Plan Review Details - Permit 08040717
Plan Review Stops For Permit 08040717
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-09 Cont ID  
Sent By jgomez Date 2008-05-09 Time 10:56 Rev Time 0.00
Received By jgomez Date 2008-05-09 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By jgomez Date 2008-04-28 Time 16:58 Rev Time 0.00
Received By jgomez Date 2008-04-28 Time 07:48 Sent To PC
Notes
2008-04-28 17:02:35MERCANTILE OCCUPANCY,BUILDING REVIEW CHECKLIST:
 BUILDING REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SPECIFY BUILDING CONSTRUCTION TYPE AS REQUIRED BY
 SEC. 602.1 FBC 2004 AND SPECIFY HOW OPENING IS GOING TO
 BE INFILLED TO VERIFY COMPLIANCE WITH BUILDING
 CONSTRUCTION TYPE.
  
 2- PROVIDE ALL THE WIND DESIGN DATAAS REQUIRED BY
 SEC. 1603.1.4FBC 2004. AND PROVIDE SPECIFICATIONS
 SHOWINGHOW NEW INFILL WALL WILL RESIST THE CALCULATED
 WIND LOADS.
 ***NOTE: ACCORDING TO SEC. 1609.4FBC 2004 THIS
 BUILDING IS LOCATED ON EXPOSURE "C".
  
 3- PERSON RESPONSIBLE FOR THE DESIGN NEEDSTO SIGN
 DRAWINGSAS REQUIRED BY SEC. 106.1.3 CITY AMENDMENTS
 TO FBC 2004.
  
 4- PLEASE IDENTIFY ALL ROOMS TO VERIFY COMPLIANCE WITH
 THE OCCUPANT LOAD OF TABLE 1004.1.2 FBC 2004. . THERE
 ARE SOME ROOMS THAT DON'TIDENTIFY THE USE OF THE
 ROOM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-28 Cont ID  
Sent By jgomez Date 2008-04-28 Time 17:02 Rev Time 0.00
Received By jgomez Date 2008-04-28 Time 17:02 Sent To  
Notes
***NONE***