH
 REQUIRED LIGHTING CONTROLS AS WELL AS OTHER COMMENTS.
 PLEASE SEE THE FOLLOWING COMMENT.
 PLEASE KNOW COMPLETE COMPLIANCE FOR AUTOMATED LIGHTING
 CONTROLS IS REQUIRED.THIS IS A BUILDING OVER 5000 SQ
 FT.
  
 E) PLEASE SEE SECTION 13-415.1.ABC.1.4 FOR EXTERIOR
 LIGHTING CONTROLS. PLANS SHOW THESE EXTERIOR LIGHTS
 THROUGH DIMMING PANEL. PLEASE SEE THE SECTION OF CODE
 WHICH PERMITS TWO METHODS.
  
  
 ** IT IS IMPORTANT TO KNOW AS NO LIGHTING CONTROL
 SYSTEM, OR DEVICES WERE SUBMITTED AS PART OF THE DESIGN
 THESE SPECIFIC ITEMS COULD NOT BE REVIEWED. CODE
 COMPLIANCE WAS REQUIRED TO BE ON DESIGN FOR INITIAL
 REVIEW. THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH COULD NOT BE MADE AT THIS TIME.
  
 6) NOTE: PLEASE KNOW AS PLANS CLEARLY INDICATE NORMAL
 LIGHTING BEING CONTROLLED THROUGH A DIMMING PANEL OF
 SOME KIND PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS FOR MINIMUM LIGHTING LEVELS.
 PLEASE KNOW THE MINIMUM LEVELS FOR LIGHTING SHALL NOT
 BE PERMITTED TO DIM BELOW THE 1FT CANDLE REQUIRED BY
 THE LIFE SAFETY CODE, NFPA-101 7.8, 7.9.
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2.
 FAC 61G15-33.004
  
 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON
 THE EXISTING 1000AMP MAIN IN WHICH THE NEW 600AMP MAIN
 IS BEING ADDED.
 PLEASE OBTAIN ALL RECENT LOADS WHICH HAVE BEEN ADDED TO
 BUILDING AND POSSIBLY THIS SERVICE.
 PLEASE SEE 220.87. A LOAD STUDY MAY NOT BE ACCURATE AS
 NEW LOADS HAVE CONTINUALLY BEEN ADDED AND SOME LOADS
 HAVE NOT BEEN COMPLETED ON SERVICE.
 PLEASE SEE CODES REFLECTED ON THE CALCULATIONS NEED TO
 COORDINATE WITH CODE. PLEASE VERIFY 220.44 AS NOTED FOR
 ALL OTHER LOADS. HOW ARE LIGHTING LOADS UNDER THIS SAME
 CODE SECTION?
 PLEASE SEE 220.42 AND 220.43.
  
 8) NOTE: PLEASE VERIFY HOW THE LOADS ON THE LIGHTING
 DIMMING PANELS ARE SHOWN EXCEEDING THE RATING OF THE
 FEEDER.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3, 230.42
 ETC PLEASE KNOW THIS WILL AFFECT OTHER LOADS ON PANELS,
 SERVICE ETC. PLEASE BE SURE TO FOLLOW THROUGH WITH
 SERVICE.
  
 9) NOTE: PLEASE SEE NOTE #7 ABOVE IN WHICH SECTION
 220.43 WAS BRIEFLY SATED FOR LOAD CALCULATIONS. PLEASE
 SHOW ALL TRACK LIGHTING LOADS AND HOW THEY ARE DERIVED.
 AS THESE ARE SPECIFIED AT THIS TIME COMPLIANCE CAN NOT
 BE VERIFIED. THIS WILL AFFECT THE DIMMER PANELS.
  
 10) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF
 EMERGENCY LIGHTS. THESE SHALL BE CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT IN ANY ONE AREA.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2008-11-21 Cont ID  
Sent By mwennerg Date 2008-11-21 Time 13:44 Rev Time 0.00
Received By mwennerg Date 2008-11-21 Time 13:44 Sent To  
Notes
2008-11-21 13:46:32SEE PERMIT #08090229 FOR PLAN REVIEW OF
 HOOD/SUPPRESSION REVISION DATED 11/20/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-09-05 Cont ID  
Sent By mwennerg Date 2008-09-05 Time 12:41 Rev Time 0.00
Received By mwennerg Date 2008-09-05 Time 12:41 Sent To  
Notes
2008-09-05 12:41:45STAMPED SHEETS A-1.0, E-6, AND FS-1.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-08-20 Cont ID  
Sent By mawillia Date 2008-08-20 Time 12:44 Rev Time 0.00
Received By mawillia Date 2008-08-20 Time 12:20 Sent To  
Notes
2008-08-20 12:43:38*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEWS HAVE NOT BEEN ADDRESSED:
  
  
 11.NFPA 72 - 2002 EDITION SHALL BE REFERENCED. PLEASE
 BE ADVISED THAT THE 1999 EDITION IS LISTED IN B UNDER
 THE FIRE ALARM SYSTEM SCOPE ON SHEET E-6.CHANGE TO
 2002 EDITION, NOT 1999.
  
 13.IN REFERENCE TO THE FIRE SPRINKLER SYSTEM, NFPA 13
 - 2002 EDITION SHALL BE REFERENCED.ADD CODE REFERENCE
 TO SHEET FS-1
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-23 Cont ID  
Sent By mwennerg Date 2008-07-23 Time 10:24 Rev Time 0.00
Received By mwennerg Date 2008-07-23 Time 10:24 Sent To  
Notes
2008-07-23 10:34:21***DENIED***
  
 SOME OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING FOR CORRECTION:
  
 01. IN ADDITION TO DEMOLITION, THIS REQUIREMENT APPLIES
 TO CONSTRUCTION AND ALTERATION. (NFPA 241)
  
 02. OK
  
 03. OK
  
 04. PLANS STILL DO NOT CLEARLY ILLUSTRATE COMPLIANCE
 WITH REQUIREMENT REGARDING PANIC AND FIRE EXIT
 HARDWARE. SEE THE DOOR SCHEDULE UNDER PANIC COLUMN.
 PLEASE ADD SPECIFIC INFORMATION TO DOOR SHEDULE.
  
 05. OK
  
 06. OK
  
 07. OK
  
 08. OK
  
 09. OK
  
 10. OK
  
 11. THE FIRE ALARM SCOPE STILL REFERENCES THE 1999
 EDITION. FIRE ALARM SHALL COMPLY WITH NFPA 72, 2002
 EDITION. PLEASE REMOVE EARLIER CODE CYCLE REFERENCE.
  
 12. OK
  
 13. NOT ADDRESSED. PLEASE ADD NOTE NFPA 13, 2002
 EDITION TO GOVERNING CODE OR FIRE SPRINKLER SHEET
 FS-1.
  
 14. NOT ADDRESSED. THE SUBMITTED PLAN SHEETS DO NOT
 ACTUALLY CORRELATE WITH THE LIST OF DRAWINGS AS SHOWN
 ON SHEET A1.0.
  
  
 NEW COMMENTS:
  
 01. OCCUPANT LOAD SIGN WILL BE REQUIRED AT TIME OF FIRE
 FINAL INSPECTION. CONTACT WPB BUREAU OF FIRE PREVENTION
 AT (561) 804-4724 FOR ASSISTANCE.
  
 02. PLEASE PROVIDE LIFE SAFETY SHEET ILLUSTRATING MAX.
 TRAVEL DISTANCE COMPLIANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-27 Cont ID  
Sent By mawillia Date 2008-05-27 Time 12:30 Rev Time 0.00
Received By mawillia Date 2008-05-27 Time 10:07 Sent To  
Notes
2008-05-27 12:30:15*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES, ETC.).
  
 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 04.SINCE THE TOTAL OCCUPANT LOAD LISTED ON SHEET A1.0
 IS 172 PEOPLE, VERIFY THAT THE DOOR(S) IN THE REQUIRED
 MEANS OF EGRESS FROM AN AREA HAVING AN OCCUPANT LOAD OF
 100 OR MORE PERSONS SHALL BE PROVIDED WITH PANIC
 HARDWARE OR FIRE EXIT HARDWARE.
  
 05.THE NUMBER OF EXIT LIGHTS SHOWN ON SHEET A2.1 DO
 NOT CORRELATE WITH THAT OF SHEET E-4.
  
 06.THE FLOOR PLAN LEGEND ON SHEET A2.0 MAKES
 REFERENCE TO DOOR SCHEDULE ON SHEET A6.HOWEVER, A
 DOOR SCHEDULE ON SHEET A6 COULD NOT BE FOUND.
  
 07.IT APPEARS ON SHEET A2.0 THAT THE JANITOR'S CLOSET
 DOOR (#10) OPENS IN THE PATH OF AN AISLE CORRIDOR MORE
 THAN ONE HALF THE WIDTH OF THE AISLE.PLEASE EXPLAIN.
  
 08.ON SHEET A4.2, DISPLAY/SHOW THE NUMERICAL ADDRESS
 AT THE BUILDING'S FRONT ELEVATION.AS PER WEST PALM
 BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 09.IT IS STATED THAT ON SHEET A5.0 THAT INTERIOR
 FINISHES SHALL COMPLY WITH NFPA 101 - 38.3.3;HOWEVER
 THIS SECTION OF NFPA DEALS WITH NEW BUSINESS
 OCCUPANCIES.
  
 10.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM.AMEND THE FIRE ALARM SYSTEM'S SEQUENCE OF
 OPERATION ON SHEET E-6 TO REFLECT THIS AHJ
 REQUIREMENT.
  
 11.NFPA 72 - 2002 EDITION SHALL BE REFERENCED. PLEASE
 BE ADVISED THAT THE 1999 EDITION IS LISTED IN B UNDER
 THE FIRE ALARM SYSTEM SCOPE ON SHEET E-6.
  
 12.SHOW THE LOCATION OF THE WATER FLOW DEVICE AND THE
 TAMPER SWITCH FOR THE FIRE ALARM/FIRE SPRINKLER
 SYSTEM.
  
 13.IN REFERENCE TO THE FIRE SPRINKLER SYSTEM, NFPA 13
 - 2002 EDITION SHALL BE REFERENCED.
  
 14.THE SUBMITTED PLAN SHEETS DO NOT ACTUALLY
 CORRELATE WITH THE LIST OF DRAWINGS AS SHOWN SO SHEET
 A1.0
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESWS, INCLUDE A
 RESPONSE LETTER INDICATING WHERE ON THE APPROPIATE PLAN
 SHEET EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2008-11-13 Cont ID  
Sent By kstevens Date 2008-11-13 Time 09:59 Rev Time 0.00
Received By kstevens Date 2008-11-13 Time 09:59 Sent To  
Notes
2008-11-13 10:22:25REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHTS P-1 & P-2 DRAWING REFERENCE NOTES 5A, (P-1),
 AND GAS RISER DIAGRAM, (P-2), INDICATE THE MANUAL SHUT
 OFF VALVE AND EMERGENCY SHUT OFF VALVE UP IN THE
 CEILING. THIS IS NOT APPROVED. ALSO THERE IS NO
 REQUIRED UNION INDICATED DOWNSTREAM OF THE MANUAL SHUT
 OFF VALVE. (SEE THE FOLLOWING):
 __ EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 2. SHTS P-1 & P-2 THE FLOOR PLAN, GAS SYSTEM
 CALCULATIONS TABLE & THE GAS RISER DIAGRAM SHOW ITEM
 18, PIZZA OVEN. PER THE CONTRACTOR, ITEM 18 HAS BEEN
 DELETED. THIS WAS INDICATED WHEN THE CONTRACTOR APPLIED
 FOR THE GAS PERMIT. THE PROVISO INDICATED ON THE PLANS
 REQUIRED MANUF. SPECIFICATION SHEETS FOR ITEM 18. THE
 GAS PERMIT WAS ISSUED WITH THE STIPULATION THAT THE
 REVISIONS DELETES ITEM 18.
  
 3. SHT P-2 GAS SYSTEM CALCULATIONS BTU'S DO NOT REFLECT
 THE MANUF. SPECIFICATION SHEETS SUBMITTED PLEASE
 CORRELATE. THE FURTHEST OUTLET IS 145 FEET NOT 140 FEET
 AS INDICATED. THIS IS WITH THE LENGTH OF PIPE FROM THE
 METER TO THE FIRST RISE, (11 FEET OF 2-1/2" PIPE), THE
 LENGTH OF PIPE THRU THE OUTSIDE WALL THRU SLEEVE, AND
 THE LENGTH OF DROP DOWNSTREAM OF THE SLEEVED PIPE.
 PLEASE INDICATE ALL PIPE LENGTHS AND RECALCULATE TOTAL
 DEVELOPED LENGHT AND INDICTE ON THE GAS SYSTEM
 CALCULATIONS.
  
 4. SHT P-2 GAS RISER DIAGRAM HAS SOME PIPE SIZING THAT
 IS INCORRECT. 1-1/4" PIPE IS REQUIRED TO THE SHUT OFF
 VALVE TO THE WATER HEATER. (1" INDICATED). -- 2" PIPE
 IS REQUIRED UP TO ITEM NUMBER 13, (NO PIPE SIZE
 INDICATED). -- 1-1/2" REQUIRED UP TO ITEM 10, (NO PIPE
 SIZE INDICATED). -- 1-1/4" REQUIRED UP TO ITEM 11, (NO
 PIPE SIZE INDICATED). -- 1" REQUIRED UP TO ITEM 9, (NO
 PIPE SIZE INDICATED). -- THE FOLLOWING STUB OUTS TO THE
 APPLIANCES ARE NOT CORRECT. -- 1" REQUIRED TO SHUT OFF
 VALVE FOR ITEM 15. -- 1-1/4" REQUIRED UP TO THE SHUT
 OFF VALVES FOR ITEMS 17, 13 & 10.
  
 5. SHT P-3 FOOD SERVICE PLUMBING EQUIPMENT SCHEDULE.
 REVISIED MANUFACTURE & MODEL NUMBER CHANGED TO READ
 "REFER TO KITCHEN CONSULTANT DRAWINGS". KITCHEN
 CONSULTANT DRAWINGS WERE NOT SUBMITTED. IF THE GAS
 EQUIPMENT HAS CHANGED, THEN THE MANUFACTURE
 SPECIFICATION SHEETS FOR THE GAS EQUIPMENT SHALL BE
 SUBMITTED AND SHALL CORRELATE WITH THE GAS LOAD
 INDICATED ON THE GAS RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-08-27 Cont ID  
Sent By kstevens Date 2008-08-27 Time 16:21 Rev Time 0.00
Received By kstevens Date 2008-08-27 Time 16:20 Sent To  
Notes
2008-08-27 16:39:52 
  
  
 PASSED/PROVISO
  
 MANUF. SPEC. SHEETS FOR THE WATER HEATER AND THE PIZZA
 OVEN NOT SUBMITTED. SUBMIT AT TIME OF GAS PERMIT
 APPLICATION.
  
 GAS PIPING NOT CORRECT. 2-1/2" REQUIRED TO ITEM 17.--
 1-1/4" REQUIRED TO SHUT OFF VALVE FOR WATER HEATER--
 2" REQUIRED TO ITEM 13,--1-1/2" REQUIRED TO ITEM
 10.--1-1/4" MINIMUM REQUIRED THRU ITEM 9 INCLUDING
 SHUT OFF VALVE.--1-14" REQUIRED FOR SUPPLY AND SHUT
 OFF VALVE FOR ITEM 10.--1" REQUIRED FOR SUPPLY AND
 SHUT OFF VALVE FOR ITEM 13.--1" REQUIRED FOR SUPPLY
 AND SHUT OFF VALVE FOR ITEM 15.--1-14" REQUIRED FOR
 SUPPLY AND SHUT OFF VALVE FOR ITEM 17. ---A
 REVISION IS REQUIRED FOR SHT P-2 GAS RISER DIAGRAM
 REFLECTING THESE AS SOON AS POSSIBLE.
  
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-08-11 Cont ID  
Sent By kstevens Date 2008-08-11 Time 10:16 Rev Time 0.00
Received By kstevens Date 2008-08-11 Time 10:16 Sent To  
Notes
2008-08-11 10:18:03DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR PERMIT:
  
 A. OK
 B. OK
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO MANUF
 SHEETS FOUND.
 ******NO RESPONSE, COMMENT NOT ADDRESSED
  
 D. N/A
 E. N/A
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM
 OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE
 RISER DIAGRAM.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By kstevens Date 2008-07-21 Time 09:45 Rev Time 0.00
Received By kstevens Date 2008-07-21 Time 09:45 Sent To  
Notes
2008-08-11 09:52:22DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR PERMIT:
  
 A. OK
 B. OK
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO MANUF
 SHEETS FOUND.
  
 D. N/A
 E. N/A
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM
 OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE
 RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-05-12 Cont ID  
Sent By kstevens Date 2008-05-12 Time 09:42 Rev Time 0.00
Received By kstevens Date 2008-05-12 Time 09:42 Sent To  
Notes
2008-08-11 09:45:07DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL).
  
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 D. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 E. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-11-21 Cont ID  
Sent By lmartine Date 2008-11-21 Time 13:37 Rev Time 0.00
Received By lmartine Date 2008-11-21 Time 13:37 Sent To  
Notes
2008-11-21 13:37:57FIRE REVIEW ROUTED TO WENNEGREN

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-11-20 Cont ID  
Sent By adarroug Date 2008-11-20 Time 11:33 Rev Time 0.00
Received By adarroug Date 2008-11-20 Time 11:33 Sent To P
Notes
2008-11-20 11:33:35TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-11-17 Cont ID  
Sent By adarroug Date 2008-11-17 Time 14:58 Rev Time 0.00
Received By adarroug Date 2008-11-17 Time 14:58 Sent To M
Notes
2008-11-17 14:58:56TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-11-13 Cont ID  
Sent By adarroug Date 2008-11-13 Time 13:33 Rev Time 0.00
Received By adarroug Date 2008-11-13 Time 13:33 Sent To M
Notes
2008-11-13 13:35:06TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-10-31 Cont ID  
Sent By adarroug Date 2008-10-31 Time 16:34 Rev Time 0.00
Received By adarroug Date 2008-10-31 Time 16:34 Sent To  
Notes
2008-10-31 16:34:45TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-10-28 Cont ID  
Sent By adarroug Date 2008-10-28 Time 17:00 Rev Time 0.00
Received By adarroug Date 2008-10-28 Time 17:00 Sent To P
Notes
2008-10-28 17:00:44TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 11:59 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 11:59 Sent To M
Notes
2008-10-06 12:00:02TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 09:46 Sent To  
Notes
2008-10-06 09:47:20TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 11:51 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 11:51 Sent To B
Notes
2008-09-25 11:51:51TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 16:43 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 16:43 Sent To  
Notes
2008-08-26 12:11:558-26-08 TO "COMM" BD. #53.
2008-08-25 16:44:47WAITING FOR "COMM" BD.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 11:10 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 11:10 Sent To  
Notes
2008-08-08 11:14:56TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-26 Cont ID  
Sent By shill Date 2008-06-26 Time 16:40 Rev Time 0.00
Received By shill Date 2008-06-26 Time 16:40 Sent To  
Notes
2008-06-30 13:56:53TO "COMM" BD#13
2008-06-26 16:41:16WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2008-05-01 Time 13:00 Sent To  
Notes
2008-05-01 13:00:36TO "COMM" BD#49

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 12:10 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 12:09 Sent To PC
Notes
2008-11-22 12:10:30MECH HOOD REVISED PLANS REVIEWED UNDER SEPARATE PERMIT
 #08070086

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 11:33 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 11:33 Sent To PC
Notes
2008-11-22 11:33:53REVISED M1 AND COOLING LOAD CALCS.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-11-04 Cont ID  
Sent By tgordon Date 2008-11-04 Time 08:24 Rev Time 1.30
Received By tgordon Date 2008-11-04 Time 08:24 Sent To  
Notes
2008-11-04 08:38:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
  
 1) THE COOLING LOAD CALCULATIONS NEED TO BE REVISED AS
 THE A/C EQUIPMENT AND THE ENGINEER OF RECORD HAS
 CHANGED, PER 13-407.1.ABC.1.1.
  
 2) OUTSIDE AIR CALCULATIONS ARE INCORRECT, SEE ATTACHED
 COPY OF THE ARCHITECTURAL PLAN'S SQUARE FOOTAGE AND
 SEATING CAPACITY. PLEASE CORRECT PER 2004 FBC/M 403.3.
 (ALSO THE OUTSIDE AIR CALCULATIONS ARE MISSING THE BAR
 AREA).
  
 3) OUTSIDE AIR CALCULATIONS SHOW 'ADJUST PER EXCEPTION
 403.3. THE EXCEPTION READS "EXCEPTION: THE OCCUPANT
 LOAD IS NOT REQUIRED TO BE DETERMINED, BASED ON THE
 ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3 WHERE APPROVED STATISTICAL DATA DOCUMENT THE
 ACCURACY OF AN ALTERNATE ANTICIPATED OCCUPANT DENSITY".
 PLEASE SUBMIT A COPY OF THE CODE SECTION THAT PERMITS A
 50% REDUCTION OF OUTSIDE AIR.
  
 4) THE AIR BALANCE DIAGRAM IS INCORRECT. SEE ATTACHED
 COPY OF HOOD PLAN FOR THE KITCHEN HOOD FANS. PLEASE
 CORRECT PER 2004 FBC 13-409.1.ABC.3.6.1.
  
 5) THE PLAN SHOWS FLEXIBLE DUCT BEING USED AT THE
 BATHROOM EXHAUST FANS. EXHAUST DUCTS SHALL BE METAL,
 PER 2004 FBC 501.4.
  
 6) THE 200,000 BTU GAS WATER HEATER IN THE JANITOR'S
 CLOSET IS A CONFINED SPACE, SEE 2004 FBC/FG 304.5.1.
 PLEASE PROVIDE FOR COMBUSTION AIR PER 2004 FBC/FG 304.1
 IF THE TRANSFER GRILL IS FOR COMBUSTION AIR, SEE 2004
 FBC/FG 304.6.2 ONE PERMANENT OPENING. PLEASE CORRECT.
  
 7) THE JANITOR'S CLOSET ALSO HAS AN EXHAUST FAN IN IT,
 PLEASE PROVIDE FOR MAKE-UP AIR TO THE GAS WATER HEATER,
 PER 2004 FBC/FG 304.4 AND 304.9.1.
  
 8) PLEASE PROVIDE COMBUSTION AND MAKE-UP AIR
 CALCULATIONS FOR THE GAS WATER HEATER, PER 2004 FBC/FG
 304.
  
 9) PLEASE SHOW THE SIZE OF THE EXISTING OUTSIDE AIR
 DUCTWORK AS ONE IS SUPPLING TWO 14" OUTSIDE AIR DUCTS,
 SEE 2004 FBC/M 603.2.
  
 10) A/C SYSTEM MODEL NUMBERS AHU 40RM-012H AND ACU
 38ARD014 LISTED ON THE A/C EQUIPMENT SCHEDULE COULD NOT
 BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT
 MANUFACTURE SPECIFICATION SHEETS, PER 2004 FBC
 13-407.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-10-06 Cont ID  
Sent By tgordon Date 2008-10-06 Time 14:13 Rev Time 1.30
Received By tgordon Date 2008-10-06 Time 14:13 Sent To  
Notes
2008-10-06 14:29:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS AND COOLING LOAD CAL'S.
 *** DENIED ***
  
 1) THE ENGINEER OF RECORD IS J. DAVID PUGA WITH PUGA
 AND ASSOCIATES INC. (305) 661-7700 ONLY HE CAN MAKE
 REVISIONS TO THE MECHANICAL PLANS AND COOLING LOAD
 CAL'S. IF YOU ARE CHANGING ENGINEERS YOU MUST SUBMIT A
 NOTARIZED LETTER FROM J. DAVID PUGA OR THE GENERAL
 CONTRACTOR REMOVING HIM FROM THE JOB. PER FAC 61G15-27.
  
 2 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-09-05 Cont ID  
Sent By tgordon Date 2008-09-05 Time 11:36 Rev Time 0.30
Received By tgordon Date 2008-09-05 Time 11:36 Sent To  
Notes
2008-09-05 11:37:52ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 ** SUBMIT PLANS WITH PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-09-02 Cont ID  
Sent By tgordon Date 2008-08-11 Time 15:51 Rev Time 1.30
Received By tgordon Date 2008-08-11 Time 15:51 Sent To  
Notes
2008-08-11 15:52:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN M-4 NEEDS TO BE SEALED BY THE
 ENGINEER, SEE FAC 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-07-01 Cont ID  
Sent By tgordon Date 2008-07-01 Time 16:33 Rev Time 0.45
Received By tgordon Date 2008-07-01 Time 16:33 Sent To  
Notes
2008-07-01 16:38:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS SUBMITTED ARE MISSING PAGES M-3, M-4, S-2, AND
 S-3. PLEASE SUBMIT TWO COPIES OF THE MISSING PAGES SO
 THAT A COMPLETE REVIEW CAN BE DONE, PER 2004 FBC
 106.1.1 AND 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-14 Cont ID  
Sent By tgordon Date 2008-05-14 Time 12:13 Rev Time 1.30
Received By tgordon Date 2008-05-14 Time 12:13 Sent To  
Notes
2008-05-14 12:27:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN M-1 GENERAL HVAC NOTE 4.1 AND M-2 EQUIPMENT
 STAND DETAIL NOTE 2, REFERENCES HURRICANE FORCE WINDS.
 NEEDS TO STATE 140 MPH HURRICANE FORCE WINDS, PER 2004
 FBC 1609.
  
 2) PLAN M-2 IF CONDENSER STANDS ARE PRE-ENGINEERED
 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 3) THE COOLING LOAD CALCULATIONS NEED TO BE SIGNED AND
 SEALED BY THE ENGINEER, PER 2004 FBC 13-407.1.ABC.1
 EXCEPT.
  
 4) WHEN RE-SUBMITTING THE ENERGY CALCULATIONS HAVE THEM
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC 13-103.3. (SEE
 ELECTRICAL REVIEW NOTE 4 REGARDING E-CAL'S, PLEASE
 CORRECT).
  
 5)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, PER 2004 FBC 13-407.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-11-13 Cont ID  
Sent By kstevens Date 2008-11-13 Time 09:53 Rev Time 0.00
Received By kstevens Date 2008-11-12 Time 17:02 Sent To  
Notes
2008-11-13 09:58:45REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1, SHT P-2 SANITARY RISER DIAGRAM SHOWS AN EXISTING 4"
 GREASE LINE FROM THE SECOND FLOOR. NO GREASE
 INTERCEPTOR OR SAMPLE POINT IS INDICATED. PLEASE
 CONTACT WILLIAM ROBERTS ENVIRONMENTAL COMPLIANCE TO
 DETERMINE THE REQUIREMENT FOR A GREASE
 INTERCEPTOR/SAMPLE POINT FOR NEW GREASE LINE NOT
 INDICATED PREVIOUSLY. ARTICLE III SECTION 90-124(7).
 MR. ROBERTS PHONE NUMBER IS (561) 822-2200 EXT 2272,
 FAX NUMBER IS (561) 659-7458 & E-MAIL IS
 [email protected].
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-08-27 Cont ID  
Sent By kstevens Date 2008-08-27 Time 16:20 Rev Time 0.00
Received By kstevens Date 2008-08-27 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-08-11 Cont ID  
Sent By kstevens Date 2008-08-11 Time 10:14 Rev Time 0.00
Received By kstevens Date 2008-08-11 Time 10:14 Sent To  
Notes
2008-08-11 10:16:50DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REV
 FBC-2004 BUILDING W/2007 REV
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR PERMIT:
  
 A. OK
 B. OK
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 MANUF. SHEETS FOUND.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 D. N/A
 E. N/A
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM
 OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE
 RISER DIAGRAM.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 15. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-07-21 Cont ID  
Sent By kstevens Date 2008-07-21 Time 13:50 Rev Time 0.00
Received By kstevens Date 2008-07-21 Time 13:50 Sent To  
Notes
2008-07-21 14:00:23DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REV
 FBC-2004 BUILDING W/2007 REV
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A1.0 LIST OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. SHTS S-1, E-6, A-1, A-2 & A-3 WERE
 SUBMITTED BUT NOT SHOWN ON THE DRAWING LIST. ALSO SHTS
 FP-1, FS-2, FS-3 & FS-4 WERE INDICATED ON THE LIST BUT
 NOT SUBMITTED. PLEASE CORRELATE THE DRAWING LIST WITH
 SHEETS SUBMITTED. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT SHEETS S-2, S-3, M-3 & M-4 ARE
 SHOWN ON THE DRAWING LIST BUT NOT SUBMITTED. PLEASE
 CORRELATE.
  
 3. OK
 4. OK
 5. OK
  
 6. SHT A5.0 FINISH SCHEDULE. SHOW COMPLIANCE WITH
 SECTION 1210.2 REQUIREMENT FOR WALLS WITHIN 2FT OF
 W/C'S & URINALS TO BE A SMOOTH, HARD & NONABSORBENT
 SURFACE. THE SCHEDULE IS INDICATING PAINT WHICH DOES
 NOT COMPLY WITH THE "HARD" PORTION OF THE
 REQUIREMENTS.
 ****RESPONSE NOTED, BUT SHTS A4.0 & A4.1 DO NOT
 INDICATE THE FINISH & SHT A5.0 STILL SHOWS AN, "EPOXY
 PAINTED SURFACE", WHICH DOES NOT COMPLY.
  
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR PERMIT:
  
 A. OK
 B. OK
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 MANUF. SHEETS FOUND.
  
 D. N/A
 E. N/A
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM
 OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE
 RISER DIAGRAM.
  
 15. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-12 Cont ID  
Sent By kstevens Date 2008-05-12 Time 10:52 Rev Time 0.00
Received By kstevens Date 2008-05-10 Time 17:08 Sent To  
Notes
2008-05-12 12:04:56DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REV
 FBC-2004 BUILDING W/2007 REV
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK. THE
 ADDRESS OF RECORD ON THE FLORIDA STATE DBPR WEBSITE
 DOES NOT REFLECT THE ADDRESS ON THE TITLE BLOCKS FOR
 THE ARCHITECT. PLEASE CORRELATE THE ADDRESS ON THE
 TITLE BLOCK SO THAT IT RELFECTS THE ADDRESS OF RECORD
 WITH THE STATE. EITHER UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS PRIOR TO RESUBMITTING PLANS FOR REVIEW.
 FAC 61G1-16.004(1) & FS 481.219, 481.2055.
  
 2. SHT A1.0 LIST OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. SHTS S-1, E-6, A-1, A-2 & A-3 WERE
 SUBMITTED BUT NOT SHOWN ON THE DRAWING LIST. ALSO SHTS
 FP-1, FS-2, FS-3 & FS-4 WERE INDICATED ON THE LIST BUT
 NOT SUBMITTED. PLEASE CORRELATE THE DRAWING LIST WITH
 SHEETS SUBMITTED. SECTION 106.1.3.
  
 3. SHTS A2.0 & A4.0 DETAIL #1 ACCESSIBLE STALL SHALL
 COMPLY WITH FIGURE 11-30(E). THE LAV CAN NOT BE IN THE
 CLEAR FLOOR SPACE OF THE W/C AND THE W/C SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO THE DOOR. SECTION
 11-4.17.3.
  
 4. SHTS A2.0 & A4.0 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 __FOR W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 __FOR LAV:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 5. SUBMIT A DETAIL FOR THE ACCESSIBLE URINAL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS &
 FIGURES.
  
 6. SHT A5.0 FINISH SCHEDULE. SHOW COMPLIANCE WITH
 SECTION 1210.2 REQUIREMENT FOR WALLS WITHIN 2FT OF
 W/C'S & URINALS TO BE A SMOOTH, HARD & NONABSORBENT
 SURFACE. THE SCHEDULE IS INDICATING PAINT WHICH DOES
 NOT COMPLY WITH THE "HARD" PORTION OF THE
 REQUIREMENTS.
  
 7. SHTS P-1 & P-2 PLEASE INDICATE ON THE RISER AND
 SUBMIT A DETAIL FOR THE SAMPLE POINT REQUIRED ON THE
 GREASE LINE. THE SAMPLE POINT SHALL BE A 4" CROSS WITH
 A MINIMUM 12" DROP BELOW THE DRAIN LINE WITH A HARD CAP
 AND A CLEANOUT UP TO FINISHED FLOOR ABOVE THE DRAIN
 LINE. SECTION 106.1.2.
  
 8. SHTS P-1 & P-2 TRAP PRIMERS ARE REQUIRED AT ALL
 FLOOR DRAINS WHERE THE TRAP IS SUBJECT TO LOSS BY
 EVAPORATION SUCH AS THE FLOOR DRAIN AT THE WATER
 HEATER. SECTION 1002.4. PLEASE SHOW ON THE RISER
 DIAGRAMS.
  
 9. SHT P-1 INDICATES 2 FFD'S BUT NO CONNECTION TO THE
 SANITARY BUILDING DRAIN OR BRANCH LINE. PLEASE CLARIFY.
 ALL INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR A
 HUB DRAIN AS A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2.
  
 10. SHT P-1 NO WATER SUPPLY IS SHOWN TO ITEMS 39, 40,
 41, 42 & 56. THIS DOES NOT REFLECT SHT P-2 RISER
 DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1, 601.1 &
 604.3.
  
 11. SHT P-2 WATER RISER DIAGRAM DOES NOT RELFLECT THE
 FLOOR PLAN. NO WATER IS SHOWN TO THE WALL HYDRANTS.
 PLEASE SHOW PIPING, PIPE SIZE, VALVES ETC.--ALSO
 THERE IS NO WATER SHOWN TO THE ICE MAKER. SECTIONS
 106.1.1, 601.1 & 604.3.
  
 12. SHT P-2 SANITARY RISER DIAGRAM. SAFE WASTES ARE NOT
 APPROVED. THE FFDS CONNECTING TO THE FLOOR SINK SHALL
 BE DELETED AND FLOOR SINKS SHALL BE INSTALLED OR THE
 INDIRECT PIPING SHALL BE INSTALLED TO THE FLOOR SINKS
 SHOWN. (SEE ITEMS 38, 39, 40, 60, 61 & 62).--ALSO
 FIXTURES SHALL NOT BE DOUBLE TRAPPED PER SECTION
 1002.1.
  
 13. SHT P-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN UPSTREAM OF ITEMS 49 & 50 AS WELL AS
 DOWNSTREAM OF ITEM 45. PLEASE CORRELATE.--IDENTIFY
 THE FIXTURE UPSTREAM OF FFD FOR ITEM 54. ITEM 54 IS
 REQUIRED TO DRAIN INTO A FLOOR SINK OR A HUB DRAIN PER
 SECTIONS 803.2 & 803.2.3.
  
 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL).
  
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 D. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 E. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 15. SHT P-4 PLUMBING FIXTURE SCHEDULE INDICATES A
 CONCRETE LAV, BUT UNDER MANUFACTURE IT STATES "REFER TO
 ARCHITECTURAL DRAWINGS". SHT A4.0 DETAIL 1 REFERS TO
 NOTE "J" WHICH REFERS TO I.D. DRAWINGS WHICH WERE NOT
 SUBMITTED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE LAV. PLEASE INDICATED MANUF & MODEL NUMBER.
 SECTION 303..4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-08-12 Cont ID  
Sent By mflis Date 2008-08-12 Time 15:29 Rev Time 0.00
Received By mflis Date 2008-08-12 Time 15:29 Sent To  
Notes
2008-08-12 15:30:09ZONING REVIEW: PASSED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2008-07-02 Cont ID  
Sent By mflis Date 2008-07-02 Time 08:42 Rev Time 0.00
Received By mflis Date 2008-07-02 Time 08:35 Sent To  
Notes
2008-07-02 08:42:34ZONING REVIEW: PASSED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2008-05-06 Cont ID  
Sent By mflis Date 2008-05-06 Time 11:09 Rev Time 0.00
Received By mflis Date 2008-05-06 Time 11:09 Sent To  
Notes
2008-05-06 11:12:17ZONING REVIEW: PASSED WITH PROVISO:
  
 1) ELEVATIONS DO NO SEEM TO INDICATE ANY AWNING OR
 CANOPIES AT CLEMATIS STREET. CONFIRM THIS IS CORRECT.
 WILL EXISTING AWNINGS REMAIN?
 2) CONFIRM IF SHUTTERS WILL BE NECESSARY FOR NEW
 GLAZING. IF SO, THEY SHOULD BE INDICATED ON THE
 ELEVATIONS AND IN PLAN.
  
 OTHER NOTES:
  
 1) RESTAURANT WILL REQUIRE 4COP-SRX OR 2COP ALCOHOL
 LICENSE, WITH APPROVAL FROM PLANNING & ZONING DEPT AT
 TIME OF BUSINESS LICENSE APPLICATION.
 2) OUTDOOR SEATING IS SUBJECT TO APPROVAL BY SIDEWALK
 CAFE PERMIT. PLEASE OBTAIN APPLICATION FROM P & Z DEPT.
 (MAY BE SUBMTTED AT TIME OF BUSINESS LICENSE APP).
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved