| Plan Review Stops For Permit 08040824 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-11-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-03 |
Time |
09:55 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-11-03 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-10-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-08 |
Time |
09:44 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-10-08 |
Time |
09:44 |
Sent To |
PC |
|
| Notes |
| 2008-10-08 09:51:18 | BUILDING PLAN REVIEW | | | PERMIT: 08040824 | | | ADD: 223 CLEMATIS ST | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)756-2553 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION REVIEW | | | ACTION: DENIED | | | 1) SUBMITEED 2 SETS OF PLANS WILL REQUIRE THREE SETS OF | | | PLANS SINCE THIS IS A THRESHOLD BUILDING. | | | FL S S 553.71(7)/ 109.3.6 OPERATING GUIDELINES FOR | | | THRESHOLD INSPECTORS. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-29 |
Time |
13:41 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-08-29 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2008-08-29 13:54:14 | BUILDING PLAN REVIEW | | | PERMIT: 08040824 | | | ADD: 223 CLEMATIS ST | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)756-2553 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | 9-29-08 | | | REVIEW | | | ACTION:REVIEWED | | | | | | BUILDING PROVISO: | | | A COPY OF THE THRESHOLD INSPECTION PLAN SUBMITTED, | | | RAISED SEAL TO BE OVERNIGHTED AND SUBMITTED TUESDAY | | | 9-02-08. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-08-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-21 |
Time |
07:11 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-08-21 |
Time |
07:11 |
Sent To |
PC |
|
| Notes |
| 2008-08-29 13:40:39 | 8-29-08 THRESHOLD INSPECTION PLAN SUBMITTED (COPIED) | | | ORIGINAL TO BE SUBMITED TUESDAY 9-02-08 | | 2008-08-21 07:22:13 | BUILDING PLAN REVIEW | | | PERMIT: 08040824 | | | ADD: 223 CLEMATIS ST | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)756-2553 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) ) INFORMATIONAL FL S S 713.13NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 2-3) COMPLIED. | | | | | | 4) SHEET A5.0 | | | | | | 4A)BUILDING PROVISO: IN RESTROOMS WET WALLS TILE | | | WAINSCOAT A MINIMUM OF 4'-0". WET WALL AREAS. PLEASE | | | SEE 1210.2 NON-ABSORBANT SURFACES. | | | | | | 4B-4C) COMPLIED. | | | | | | 5-10) COMPLIED. | | | | | | 11) NOTE, AGAIN THIS IS A FOUR STORY BUILDING, REQUIRES | | | A THRESHOLD INSPECTOR, A THRESHOLD INSPECTION REPORT: | | | 11A)THRESHOLD INSPECTION PLANFL S. S. 553.71(7) " | | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 11B) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | 11C) THRESHOLD INSPECTOR: | | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | | CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | THRESHOLD BLDG,REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE | | | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY | | | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. ED ADDITIONAL COMMENTS MAY APPEAR THAT | | | WERE NOT PART OF THIS REVIEW. | | | | | | 12) COMPLIED, SCOPE OF WORK REMOVED FROM PROJECT. | | | | | | 13) NEW COMMENT, PRODUCT APPROVALS FOR FRONT DOORS | | | SWING & SLIDDING WERE NOT SUBMITTED THIS REVIEW. | | | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE | | | 3COPIES OF PRODUCT APPROVALS FOR THRESHOLDINSPECTOR | | | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS | | | FOLLOWS: | | | 13A) PAIR OF FRONT ENTRY DOORS | | | 13B) PAIR OF FRONT ENTRY SLIDDING GLASS DOORS | | | | | | 14)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 15)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-07-09 |
Time |
15:52 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-07-09 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2008-07-09 15:52:50 | BUILDING PLAN REVIEW | | | PERMIT: 08040824 | | | ADD: 223 CLEMATIS ST | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)756-2553 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) ) INFORMATIONAL FL S S 713.13NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 2-3) COMPLIED. | | | | | | 4) SHEET A5.0 | | | | | | 4A) WOMENS RESTROOM 105 ANF MENS RESTROOM 107 BOTH | | | INDICATE THE USE OFPAINTED WALLS ON THE WET WALL | | | AREAS. PLEASE SEE 1210.2 NON-ABSORBANT SURFACES. | | | | | | 4B-4C) COMPLIED. | | | | | | 5-10) COMPLIED. | | | | | | 11) NOTE, AGAIN THIS IS A FOUR STORY BUILDING, REQUIRES | | | A THRESHOLD INSPECTOR, A THRESHOLD INSPECTION REPORT: | | | 11A)THRESHOLD INSPECTION PLANFL S. S. 553.71(7) " | | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 11B) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | 11C) THRESHOLD INSPECTOR: | | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | | CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | THRESHOLD BLDG,REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE | | | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY | | | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. ED ADDITIONAL COMMENTS MAY APPEAR THAT | | | WERE NOT PART OF THIS REVIEW. | | | | | | 12) NEW COMMENT: INDEX SHEET INDICATES A S-2 & S-3 AS | | | WELL ASM-3 & M-4 ALL MISSING. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-02 |
Time |
08:25 |
Rev Time |
4.40 |
| Received By |
jwitmer |
Date |
2008-06-02 |
Time |
08:25 |
Sent To |
PC |
|
| Notes |
| 2008-06-02 08:26:27 | BUILDING PLAN REVIEW | | | PERMIT: 08040824 | | | ADD: 223 CLEMATIS ST | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)756-2553 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1 REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 2-3) COMPLIED. | | | | | | 4) SHEET A5.0 | | | | | | 4A) WOMENS RESTROOM 105 ANF MENS RESTROOM 107 BOTH | | | INDICATE THE USE OF PAINTED WALLS ON THE WET WALL | | | AREAS. PLEASE SEE 1210.2 NON-ABSORBANT SURFACES. | | | | | | 4B-4C) COMPLIED. | | | | | | 5-10) COMPLIED. | | | | | | 11) NOTE, AGAIN THIS IS A FOUR STORY BUILDING, REQUIRES | | | A THRESHOLD INSPECTOR, A THRESHOLD INSPECTION REPORT: | | | 11A)THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " | | | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH | | | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN | | | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | 11B) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A | | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | 11C) THRESHOLD INSPECTOR: | | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA | | | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS | | | CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | THRESHOLD BLDG, REQUIRED STATEMENT: | | | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE | | | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. ED ADDITIONAL COMMENTS MAY APPEAR THAT | | | WERE NOT PART OF THIS REVIEW. | | | | | | 12) NEW COMMENT: INDEX SHEET INDICATES A S-2 & S-3 AS | | | WELL AS M-3 & M-4 ALL MISSING. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2008-09-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-04 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-04 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2008-09-04 09:42:47 | NEW SHEETS BROUGTH IN BY MARK FROM ARCHITECT'S OFFICE. | | | E-1,4 AND E5. ALSO NEW CALCULATIONS. | | | OK. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-02 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-02 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2008-09-02 16:17:52 | ** DENIED/TEMPORARY FAILED ** | | | | | | 1) NOTE: LIGHTING PERFORMACE CALCULATIONS LOCATED IN | | | THE PLUMBING SUBMITTALS FOR KITCHEN EQUIPMENT. | | | CALCULATIONS WERE REVIEWED. MINOR CORRECTION NEEDED. | | | SPOKE TO ENGINEER AND WILL SEND NEW SHEETS ALONG WITH | | | SHEETS E-1, E-4 AND E-5 BEING REVISED. | | | ALSO PER MECHANICAL COMMENTS NEED NEW SHEET M-4. SPOKE | | | TO DAVIS PUGA AS SHEETS IN BOTH SETS ARE NOT SIGNED, | | | DATED OR SEALED. THEY CONTAIN A DIGITAL SEAL AND COLOR | | | DIGITAL SIGNATURE. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-02 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-02 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2008-09-02 10:36:41 | | | | | | | | | | | | | | | | ** DENIED 4TH REVIEW ** | | | | | | | | | **** PLEASE SEE COMMENTS BELOW WHICH ARE THE SAME AS | | | PREVIOUS REVIEWS. | | | | | | | | | 1) NOTE: PLANS STILL DO NOT STATE ANY MAXIMUM OVER RIDE | | | TIMES OR MAXIMUM OCCUPANCY SENSOR TIMES. THE NEW *KP* | | | KEY PAD AS NOTED ON SHEET E-4 AND ON SYMBOL LEGEND DOES | | | NOT CONTAIN ANY TIMES. THE OCCUPANCY SENSORS AS NOTED | | | ON SYMBOL LEGEND DOES NOT CONTAIN ANY TIMES. | | | PLEASE STATE THE REQUIRED *MAXIMUM* OVER RIDE TIMES PER | | | THE SAME SECTIONS. | | | PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3. | | | (( IF TIMED OVER RIDE, MUST BE A MAXIMUM OF FOUR HOURS | | | OR LESS) (IF AN OCCUPANCY SENSOR IS USED FOR OVER RIDE, | | | TIME IS A MAXIMUM OF 30MINUTES OR LESS) | | | | | | 2) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2, 13-415.2.B, | | | 13-415.2, 13-415.2, 13-415.2.ABC.1, 13-415.2.C ETC. THE | | | ENTIRE SECTION OF 13-415.2 APPLIES. | | | PLEASE KNOW ON PREVIOUS CORRESPONDENCE THE LIGHTING | | | PERFORMANCE CALCULATIONS GOING TO BE PLACED ON PLANS | | | HOWEVER SHEETS E-1-E-6 AND ELP-1 DO NOT CONTAIN ANY | | | LIGHTING CALCULATIONS TO REVIEW AND COMPARE TO THE | | | LIGHTING AS SHOWN ON PLANS. | | | PLEASE BE SURE TO SEE THE TRACK LIGHTING SECTIONS OF | | | THE CODE. | | | PLEASE SEE SPACE BY SPACE METHOD FOR DINING ALLOWANCES, | | | OTHER SPACES, DECORATIVE ETC. | | | CALLED AND SPOKE TO ELECTRICAL ENGINEER AND MECHANICAL | | | ENGINEER. CALCULATIONS ARE REQUIRED TO MEET | | | PRESCRIPTIVE REQUIREMENTS. | | | BASED ON THE PLANS SUBMITTED THE LIGHTING AS SHOWN DOES | | | NOT PROVIDE THE MINIMUM INFORMATION WHICH IS REQUIRED. | | | PLEASE BE SURE TO SEE 13-415.2.ABC.1.1, AND .1.2 AS | | | NOTED ABOVE FOR TRACK LIGHTING AND THE VA RATINGS FOR | | | FIXTURES AND VA RATINGS FOR TRACK TO BE USED. | | | *** PLEASE KEEP IN MIND LINE VOLTAGE TRACK VA WATTAGE | | | IS BASED ON VA PER FIXTURE TIMES THE NUMBER OF FIXTURES | | | ON PLANS OR 30VA PER FOOT OF TRACK,,,,,, (WHICH EVER IS | | | GREATER). | | | *** PLEASE SEE LOW VOLTAGE TRACK VA IS BASED ON THE | | | REMOTE TYPE TRANSFORMER RATING. | | | ** PLEASE BE SURE TO COMPLETE THE FIXTURE SCHEDULE WITH | | | THE TRACK LIGHTING AS NOTED ON SYMBOL LEGEND. | | | | | | 3) NOTE: PLEASE KNOW AS REQUIRED BY FLORIDA STATUTES | | | 553.80(2)(B) A FEE IS NOW ASSESSED BASED ON REPEAT | | | COMMENTS FOR CODE COMPLIANCE. THIS IS A *STATUTORY* | | | REQUIRED FEE AND IS NOT A LOCAL ENFORCEMENT RULING. THE | | | FEE AMOUNT IS BASED ON 4X THE PLAN REVIEW PORTION OF | | | THE BASE PERMIT FEE. IN THIS CASE THE BASE PERMIT FEE | | | IS $7,300.00. THE PLAN REVIEW PORTION OF THIS FEE IS 30 | | | PERCENT WHICH IS $2,190.00. THAT IS THE FEE TIMES FOUR. | | | THIS COMES TO $9,300.00 WHICH IS REQUIRED TO BE PAID. | | | ONCE AGAIN THIS IS A *STATE* REQUIRED FEE AND IS NOT A | | | LOCAL REQUIREMENT. THE SECTION OF THE FLORIDA STATUTES | | | IS ATTACHED TO THE PLAN REVIEW NOTES. | | | ** ONE SET OF ELECTRICAL PLANS ARE RETAINED ONCE AGAIN | | | FOR FILE. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-08-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-12 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-12 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2008-08-12 16:53:58 | | | | ** DENIED PLANS. ** | | | | | | | | | 1) NOTE: NEW *KP* KEY PAD AS NOTED FOR | | | 13-415.1.ABC.1.1, .1.2. PLEASE STATE THE REQUIRED | | | *MAXIMUM* OVER RIDE TIMES PER THE SAME SECTIONS. | | | (( IF TIMED OVER RIDE, MUST BE A MAXIMUM OF FOUR HOURS) | | | (IF AN OCCUPANCY SENSOR IS USED FOR OVER RIDE, TIME IS | | | A MAXIMUM OF 30MINUTES) | | | | | | 2) NOTE: PLEASE SEE 13-415.2.ABC.2.1, .1.2, 13-415.2.B, | | | 13-415.2, 13-415.2, 13-415.2.ABC.1. PLEASE SEE SECTIONS | | | AS NOTED MAY NOT USE THE EXCEPTION IN THE CODE FOR THIS | | | OCCUPANCY. PLEASE SEE SPACE BY SPACE METHOD FOR DINING | | | ALLOWANCES, OTHER SPACES, DECORATIVE ETC. | | | CALLED AND SPOKE TO ELECTRICAL ENGINEER AND MECHANICAL | | | ENGINEER. THEY WILL BE REFIGURING CALCULATIONS TO MEET | | | PRESCRIPTIVE REQUIREMENTS. | | | BASED ON THE CALCULATIONS SUBMITTED THE DESIGN WATTAGE | | | EXCEEDS THE ALLOWANCES BASED ON THIS OCCUPANCY. | | | PLEASE BE SURE TO SEE 13-415.2.ABC.1.1, AND .1.2 AS | | | NOTED ABOVE FOR TRACK LIGHTING AND THE VA RATINGS FOR | | | FIXTURES AND VA RATINGS FOR TRACK TO BE USED. | | | *** PLEASE KEEP IN MIND LINE VOLTAGE TRACK VA WATTAGE | | | IS BASED ON VA PER FIXTURE TIMES THE NUMBER OF FIXTURES | | | ON PLANS OR 30VA PER FOOT OF TRACK,,,,,, (WHICH EVER IS | | | GREATER). | | | *** PLEASE SEE LOW VOLTAGE TRACK VA IS BASED ON THE | | | REMOTE TYPE TRANSFORMER RATING. | | | ** PLEASE BE SURE TO COMPLETE THE FIXTURE SCHEDULE WITH | | | THE TRACK LIGHTING AS NOTED ON SYMBOL LEGEND. | | | | | | ENGINEER WILL SEND PDF TO MAKE SURE CALCULATIONS ARE | | | SET UP FOR SPACE BY SPACE AREAS. THE E-MAILING OF THE | | | PDF WILL NOT CONSTITUTE AS A TECHNICAL REVIEW OF CODE | | | LIGHTING CALCULATIONS FOR THE ENERGY CODE. THIS WILL BE | | | TO HELP WITH A SET UP OF PERFORMANCE CALCULATIONS. | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-07-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-25 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-25 |
Time |
16:42 |
Sent To |
PC |
|
| Notes |
| 2008-07-25 16:42:30 | | | | ** DENIED2ND REVIEW ** | | | | | | *** PLEASE KNOW IT IS IMPORTANT TO KNOW THERE ARE | | | SEVERAL ITEMS WHICH ARE FROM PREVIOUS REVIEW WHICH ARE | | | STILL IN NEED OF ADDRESSING. | | | PLEASE ALSO SEE NOTES BELOW AS THERE ARE ALSO NEW | | | COMMENTS AS THERE HAVE BEEN REVISIONS MADE TO PLANS | | | WHICH WERE NOT PART OF THE PREVIOUS REVIEWED PLANS. | | | | | | ** THERE IS INFORMATION STILL NOT YET SUBMITTED | | | THEREFORE A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT | | | POSSIBLY BE DONE. | | | | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3. THE ADA | | | LEVELS FOR STROBES WERE SHOWN HOWEVER WHERE IS THE | | | AUDIBLE LEVELS? | | | FBC 11-4.28.1, .2 AN D.3(4). | | | | | | 2) NOTE: PLEASE SEEPREVIOUS REVIEW NOTE #4. NOW A | | | SUBMITTED FLA COM METHOD *B* IS BEING SUBMITTED. THE | | | SECTIONS OF THE CODE WERE GIVEN ON PREVIOUS REVIEW FOR | | | DEFINITIONS OF THE SCOPE OF WORK. THIS TENANT | | | RENOVATION DOES NOT APPEAR TO QUALIFY AS A RENOVATION | | | TO THE BUILDING. THE LIGHTING PERFORMANCE PARTOF | | | TABLE *B* AND SECTIONS 13-415.2.ABC.1.1,.1.2 AND .1.3 | | | NEED TO BE MET. THIS IS NOT YET DONE. | | | PLEASE ALSO SEE THE METHOD OF CONTROLS IS STILL SHOWN | | | AS MANUAL ON OFF AND CONTINUOUS DIMMING. THIS IS NOT | | | POSSIBLE. | | | . | | | PLEASE SEE 13-101.1.1, 13-101.1.2,13-101.3, | | | 13-400.0.A,13-400.0.B, 13-400.0.C,ETC. | | | PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO | | | MINIMUM REQUIREMENTS REQUIRED. | | | THIS COMMENT IS GIVEN FOR INFORMATION FOR ALL OTHER | | | TRADES HOWEVER ELECTRICAL COMPLIANCE WITH SECTIONS | | | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 NEED TO BE | | | MET. | | | THE INPUT DATA REPORT IS REQUIRED TO COORDINATE WITH | | | PLANS. HOW IS THIS POSSIBLE WHEN THERE ARE SEVERAL | | | ITEMS IN THE IDR WHICH ARE BLANK OR SHOWING OTHER | | | INFORMATION THAN WHAT IS ON PLANS. IDR SHOWS ONLY ONE | | | WALL, HOW IS THIS POSSIBLE? IDR SHOWS NO DOORS FROM | | | CONDITIONED TO UNCONDITIONED SPACE, HOW IS THIS | | | POSSIBLE. THE IDR SHOWS NO FLOORS, HOW IS THIS | | | POSSIBLE?THERE IS HOT WATER SYSTEMS YET THE PIPING | | | INSULATION IS BLANK, HOW IS THIS POSSIBLE. THESE ARE A | | | FEW EXAMPLES. | | | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORTS IS | | | REQUIRED TO COORDINATE WITH PLANS COMPLETELY. | | | | | | 3) NOTE: PLEASE SEEPREVIOUS NOTES AND | | | SECTIONS13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. | | | PLANS DO NOT SHOW ENOUGH INFORMATION FOR ANY TIMED | | | SCHEDULING SYSTEM. PLANS STILL SHOW NUMEROUS LOCATIONS | | | WHERE STANDARD SINGLE POLE SWITCHES ARE STILL BEING | | | SHOWN. HOW DO THESE STANDARD DINGLE POLE DEVICES MEET | | | THE *MINIMUM* REQUIRED BY CODE WHEN THEY DO NOT MEET | | | THE SECTIONS NOTED? | | | SOME EXAMPLES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS | | | REVIEW NOTES. | | | | | | A) PLEASE VERIFY ALL OVER RIDE LOCATIONS REQUIRED. | | | PLEASE SEE THAT AN OCCUPANT MUST BE ABLE TO OVER RIDE | | | ANY TIME OF DAY SCHEDULING AT THE POINT OF ENTRANCE | | | INTO ANY ONE SPACE. THE OCCUPANT MUST BE ABLE TO SEE | | | ALL LIGHTING WHICH IS BEING CONTROLLED OR NEEDS TO MEET | | | EXCEPTIONS. | | | | | | B) PLEASE SEE SOME LIGHTING CONTROLS SHOWN ON PLANS ARE | | | STANDARD SWITCHES. HOW IS THIS POSSIBLE WHEN AUTOMATED | | | CONTROLS ARE REQUIRED? | | | SOME LOCATION EXAMPLES ARE HALL, ACCENT LIGHTS, LIQUOR | | | STORAGE, CLOSET ETC | | | ** THIS IS NOT ALL LOCATIONS AS THERE ARE OTHERS. ONLY | | | SOME ARE GIVEN AS EXAMPLES. | | | | | | C) PLEASE SEE PLANS ARE MISSING REQUIRED SEPARATE SPACE | | | CONTROLS. THESE ARE REQUIRED TO BE AUTOMATED OR PART OF | | | A SYSTEM WITH OVER RIDES. | | | | | | D) PLEASE PROVIDE A COMPLETE SYSTEM/ETC FOR MINIMUM | | | LIGHTING CONTROLS AS REQUIRED PER SECTIONS ABOVE. | | | PLEASE PROVIDE COMPLETE SCHEDULE OF SYSTEM, SCHEDULE | | | FOR ALL ITEMS ON THE DIMMING PANEL. | | | AS NO SCHEDULE WAS SUBMITTED THERE ARE SEVERAL ITEMS | | | WHICH CAN NOT BE DETERMINED FOR CODE COMPLIANCE WITH | | | REQUIRED LIGHTING CONTROLS AS WELL AS OTHER COMMENTS. | | | PLEASE SEE THE FOLLOWING COMMENT. | | | PLEASE KNOW COMPLETE COMPLIANCE FOR AUTOMATED LIGHTING | | | CONTROLS IS REQUIRED.THIS IS A BUILDING OVER 5000 SQ | | | FT. | | | | | | | | | 4) NOTE: PLEASE KNOW AS PLANS CLEARLY INDICATE NORMAL | | | LIGHTING BEING CONTROLLED THROUGH A DIMMING PANEL OF | | | SOME KIND PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR | | | EGRESS PATHS FOR MINIMUM LIGHTING LEVELS. | | | PLEASE KNOW THE MINIMUM LEVELS FOR LIGHTING SHALL NOT | | | BE PERMITTED TO DIM BELOW THE 1FT CANDLE REQUIRED BY | | | THE LIFE SAFETY CODE, NFPA-101 7.8, 7.9. 7.8.1.3 | | | PLEASE PROVIDE MORE INFORMATION. THIS WAS NOT | | | SUBMITTED. THE PLANS NOW INDICATE A NOTE WHICH STATES | | | LIGHTING LEVELS MUST MEET CODE HOWEVER IF THE DIMMING | | | SYSTEM IS NOT DESIGNED TO BE SPECIFIC THE LIGHTING | | | LEVELS MAY VERY WELL BE DIMMED TO A LIGHTING LEVEL OF | | | *0* WHEN OCCUPIED UNDER NORMAL CONDITIONS. PLEASE | | | DESIGN/SPECIFY THE DEVICE SET LEVELS ETC | | | FBC 106.1.2. | | | FAC 61G15-33.004 | | | | | | 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON | | | THE EXISTING 1000AMP MAIN IN WHICH THE PROPOSED | | | SERVICE. PLEASE SEE THE NEXT FEW NOTES AS THE RISER HAS | | | BEEN COMPLETELY REVISED AND THERE WILL BE COMMENTS | | | BELOW WHICH WILL AFFECT SERVICE LOADS CALCULATIONS.. | | | PLEASE OBTAIN ALL RECENT LOADS WHICH HAVE BEEN ADDED TO | | | BUILDING AND POSSIBLY THIS SERVICE. | | | PLEASE SEE 220.87. A LOAD STUDY MAY NOT BE ACCURATE AS | | | NEW LOADS HAVE CONTINUALLY BEEN ADDED AND SOME LOADS | | | HAVE NOT BEEN COMPLETED ON SERVICE. | | | PLEASE SEE CODES REFLECTED ON THE CALCULATIONS NEED TO | | | COORDINATE WITH CODE. PLEASE VERIFY 220.44 AS NOTED FOR | | | ALL OTHER LOADS. HOW ARE LIGHTING LOADS UNDER THIS SAME | | | CODE SECTION? | | | PLEASE SEE 220.42 AND 220.43. | | | | | | 6) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #9. TRACK | | | LIGHTING LOADS ARE STILL NOT SHOWN. | | | PLEASE SEE NOTE #5 ABOVE IN WHICH SECTION 220.43 WAS | | | BRIEFLY SATED FOR LOAD CALCULATIONS. PLEASE SHOW ALL | | | TRACK LIGHTING LOADS AND HOW THEY ARE DERIVED. AS THESE | | | ARE SPECIFIED AT THIS TIME COMPLIANCE CAN NOT BE | | | VERIFIED. THIS WILL AFFECT THE DIMMER PANELS. | | | | | | 7) NOTE: PLEASE SEE PREVIOUS NOTE #10. PLEASE SEE THESE | | | WERE NOT REVISED. TO MEET THE EXCEPTION IN THE CODE | | | ONLY A SPECIFIC BREAKER MAY BE USED. A SNAP ON TYPE | | | DEVICE IS NOT LISTED FOR PERMANENT INSTALLATION. PLEASE | | | SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS. THESE | | | SHALL BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN ANY | | | ONE AREA. | | | | | | 8) NOTE: PLEASE SEE NEW RISER AS TENANT IS NOW SHOWN | | | BEING FED FROM TWO COMPLETELY SEPARATE SERVICES WHICH | | | IS NOT PERMITTED. | | | THERE ARE NO SEPARATE VOLTAGES ETC WHICH WOULD REQUIRE | | | THE ELECTRICAL TO BE FED FROM SEPARATE SERVICES. THERE | | | ARE NO OTHER EXCEPTIONS SHOWN TO JUSTIFY. | | | PLEASE KNOW THE FIRE MARSHAL ALSO HAS CONCERN OVER | | | MULTIPLE MAIN DISCONNECTS FOR ONE TENANT. NO SIGNAGE, | | | NO NOTES, NO INFORMATION OF LABELING ETC IS SHOWN. AS | | | NOTED ABOVE NO LOAD CALCULATIONS ETC WERE SUBMITTED. AS | | | THIS IS NO COMPLETE AT THIS TIME THERE ARE MANY | | | UNANSWERED QUESTIONS. | | | 230, 240, 220 ET | | | | | | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE KNOW ONE | | | SET OF ELECTRICAL PLANS HAVE BEEN RETAINED BY THIS | | | OFFICE/REVIEWER. | | | | | | | | | IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-05-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-05 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-05 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2008-05-05 07:43:26 | ** DENIED** | | | | | | *** PLEASE KNOW IT IS IMPORTANT TO KNOW THERE ARE | | | SEVERAL ITEMS NOT YET SUBMITTED FOR CODE COMPLIANCE IN | | | DESIGN. IT IS IMPORTANT TO UNDERSTAND THERE MAY VERY | | | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN | | | NOT BE MADE AT THIS TIME. | | | | | | | | | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES AT A | | | MINIMUM FOR THE REVIEWER ARE STATED ON ELECTRICAL PLANS | | | AS WELL AS COVER SHEET. | | | | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | ** SOME CODES ARE ALREADY STATED HOWEVER NOT ALL | | | RELEVANT AS STATED ABOVE. THIS IS ONLY FOR ELECTRICAL | | | REVIEW AND OTHER CODES FROM OTHER TRADES MAY CERTAINLY | | | BE REQUIRED. | | | | | | 2) NOTE: PLEASE SEE FIRE REVIEW AND BUILDING REVIEW | | | COMMENTS AS THIS BUILDING IS CONSIDERED MORE THAN THREE | | | STORIES. | | | SHEET A1.0 CLEARLY STATES THIS IS A *2-STORY* BUILDING | | | HOWEVER THIS IS NOT THE CASE. THE BUILDING BY | | | DEFINITION IS AT MINIMUM 4-STORY. PLEASE SEE COMMENTS | | | FROM BUILDING REVIEW. | | | FOR INFORMATION: THE ORIGINAL FIRE WALLS WHICH USED TO | | | SEPARATE PARTS OF THIS STRUCTURE ARE NO LONGER FIRE | | | WALLS BY DEFINITION. | | | | | | 3) NOTE: PLEASE SEE SOME LOCATIONS ARE MISSING | | | HORN/STROBE FOR ADA COMPLIANCE PER FBC 11-4.28.1, .2 AN | | | D.3(4). | | | PLEASE SEE ONE LOCATION FOR EXAMPLE IS THE BATHROOMS. | | | NOTE #9 ON PLANS MENTIONS TO INSTALL NEW DEVICES TO | | | MATCH EXISTING. IT IS NOT POSSIBLE TO MATCH EXISTING | | | WHEN THERE ARE NOT EXISTING DEVICES. THIS SPACE HAS | | | BEEN COMPLETELY GUTTED. | | | PLEASE SHOW DEVICES FOR COMPLIANCE. | | | | | | 4) NOTE: PLEASE SEE THE SUBMITTED METHOD *A* ENERGY | | | CALCULATIONS MAY NOT BE USED. THIS IS FOR A TENANT | | | BUILD OUT ONLY, THIS IS NOT FOR A WHOLE BUILDING. | | | PLEASE SEE THE DEFINITIONS. METHOD *A* MAY BE USED ON | | | ADDITIONS AND WHOLE BUILDINGS OR WHEN *ALL BUILDING | | | COMPONENTS* ARE KNOWN. THIS SCENARIO AS SUBMITTED WOULD | | | NOT FALL UNDER THIS CRITERIA. | | | PLEASE SEE 13-101.1.1, 13-101.1.2,13-101.3, | | | 13-400.0.A,13-400.0.B, 13-400.0.C,ETC. | | | PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO | | | MINIMUM REQUIREMENTS REQUIRED. | | | THIS COMMENT IS GIVEN FOR INFORMATION FOR ALL OTHER | | | TRADES HOWEVER ELECTRICAL COMPLIANCE WITH SECTIONS | | | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 NEED TO BE | | | MET. | | | AS THE CALCULATIONS SUBMITTED ARE NOT VALID PLEASE | | | SUBMIT COMPLETE LIGHTING PERFORMANCE CALCULATIONS UNDER | | | METHOD PERMITTED. | | | PLEASE CALL TO GO OVER THIS. | | | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORTS IS | | | REQUIRED TO COORDINATE WITH PLANS COMPLETELY. | | | | | | A) PLEASE SEE ONE EXAMPLE IS THAT THE METHOD OF | | | CONTROLS FOR LIGHTING IS SHOWN AS *MANUAL ON/OFF*. HOW | | | IS THIS POSSIBLE WHEN ALL LIGHTING IS REQUIRED TO | | | CONTAIN AUTOMATED CONTROLS? | | | PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO | | | LIGHTING CONTROLS. | | | | | | B) PLEASE SEE ANOTHER EXAMPLE OF ITEMS ON THE IDR WHICH | | | DO NOT COORDINATE WITH PLANS IS THE NUMBER OF LIGHT | | | FIXTURES SHOWN. PLEASE SEE THE TOTAL NUMBER OF FIXTURES | | | SHOWN ON THE IDR FOR INTERIOR IS *8*. THIS IS NOT | | | POSSIBLE WHEN THERE IS CLEARLY DOZENS OF FIXTURES ON | | | PLANS. | | | | | | C) PLEASE SEE ANOTHER EXAMPLE OF ITEMS ON PLANS WHICH | | | DO NOT COORDINATE WITH THE IDR IS THE EXTERIOR | | | FIXTURES. PLEASE SEE THIS IS ACTUALLY BLANK ON THE IDR | | | YET THERE ARE CLEARLY EXTERIOR LIGHT FIXTURES ON PLANS. | | | PLEASE SEE 13-415.2.ABC.1.3 AS NOTED ABOVE FOR EXTERIOR | | | LIGHTING PERFORMANCE. | | | | | | D) PLEASE BE SURE TO SEE THE SECTIONS OF CODE AS NOTED | | | ABOVE SPECIFICALLY FOR TRACK LIGHTING. | | | BASED ON THE PLANS THE FIXTURE LEGEND IS NOT COMPLETE. | | | ALL FIXTURES MUST BE LABELED. ALL FIXTURES MUST BE | | | FIGURED INTO THE PERFORMANCE CALCULATIONS OF SPACE. | | | | | | ** IMPORTANT** | | | THESE EXAMPLES ABOVE ARE NOT IN ANYWAY AN EXHAUSTED | | | LIST OF ALL ITEMS ON PLANS WHICH DO NOT COORDINATE WITH | | | THE SUBMITTED CALCULATIONS. THESE ARE GIVEN AS A | | | BENEFIT ONLY AS CODE COMPLIANCE HAS NOT BEEN ACHIEVED. | | | PLEASE BE SURE TO GO OVER COMMENTS AND COORDINATE ALL. | | | | | | | | | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND | | | .1.4. | | | | | | A) PLEASE VERIFY ALL OVER RIDE LOCATIONS REQUIRED. | | | PLEASE SEE THAT AN OCCUPANT MUST BE ABLE TO OVER RIDE | | | ANY TIME OF DAY SCHEDULING AT THE POINT OF ENTRANCE | | | INTO ANY ONE SPACE. THE OCCUPANT MUST BE ABLE TO SEE | | | ALL LIGHTING WHICH IS BEING CONTROLLED OR NEEDS TO MEET | | | EXCEPTIONS. | | | | | | B) PLEASE SEE SOME LIGHTING CONTROLS SHOWN ON PLANS ARE | | | STANDARD SWITCHES. HOW IS THIS POSSIBLE WHEN AUTOMATED | | | CONTROLS ARE REQUIRED? | | | SOME LOCATION EXAMPLES ARE HALL, ACCENT LIGHTS, LIQUOR | | | STORAGE, CLOSET ETC | | | ** THIS IS NOT ALL LOCATIONS AS THERE ARE OTHERS. ONLY | | | SOME ARE GIVEN AS EXAMPLES. | | | | | | C) PLEASE SEE PLANS ARE MISSING REQUIRED SEPARATE SPACE | | | CONTROLS. THESE ARE REQUIRED TO BE AUTOMATED OR PART OF | | | A SYSTEM WITH OVER RIDES. | | | | | | D) PLEASE PROVIDE A COMPLETE SYSTEM/ETC FOR MINIMUM | | | LIGHTING CONTROLS AS REQUIRED PER SECTIONS ABOVE. | | | PLEASE PROVIDE COMPLETE SCHEDULE OF SYSTEM, SCHEDULE | | | FOR ALL ITEMS ON THE DIMMING PANEL. | | | AS NO SCHEDULE WAS SUBMITTED THERE ARE SEVERAL ITEMS | | | WHICH CAN NOT BE DETERMINED FOR CODE COMPLIANCE WITH | | | REQUIRED LIGHTING CONTROLS AS WELL AS OTHER COMMENTS. | | | PLEASE SEE THE FOLLOWING COMMENT. | | | PLEASE KNOW COMPLETE COMPLIANCE FOR AUTOMATED LIGHTING | | | CONTROLS IS REQUIRED.THIS IS A BUILDING OVER 5000 SQ | | | FT. | | | | | | E) PLEASE SEE SECTION 13-415.1.ABC.1.4 FOR EXTERIOR | | | LIGHTING CONTROLS. PLANS SHOW THESE EXTERIOR LIGHTS | | | THROUGH DIMMING PANEL. PLEASE SEE THE SECTION OF CODE | | | WHICH PERMITS TWO METHODS. | | | | | | | | | ** IT IS IMPORTANT TO KNOW AS NO LIGHTING CONTROL | | | SYSTEM, OR DEVICES WERE SUBMITTED AS PART OF THE DESIGN | | | THESE SPECIFIC ITEMS COULD NOT BE REVIEWED. CODE | | | COMPLIANCE WAS REQUIRED TO BE ON DESIGN FOR INITIAL | | | REVIEW. THERE MAY BE NEW COMMENTS ON THE FOLLOWING | | | REVIEW WHICH COULD NOT BE MADE AT THIS TIME. | | | | | | 6) NOTE: PLEASE KNOW AS PLANS CLEARLY INDICATE NORMAL | | | LIGHTING BEING CONTROLLED THROUGH A DIMMING PANEL OF | | | SOME KIND PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR | | | EGRESS PATHS FOR MINIMUM LIGHTING LEVELS. | | | PLEASE KNOW THE MINIMUM LEVELS FOR LIGHTING SHALL NOT | | | BE PERMITTED TO DIM BELOW THE 1FT CANDLE REQUIRED BY | | | THE LIFE SAFETY CODE, NFPA-101 7.8, 7.9. | | | PLEASE PROVIDE MORE INFORMATION. | | | FBC 106.1.2. | | | FAC 61G15-33.004 | | | | | | 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON | | | THE EXISTING 1000AMP MAIN IN WHICH THE NEW 600AMP MAIN | | | IS BEING ADDED. | | | PLEASE OBTAIN ALL RECENT LOADS WHICH HAVE BEEN ADDED TO | | | BUILDING AND POSSIBLY THIS SERVICE. | | | PLEASE SEE 220.87. A LOAD STUDY MAY NOT BE ACCURATE AS | | | NEW LOADS HAVE CONTINUALLY BEEN ADDED AND SOME LOADS | | | HAVE NOT BEEN COMPLETED ON SERVICE. | | | PLEASE SEE CODES REFLECTED ON THE CALCULATIONS NEED TO | | | COORDINATE WITH CODE. PLEASE VERIFY 220.44 AS NOTED FOR | | | ALL OTHER LOADS. HOW ARE LIGHTING LOADS UNDER THIS SAME | | | CODE SECTION? | | | PLEASE SEE 220.42 AND 220.43. | | | | | | 8) NOTE: PLEASE VERIFY HOW THE LOADS ON THE LIGHTING | | | DIMMING PANELS ARE SHOWN EXCEEDING THE RATING OF THE | | | FEEDER. | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3, 230.42 | | | ETC PLEASE KNOW THIS WILL AFFECT OTHER LOADS ON PANELS, | | | SERVICE ETC. PLEASE BE SURE TO FOLLOW THROUGH WITH | | | SERVICE. | | | | | | 9) NOTE: PLEASE SEE NOTE #7 ABOVE IN WHICH SECTION | | | 220.43 WAS BRIEFLY SATED FOR LOAD CALCULATIONS. PLEASE | | | SHOW ALL TRACK LIGHTING LOADS AND HOW THEY ARE DERIVED. | | | AS THESE ARE SPECIFIED AT THIS TIME COMPLIANCE CAN NOT | | | BE VERIFIED. THIS WILL AFFECT THE DIMMER PANELS. | | | | | | 10) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF | | | EMERGENCY LIGHTS. THESE SHALL BE CIRCUITED TO THE LOCAL | | | BRANCH CIRCUIT IN ANY ONE AREA. | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
N |
Date |
2008-11-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-11-21 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-11-21 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2008-11-21 13:46:32 | SEE PERMIT #08090229 FOR PLAN REVIEW OF | | | HOOD/SUPPRESSION REVISION DATED 11/20/08. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-09-05 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-09-05 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2008-09-05 12:41:45 | STAMPED SHEETS A-1.0, E-6, AND FS-1. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-08-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-08-20 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-20 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2008-08-20 12:43:38 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEWS HAVE NOT BEEN ADDRESSED: | | | | | | | | | 11.NFPA 72 - 2002 EDITION SHALL BE REFERENCED. PLEASE | | | BE ADVISED THAT THE 1999 EDITION IS LISTED IN B UNDER | | | THE FIRE ALARM SYSTEM SCOPE ON SHEET E-6.CHANGE TO | | | 2002 EDITION, NOT 1999. | | | | | | 13.IN REFERENCE TO THE FIRE SPRINKLER SYSTEM, NFPA 13 | | | - 2002 EDITION SHALL BE REFERENCED.ADD CODE REFERENCE | | | TO SHEET FS-1 | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-07-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-23 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-23 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2008-07-23 10:34:21 | ***DENIED*** | | | | | | SOME OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED. | | | PLEASE SEE THE FOLLOWING FOR CORRECTION: | | | | | | 01. IN ADDITION TO DEMOLITION, THIS REQUIREMENT APPLIES | | | TO CONSTRUCTION AND ALTERATION. (NFPA 241) | | | | | | 02. OK | | | | | | 03. OK | | | | | | 04. PLANS STILL DO NOT CLEARLY ILLUSTRATE COMPLIANCE | | | WITH REQUIREMENT REGARDING PANIC AND FIRE EXIT | | | HARDWARE. SEE THE DOOR SCHEDULE UNDER PANIC COLUMN. | | | PLEASE ADD SPECIFIC INFORMATION TO DOOR SHEDULE. | | | | | | 05. OK | | | | | | 06. OK | | | | | | 07. OK | | | | | | 08. OK | | | | | | 09. OK | | | | | | 10. OK | | | | | | 11. THE FIRE ALARM SCOPE STILL REFERENCES THE 1999 | | | EDITION. FIRE ALARM SHALL COMPLY WITH NFPA 72, 2002 | | | EDITION. PLEASE REMOVE EARLIER CODE CYCLE REFERENCE. | | | | | | 12. OK | | | | | | 13. NOT ADDRESSED. PLEASE ADD NOTE NFPA 13, 2002 | | | EDITION TO GOVERNING CODE OR FIRE SPRINKLER SHEET | | | FS-1. | | | | | | 14. NOT ADDRESSED. THE SUBMITTED PLAN SHEETS DO NOT | | | ACTUALLY CORRELATE WITH THE LIST OF DRAWINGS AS SHOWN | | | ON SHEET A1.0. | | | | | | | | | NEW COMMENTS: | | | | | | 01. OCCUPANT LOAD SIGN WILL BE REQUIRED AT TIME OF FIRE | | | FINAL INSPECTION. CONTACT WPB BUREAU OF FIRE PREVENTION | | | AT (561) 804-4724 FOR ASSISTANCE. | | | | | | 02. PLEASE PROVIDE LIFE SAFETY SHEET ILLUSTRATING MAX. | | | TRAVEL DISTANCE COMPLIANCE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-27 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-27 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2008-05-27 12:30:15 | *****DENIED***** | | | | | | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE | | | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE | | | LANES, ETC.). | | | | | | 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 04.SINCE THE TOTAL OCCUPANT LOAD LISTED ON SHEET A1.0 | | | IS 172 PEOPLE, VERIFY THAT THE DOOR(S) IN THE REQUIRED | | | MEANS OF EGRESS FROM AN AREA HAVING AN OCCUPANT LOAD OF | | | 100 OR MORE PERSONS SHALL BE PROVIDED WITH PANIC | | | HARDWARE OR FIRE EXIT HARDWARE. | | | | | | 05.THE NUMBER OF EXIT LIGHTS SHOWN ON SHEET A2.1 DO | | | NOT CORRELATE WITH THAT OF SHEET E-4. | | | | | | 06.THE FLOOR PLAN LEGEND ON SHEET A2.0 MAKES | | | REFERENCE TO DOOR SCHEDULE ON SHEET A6.HOWEVER, A | | | DOOR SCHEDULE ON SHEET A6 COULD NOT BE FOUND. | | | | | | 07.IT APPEARS ON SHEET A2.0 THAT THE JANITOR'S CLOSET | | | DOOR (#10) OPENS IN THE PATH OF AN AISLE CORRIDOR MORE | | | THAN ONE HALF THE WIDTH OF THE AISLE.PLEASE EXPLAIN. | | | | | | 08.ON SHEET A4.2, DISPLAY/SHOW THE NUMERICAL ADDRESS | | | AT THE BUILDING'S FRONT ELEVATION.AS PER WEST PALM | | | BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN | | | HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. | | | | | | 09.IT IS STATED THAT ON SHEET A5.0 THAT INTERIOR | | | FINISHES SHALL COMPLY WITH NFPA 101 - 38.3.3;HOWEVER | | | THIS SECTION OF NFPA DEALS WITH NEW BUSINESS | | | OCCUPANCIES. | | | | | | 10.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM.AMEND THE FIRE ALARM SYSTEM'S SEQUENCE OF | | | OPERATION ON SHEET E-6 TO REFLECT THIS AHJ | | | REQUIREMENT. | | | | | | 11.NFPA 72 - 2002 EDITION SHALL BE REFERENCED. PLEASE | | | BE ADVISED THAT THE 1999 EDITION IS LISTED IN B UNDER | | | THE FIRE ALARM SYSTEM SCOPE ON SHEET E-6. | | | | | | 12.SHOW THE LOCATION OF THE WATER FLOW DEVICE AND THE | | | TAMPER SWITCH FOR THE FIRE ALARM/FIRE SPRINKLER | | | SYSTEM. | | | | | | 13.IN REFERENCE TO THE FIRE SPRINKLER SYSTEM, NFPA 13 | | | - 2002 EDITION SHALL BE REFERENCED. | | | | | | 14.THE SUBMITTED PLAN SHEETS DO NOT ACTUALLY | | | CORRELATE WITH THE LIST OF DRAWINGS AS SHOWN SO SHEET | | | A1.0 | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESWS, INCLUDE A | | | RESPONSE LETTER INDICATING WHERE ON THE APPROPIATE PLAN | | | SHEET EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2008-11-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-13 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-13 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2008-11-13 10:22:25 | REVISION DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHTS P-1 & P-2 DRAWING REFERENCE NOTES 5A, (P-1), | | | AND GAS RISER DIAGRAM, (P-2), INDICATE THE MANUAL SHUT | | | OFF VALVE AND EMERGENCY SHUT OFF VALVE UP IN THE | | | CEILING. THIS IS NOT APPROVED. ALSO THERE IS NO | | | REQUIRED UNION INDICATED DOWNSTREAM OF THE MANUAL SHUT | | | OFF VALVE. (SEE THE FOLLOWING): | | | __ EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | 2. SHTS P-1 & P-2 THE FLOOR PLAN, GAS SYSTEM | | | CALCULATIONS TABLE & THE GAS RISER DIAGRAM SHOW ITEM | | | 18, PIZZA OVEN. PER THE CONTRACTOR, ITEM 18 HAS BEEN | | | DELETED. THIS WAS INDICATED WHEN THE CONTRACTOR APPLIED | | | FOR THE GAS PERMIT. THE PROVISO INDICATED ON THE PLANS | | | REQUIRED MANUF. SPECIFICATION SHEETS FOR ITEM 18. THE | | | GAS PERMIT WAS ISSUED WITH THE STIPULATION THAT THE | | | REVISIONS DELETES ITEM 18. | | | | | | 3. SHT P-2 GAS SYSTEM CALCULATIONS BTU'S DO NOT REFLECT | | | THE MANUF. SPECIFICATION SHEETS SUBMITTED PLEASE | | | CORRELATE. THE FURTHEST OUTLET IS 145 FEET NOT 140 FEET | | | AS INDICATED. THIS IS WITH THE LENGTH OF PIPE FROM THE | | | METER TO THE FIRST RISE, (11 FEET OF 2-1/2" PIPE), THE | | | LENGTH OF PIPE THRU THE OUTSIDE WALL THRU SLEEVE, AND | | | THE LENGTH OF DROP DOWNSTREAM OF THE SLEEVED PIPE. | | | PLEASE INDICATE ALL PIPE LENGTHS AND RECALCULATE TOTAL | | | DEVELOPED LENGHT AND INDICTE ON THE GAS SYSTEM | | | CALCULATIONS. | | | | | | 4. SHT P-2 GAS RISER DIAGRAM HAS SOME PIPE SIZING THAT | | | IS INCORRECT. 1-1/4" PIPE IS REQUIRED TO THE SHUT OFF | | | VALVE TO THE WATER HEATER. (1" INDICATED). -- 2" PIPE | | | IS REQUIRED UP TO ITEM NUMBER 13, (NO PIPE SIZE | | | INDICATED). -- 1-1/2" REQUIRED UP TO ITEM 10, (NO PIPE | | | SIZE INDICATED). -- 1-1/4" REQUIRED UP TO ITEM 11, (NO | | | PIPE SIZE INDICATED). -- 1" REQUIRED UP TO ITEM 9, (NO | | | PIPE SIZE INDICATED). -- THE FOLLOWING STUB OUTS TO THE | | | APPLIANCES ARE NOT CORRECT. -- 1" REQUIRED TO SHUT OFF | | | VALVE FOR ITEM 15. -- 1-1/4" REQUIRED UP TO THE SHUT | | | OFF VALVES FOR ITEMS 17, 13 & 10. | | | | | | 5. SHT P-3 FOOD SERVICE PLUMBING EQUIPMENT SCHEDULE. | | | REVISIED MANUFACTURE & MODEL NUMBER CHANGED TO READ | | | "REFER TO KITCHEN CONSULTANT DRAWINGS". KITCHEN | | | CONSULTANT DRAWINGS WERE NOT SUBMITTED. IF THE GAS | | | EQUIPMENT HAS CHANGED, THEN THE MANUFACTURE | | | SPECIFICATION SHEETS FOR THE GAS EQUIPMENT SHALL BE | | | SUBMITTED AND SHALL CORRELATE WITH THE GAS LOAD | | | INDICATED ON THE GAS RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2008-08-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-27 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-27 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2008-08-27 16:39:52 | | | | | | | | | | PASSED/PROVISO | | | | | | MANUF. SPEC. SHEETS FOR THE WATER HEATER AND THE PIZZA | | | OVEN NOT SUBMITTED. SUBMIT AT TIME OF GAS PERMIT | | | APPLICATION. | | | | | | GAS PIPING NOT CORRECT. 2-1/2" REQUIRED TO ITEM 17.-- | | | 1-1/4" REQUIRED TO SHUT OFF VALVE FOR WATER HEATER-- | | | 2" REQUIRED TO ITEM 13,--1-1/2" REQUIRED TO ITEM | | | 10.--1-1/4" MINIMUM REQUIRED THRU ITEM 9 INCLUDING | | | SHUT OFF VALVE.--1-14" REQUIRED FOR SUPPLY AND SHUT | | | OFF VALVE FOR ITEM 10.--1" REQUIRED FOR SUPPLY AND | | | SHUT OFF VALVE FOR ITEM 13.--1" REQUIRED FOR SUPPLY | | | AND SHUT OFF VALVE FOR ITEM 15.--1-14" REQUIRED FOR | | | SUPPLY AND SHUT OFF VALVE FOR ITEM 17. ---A | | | REVISION IS REQUIRED FOR SHT P-2 GAS RISER DIAGRAM | | | REFLECTING THESE AS SOON AS POSSIBLE. | | | | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-11 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-11 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2008-08-11 10:18:03 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR PERMIT: | | | | | | A. OK | | | B. OK | | | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO MANUF | | | SHEETS FOUND. | | | ******NO RESPONSE, COMMENT NOT ADDRESSED | | | | | | D. N/A | | | E. N/A | | | | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM | | | OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE | | | RISER DIAGRAM. | | | ******NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-21 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-21 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2008-08-11 09:52:22 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR PERMIT: | | | | | | A. OK | | | B. OK | | | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO MANUF | | | SHEETS FOUND. | | | | | | D. N/A | | | E. N/A | | | | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM | | | OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE | | | RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-05-12 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-05-12 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2008-08-11 09:45:07 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR PERMIT: | | | | | | A. TYPE OF GAS, (LP OR NATURAL). | | | | | | B. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | D. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | E. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2008-11-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-11-21 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-11-21 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2008-11-21 13:37:57 | FIRE REVIEW ROUTED TO WENNEGREN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-11-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-20 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-20 |
Time |
11:33 |
Sent To |
P |
|
| Notes |
| 2008-11-20 11:33:35 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-17 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-17 |
Time |
14:58 |
Sent To |
M |
|
| Notes |
| 2008-11-17 14:58:56 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-11-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-13 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-13 |
Time |
13:33 |
Sent To |
M |
|
| Notes |
| 2008-11-13 13:35:06 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-31 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-31 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2008-10-31 16:34:45 | TO "COMM" BD#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-10-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-28 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-28 |
Time |
17:00 |
Sent To |
P |
|
| Notes |
| 2008-10-28 17:00:44 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-10-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-06 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-06 |
Time |
11:59 |
Sent To |
M |
|
| Notes |
| 2008-10-06 12:00:02 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
|
Date |
2008-10-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-06 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-06 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2008-10-06 09:47:20 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-25 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-25 |
Time |
11:51 |
Sent To |
B |
|
| Notes |
| 2008-09-25 11:51:51 | TO "JWITMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-08-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-25 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-08-25 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2008-08-26 12:11:55 | 8-26-08 TO "COMM" BD. #53. | | 2008-08-25 16:44:47 | WAITING FOR "COMM" BD. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-08-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-08 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-08 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2008-08-08 11:14:56 | TO "COMM" BD#11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-06-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-06-26 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-06-26 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2008-06-30 13:56:53 | TO "COMM" BD#13 | | 2008-06-26 16:41:16 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-02 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2008-05-01 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2008-05-01 13:00:36 | TO "COMM" BD#49 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2008-11-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-22 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-22 |
Time |
12:09 |
Sent To |
PC |
|
| Notes |
| 2008-11-22 12:10:30 | MECH HOOD REVISED PLANS REVIEWED UNDER SEPARATE PERMIT | | | #08070086 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2008-11-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-22 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-22 |
Time |
11:33 |
Sent To |
PC |
|
| Notes |
| 2008-11-22 11:33:53 | REVISED M1 AND COOLING LOAD CALCS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-11-04 |
Time |
08:24 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2008-11-04 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2008-11-04 08:38:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO MECHANICAL PLANS | | | *** DENIED *** | | | | | | 1) THE COOLING LOAD CALCULATIONS NEED TO BE REVISED AS | | | THE A/C EQUIPMENT AND THE ENGINEER OF RECORD HAS | | | CHANGED, PER 13-407.1.ABC.1.1. | | | | | | 2) OUTSIDE AIR CALCULATIONS ARE INCORRECT, SEE ATTACHED | | | COPY OF THE ARCHITECTURAL PLAN'S SQUARE FOOTAGE AND | | | SEATING CAPACITY. PLEASE CORRECT PER 2004 FBC/M 403.3. | | | (ALSO THE OUTSIDE AIR CALCULATIONS ARE MISSING THE BAR | | | AREA). | | | | | | 3) OUTSIDE AIR CALCULATIONS SHOW 'ADJUST PER EXCEPTION | | | 403.3. THE EXCEPTION READS "EXCEPTION: THE OCCUPANT | | | LOAD IS NOT REQUIRED TO BE DETERMINED, BASED ON THE | | | ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE | | | 403.3 WHERE APPROVED STATISTICAL DATA DOCUMENT THE | | | ACCURACY OF AN ALTERNATE ANTICIPATED OCCUPANT DENSITY". | | | PLEASE SUBMIT A COPY OF THE CODE SECTION THAT PERMITS A | | | 50% REDUCTION OF OUTSIDE AIR. | | | | | | 4) THE AIR BALANCE DIAGRAM IS INCORRECT. SEE ATTACHED | | | COPY OF HOOD PLAN FOR THE KITCHEN HOOD FANS. PLEASE | | | CORRECT PER 2004 FBC 13-409.1.ABC.3.6.1. | | | | | | 5) THE PLAN SHOWS FLEXIBLE DUCT BEING USED AT THE | | | BATHROOM EXHAUST FANS. EXHAUST DUCTS SHALL BE METAL, | | | PER 2004 FBC 501.4. | | | | | | 6) THE 200,000 BTU GAS WATER HEATER IN THE JANITOR'S | | | CLOSET IS A CONFINED SPACE, SEE 2004 FBC/FG 304.5.1. | | | PLEASE PROVIDE FOR COMBUSTION AIR PER 2004 FBC/FG 304.1 | | | IF THE TRANSFER GRILL IS FOR COMBUSTION AIR, SEE 2004 | | | FBC/FG 304.6.2 ONE PERMANENT OPENING. PLEASE CORRECT. | | | | | | 7) THE JANITOR'S CLOSET ALSO HAS AN EXHAUST FAN IN IT, | | | PLEASE PROVIDE FOR MAKE-UP AIR TO THE GAS WATER HEATER, | | | PER 2004 FBC/FG 304.4 AND 304.9.1. | | | | | | 8) PLEASE PROVIDE COMBUSTION AND MAKE-UP AIR | | | CALCULATIONS FOR THE GAS WATER HEATER, PER 2004 FBC/FG | | | 304. | | | | | | 9) PLEASE SHOW THE SIZE OF THE EXISTING OUTSIDE AIR | | | DUCTWORK AS ONE IS SUPPLING TWO 14" OUTSIDE AIR DUCTS, | | | SEE 2004 FBC/M 603.2. | | | | | | 10) A/C SYSTEM MODEL NUMBERS AHU 40RM-012H AND ACU | | | 38ARD014 LISTED ON THE A/C EQUIPMENT SCHEDULE COULD NOT | | | BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT | | | MANUFACTURE SPECIFICATION SHEETS, PER 2004 FBC | | | 13-407.1.ABC.3.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2008-10-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-10-06 |
Time |
14:13 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2008-10-06 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2008-10-06 14:29:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO MECHANICAL PLANS AND COOLING LOAD CAL'S. | | | *** DENIED *** | | | | | | 1) THE ENGINEER OF RECORD IS J. DAVID PUGA WITH PUGA | | | AND ASSOCIATES INC. (305) 661-7700 ONLY HE CAN MAKE | | | REVISIONS TO THE MECHANICAL PLANS AND COOLING LOAD | | | CAL'S. IF YOU ARE CHANGING ENGINEERS YOU MUST SUBMIT A | | | NOTARIZED LETTER FROM J. DAVID PUGA OR THE GENERAL | | | CONTRACTOR REMOVING HIM FROM THE JOB. PER FAC 61G15-27. | | | | | | 2 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR | | | PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND | | | FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G). | | | | | | **PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND | | | SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. | | | AMEND. 106.3. | | | | | | *** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-09-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-05 |
Time |
11:36 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-09-05 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2008-09-05 11:37:52 | ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | | (A) WALK-IN-COOLER | | | (B) KITCHEN HOOD | | | (C) FIRE SUPPRESSION | | | ** SUBMIT PLANS WITH PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-11 |
Time |
15:51 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2008-08-11 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2008-08-11 15:52:31 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) MECHANICAL PLAN M-4 NEEDS TO BE SEALED BY THE | | | ENGINEER, SEE FAC 61G15-23.002. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-01 |
Time |
16:33 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-07-01 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2008-07-01 16:38:11 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLANS SUBMITTED ARE MISSING PAGES M-3, M-4, S-2, AND | | | S-3. PLEASE SUBMIT TWO COPIES OF THE MISSING PAGES SO | | | THAT A COMPLETE REVIEW CAN BE DONE, PER 2004 FBC | | | 106.1.1 AND 106.3.5. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-05-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-14 |
Time |
12:13 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2008-05-14 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2008-05-14 12:27:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLAN M-1 GENERAL HVAC NOTE 4.1 AND M-2 EQUIPMENT | | | STAND DETAIL NOTE 2, REFERENCES HURRICANE FORCE WINDS. | | | NEEDS TO STATE 140 MPH HURRICANE FORCE WINDS, PER 2004 | | | FBC 1609. | | | | | | 2) PLAN M-2 IF CONDENSER STANDS ARE PRE-ENGINEERED | | | PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR | | | PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND | | | FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G). | | | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | 3) THE COOLING LOAD CALCULATIONS NEED TO BE SIGNED AND | | | SEALED BY THE ENGINEER, PER 2004 FBC 13-407.1.ABC.1 | | | EXCEPT. | | | | | | 4) WHEN RE-SUBMITTING THE ENERGY CALCULATIONS HAVE THEM | | | SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC 13-103.3. (SEE | | | ELECTRICAL REVIEW NOTE 4 REGARDING E-CAL'S, PLEASE | | | CORRECT). | | | | | | 5)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C | | | EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI | | | DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI | | | CERTIFICATE, PER 2004 FBC 13-407.1.ABC.3.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2008-11-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-13 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-12 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2008-11-13 09:58:45 | REVISION DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | 1, SHT P-2 SANITARY RISER DIAGRAM SHOWS AN EXISTING 4" | | | GREASE LINE FROM THE SECOND FLOOR. NO GREASE | | | INTERCEPTOR OR SAMPLE POINT IS INDICATED. PLEASE | | | CONTACT WILLIAM ROBERTS ENVIRONMENTAL COMPLIANCE TO | | | DETERMINE THE REQUIREMENT FOR A GREASE | | | INTERCEPTOR/SAMPLE POINT FOR NEW GREASE LINE NOT | | | INDICATED PREVIOUSLY. ARTICLE III SECTION 90-124(7). | | | MR. ROBERTS PHONE NUMBER IS (561) 822-2200 EXT 2272, | | | FAX NUMBER IS (561) 659-7458 & E-MAIL IS | | | [email protected]. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-08-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-27 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-27 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-11 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-11 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2008-08-11 10:16:50 | DENIED | | | REFERENCE: FBC-2004 PLUMBING W/2007 REV | | | FBC-2004 BUILDING W/2007 REV | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | | | | 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR PERMIT: | | | | | | A. OK | | | B. OK | | | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO | | | MANUF. SHEETS FOUND. | | | ******NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | D. N/A | | | E. N/A | | | | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM | | | OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE | | | RISER DIAGRAM. | | | ******NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 15. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-21 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-21 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2008-07-21 14:00:23 | DENIED | | | REFERENCE: FBC-2004 PLUMBING W/2007 REV | | | FBC-2004 BUILDING W/2007 REV | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | | | | 2. SHT A1.0 LIST OF DRAWINGS DOES NOT REFLECT THE | | | SHEETS SUBMITTED. SHTS S-1, E-6, A-1, A-2 & A-3 WERE | | | SUBMITTED BUT NOT SHOWN ON THE DRAWING LIST. ALSO SHTS | | | FP-1, FS-2, FS-3 & FS-4 WERE INDICATED ON THE LIST BUT | | | NOT SUBMITTED. PLEASE CORRELATE THE DRAWING LIST WITH | | | SHEETS SUBMITTED. SECTION 106.1.3. | | | ****RESPONSE NOTED, BUT SHEETS S-2, S-3, M-3 & M-4 ARE | | | SHOWN ON THE DRAWING LIST BUT NOT SUBMITTED. PLEASE | | | CORRELATE. | | | | | | 3. OK | | | 4. OK | | | 5. OK | | | | | | 6. SHT A5.0 FINISH SCHEDULE. SHOW COMPLIANCE WITH | | | SECTION 1210.2 REQUIREMENT FOR WALLS WITHIN 2FT OF | | | W/C'S & URINALS TO BE A SMOOTH, HARD & NONABSORBENT | | | SURFACE. THE SCHEDULE IS INDICATING PAINT WHICH DOES | | | NOT COMPLY WITH THE "HARD" PORTION OF THE | | | REQUIREMENTS. | | | ****RESPONSE NOTED, BUT SHTS A4.0 & A4.1 DO NOT | | | INDICATE THE FINISH & SHT A5.0 STILL SHOWS AN, "EPOXY | | | PAINTED SURFACE", WHICH DOES NOT COMPLY. | | | | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | | | | 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR PERMIT: | | | | | | A. OK | | | B. OK | | | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO | | | MANUF. SHEETS FOUND. | | | | | | D. N/A | | | E. N/A | | | | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT THE UNION REQUIRED DOWNSTREAM | | | OF THE MANUAL SHUT OFF VALVE IS NOT INDICATED ON THE | | | RISER DIAGRAM. | | | | | | 15. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-05-12 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-05-10 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2008-05-12 12:04:56 | DENIED | | | REFERENCE: FBC-2004 PLUMBING W/2007 REV | | | FBC-2004 BUILDING W/2007 REV | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK. THE | | | ADDRESS OF RECORD ON THE FLORIDA STATE DBPR WEBSITE | | | DOES NOT REFLECT THE ADDRESS ON THE TITLE BLOCKS FOR | | | THE ARCHITECT. PLEASE CORRELATE THE ADDRESS ON THE | | | TITLE BLOCK SO THAT IT RELFECTS THE ADDRESS OF RECORD | | | WITH THE STATE. EITHER UPDATE THE DBPR WEBSITE OR THE | | | TITLE BLOCKS PRIOR TO RESUBMITTING PLANS FOR REVIEW. | | | FAC 61G1-16.004(1) & FS 481.219, 481.2055. | | | | | | 2. SHT A1.0 LIST OF DRAWINGS DOES NOT REFLECT THE | | | SHEETS SUBMITTED. SHTS S-1, E-6, A-1, A-2 & A-3 WERE | | | SUBMITTED BUT NOT SHOWN ON THE DRAWING LIST. ALSO SHTS | | | FP-1, FS-2, FS-3 & FS-4 WERE INDICATED ON THE LIST BUT | | | NOT SUBMITTED. PLEASE CORRELATE THE DRAWING LIST WITH | | | SHEETS SUBMITTED. SECTION 106.1.3. | | | | | | 3. SHTS A2.0 & A4.0 DETAIL #1 ACCESSIBLE STALL SHALL | | | COMPLY WITH FIGURE 11-30(E). THE LAV CAN NOT BE IN THE | | | CLEAR FLOOR SPACE OF THE W/C AND THE W/C SHALL BE | | | LOCATED IN THE CORNER, DIAGONAL TO THE DOOR. SECTION | | | 11-4.17.3. | | | | | | 4. SHTS A2.0 & A4.0 SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | __FOR W/C: | | | A. 11-4.16.5 FLUSH CONTROLS | | | __FOR LAV: | | | A. 11-4.19.2 CLEARANCES | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | | | | 5. SUBMIT A DETAIL FOR THE ACCESSIBLE URINAL SHOWING | | | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS & | | | FIGURES. | | | | | | 6. SHT A5.0 FINISH SCHEDULE. SHOW COMPLIANCE WITH | | | SECTION 1210.2 REQUIREMENT FOR WALLS WITHIN 2FT OF | | | W/C'S & URINALS TO BE A SMOOTH, HARD & NONABSORBENT | | | SURFACE. THE SCHEDULE IS INDICATING PAINT WHICH DOES | | | NOT COMPLY WITH THE "HARD" PORTION OF THE | | | REQUIREMENTS. | | | | | | 7. SHTS P-1 & P-2 PLEASE INDICATE ON THE RISER AND | | | SUBMIT A DETAIL FOR THE SAMPLE POINT REQUIRED ON THE | | | GREASE LINE. THE SAMPLE POINT SHALL BE A 4" CROSS WITH | | | A MINIMUM 12" DROP BELOW THE DRAIN LINE WITH A HARD CAP | | | AND A CLEANOUT UP TO FINISHED FLOOR ABOVE THE DRAIN | | | LINE. SECTION 106.1.2. | | | | | | 8. SHTS P-1 & P-2 TRAP PRIMERS ARE REQUIRED AT ALL | | | FLOOR DRAINS WHERE THE TRAP IS SUBJECT TO LOSS BY | | | EVAPORATION SUCH AS THE FLOOR DRAIN AT THE WATER | | | HEATER. SECTION 1002.4. PLEASE SHOW ON THE RISER | | | DIAGRAMS. | | | | | | 9. SHT P-1 INDICATES 2 FFD'S BUT NO CONNECTION TO THE | | | SANITARY BUILDING DRAIN OR BRANCH LINE. PLEASE CLARIFY. | | | ALL INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR A | | | HUB DRAIN AS A FLOOR DRAIN IS NOT AN APPROVED INDIRECT | | | WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. | | | | | | 10. SHT P-1 NO WATER SUPPLY IS SHOWN TO ITEMS 39, 40, | | | 41, 42 & 56. THIS DOES NOT REFLECT SHT P-2 RISER | | | DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1, 601.1 & | | | 604.3. | | | | | | 11. SHT P-2 WATER RISER DIAGRAM DOES NOT RELFLECT THE | | | FLOOR PLAN. NO WATER IS SHOWN TO THE WALL HYDRANTS. | | | PLEASE SHOW PIPING, PIPE SIZE, VALVES ETC.--ALSO | | | THERE IS NO WATER SHOWN TO THE ICE MAKER. SECTIONS | | | 106.1.1, 601.1 & 604.3. | | | | | | 12. SHT P-2 SANITARY RISER DIAGRAM. SAFE WASTES ARE NOT | | | APPROVED. THE FFDS CONNECTING TO THE FLOOR SINK SHALL | | | BE DELETED AND FLOOR SINKS SHALL BE INSTALLED OR THE | | | INDIRECT PIPING SHALL BE INSTALLED TO THE FLOOR SINKS | | | SHOWN. (SEE ITEMS 38, 39, 40, 60, 61 & 62).--ALSO | | | FIXTURES SHALL NOT BE DOUBLE TRAPPED PER SECTION | | | 1002.1. | | | | | | 13. SHT P-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE | | | FLOOR PLAN UPSTREAM OF ITEMS 49 & 50 AS WELL AS | | | DOWNSTREAM OF ITEM 45. PLEASE CORRELATE.--IDENTIFY | | | THE FIXTURE UPSTREAM OF FFD FOR ITEM 54. ITEM 54 IS | | | REQUIRED TO DRAIN INTO A FLOOR SINK OR A HUB DRAIN PER | | | SECTIONS 803.2 & 803.2.3. | | | | | | 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR PERMIT: | | | | | | A. TYPE OF GAS, (LP OR NATURAL). | | | | | | B. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | D. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | E. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | 15. SHT P-4 PLUMBING FIXTURE SCHEDULE INDICATES A | | | CONCRETE LAV, BUT UNDER MANUFACTURE IT STATES "REFER TO | | | ARCHITECTURAL DRAWINGS". SHT A4.0 DETAIL 1 REFERS TO | | | NOTE "J" WHICH REFERS TO I.D. DRAWINGS WHICH WERE NOT | | | SUBMITTED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS | | | FOR THE LAV. PLEASE INDICATED MANUF & MODEL NUMBER. | | | SECTION 303..4. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-08-12 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-08-12 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-08-12 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2008-08-12 15:30:09 | ZONING REVIEW: PASSED | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-07-02 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-07-02 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2008-07-02 08:42:34 | ZONING REVIEW: PASSED | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-05-06 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-05-06 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2008-05-06 11:12:17 | ZONING REVIEW: PASSED WITH PROVISO: | | | | | | 1) ELEVATIONS DO NO SEEM TO INDICATE ANY AWNING OR | | | CANOPIES AT CLEMATIS STREET. CONFIRM THIS IS CORRECT. | | | WILL EXISTING AWNINGS REMAIN? | | | 2) CONFIRM IF SHUTTERS WILL BE NECESSARY FOR NEW | | | GLAZING. IF SO, THEY SHOULD BE INDICATED ON THE | | | ELEVATIONS AND IN PLAN. | | | | | | OTHER NOTES: | | | | | | 1) RESTAURANT WILL REQUIRE 4COP-SRX OR 2COP ALCOHOL | | | LICENSE, WITH APPROVAL FROM PLANNING & ZONING DEPT AT | | | TIME OF BUSINESS LICENSE APPLICATION. | | | 2) OUTDOOR SEATING IS SUBJECT TO APPROVAL BY SIDEWALK | | | CAFE PERMIT. PLEASE OBTAIN APPLICATION FROM P & Z DEPT. | | | (MAY BE SUBMTTED AT TIME OF BUSINESS LICENSE APP). | | | | | | MATT FLIS - 822-1445 |
|
|