| 2008-04-24 15:58:19 | MERRY PLACE PROJECT, PICNIC SHELTERS BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004. |
| | |
| | 1- SITESTRUCTURE AMENITIES LIKE PICNIC SHELTERS AND |
| | PLAYGROUNDS NEED TO BE SUBMITTED UNDER A SEPARATE |
| | PERMIT. |
| | |
| | 2- CALCULATIONS SUBMITTED DON'T MATCH SIZE AND TYPE OF |
| | STRUCTURE SHOWN ON FLOOR PLAN SUBMITTED. CALCULATIONS |
| | ARE FOR 18' PITTSBURGH SQUARE SHELTERS, WHILE DRAWINGS |
| | SHOW 18' X 36'RECTANGULAR SHELTERS.ALSO, SEE THE |
| | 1/4" STEEL CABLE AROUND PERIMETER OF SHELTER. REVISE AS |
| | REQUIRED TO MATCH. |
| | |
| | 3- ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATION IN ALL |
| | CALCULATIONS SHEETSAS REQUIRED BY SEC. 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA |
| | STATUTE. |
| | |
| | 4- ENGINEER NEEDS TO SIGN AND SEAL ALL CALCULATIONS |
| | SHEETS. SOME ARE MISSING THE SIGNATURE. SEC |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND CHAPTER |
| | 471 FLORIDA STATUTE. |
| | |
| | 5-IF ONLY THE STRUCTURE IS DESIGNED TO RESIST THE |
| | 140MPH WIND LOAD WITHOUT THE FABRIC , THEN NEED TO |
| | PROVIDE FABRIC REMOVAL INSTRUCTIONS TO SHOW COMPLIANCE |
| | WITH SEC. 3105.4.2.1 FBC 2004 FOR QUICK RELEASE.THE |
| | INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS. |
| | THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL. |
| | PROVIDE COMPLETE INFORMATION AS REQUIRED. |
| | |
| | 6- PER BUILDING OFFICIAL, NEIL MELICK,A LETTER SIGNED |
| | BY THE OWNER (NOT TENANT)IS REQUIREDACKNOWLEDGING |
| | RESPONSIBILITY TO HAVE THE FABRIC REMOVED PRIOR TO ANY |
| | WIND EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH OR |
| | GREATER.PROVIDE LETTER FROM OWNER ACKNOWLEDGING REMOVAL |
| | OFFABRIC. |
| | |
| | 7-PICNIC TABLES : |
| | A) PROVIDE COMPLETE DRAWINGS SHOWING COMPLIANCE WITH |
| | CHAPTER TWOOF FAIR HOUSING ACT (ACCESSIBLE AND USABLE |
| | PUBLIC AND COMMON USE AREAS). ***NOTE: READ DEFINITIONS |
| | ON SHEET 2.2 OF FAIR HOUSING ACT TO BETTER UNDERSTAND |
| | DRAWINGS REQUIRED TO SHOW COMPLIANCE WITH THIS |
| | CHAPTER. |
| | |
| | B) CLARIFY IF TABLES AND CHAIRS WILL BE ANCHORED TO |
| | THE GROUND TO RESIST THE 140MPH WIND LOADS (PROVIDE |
| | DETAILS) OF SEC.1609 FBC 2004OR IF THEY WILL BE |
| | STORED DURING HURRICANE WARNINGS.IF SECOND OPTION, |
| | THEN PROVIDE LETTER FROM OWNER ACKNOWLEDGING SO. |
| | |
| | |