Plan Review Details - Permit 08040787
Plan Review Stops For Permit 08040787
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-09 Cont ID  
Sent By rmcdouga Date 2008-05-09 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2008-05-09 Time 14:21 Sent To  
Notes
2008-05-09 15:27:022004 FBC W/2007 REVISIONS
 LIGHT POLES
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SURVEY/SITE PLAN SPECIFYING
 THE LOCATION OF THE NEW LIGHT POLES.
  
 2) SUBMIT TWO COPIES OF SIGNED AND SEALED ENGINEERING
 FOR THE LIGHT POLES, BASES AND ANCHORS. SPECIFY THE
 WINDLOAD DESIGN DATA ON THE ENGINEERING. SEE FBC
 1609.1.1 AND ASCE 7-02.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-07 Cont ID  
Sent By btrobaug Date 2008-05-07 Time 14:27 Rev Time 0.00
Received By btrobaug Date 2008-05-07 Time 13:45 Sent To B
Notes
2008-05-07 14:27:32 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 THE POLES TO BE INSTALLED AND THE EXISTING POLES FOR
 RECORD RETENTION 106.5 FBC.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 4} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 EQUIPMENT BEING WIRED UNDER THIS PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-09 Cont ID  
Sent By rmcdouga Date 2008-05-09 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2008-04-30 Time 10:32 Sent To  
Notes
2008-04-30 10:32:14TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-02 Cont ID  
Sent By mflis Date 2008-05-02 Time 11:02 Rev Time 0.00
Received By mflis Date 2008-05-02 Time 11:01 Sent To E
Notes
2008-05-02 11:02:53ZONING REVIEW: FAILED
  
 * NO SURVEY OR SITE PLAN PROVIDED TO INDICATE LOCATION
 OF POLLS TO BE REPLACED. PLEASE INCLUDE IN
 RESUBMISSION
  
 MATT FLIS - 822-1445