| 2008-04-25 09:26:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | |
| | 1) PLEASE SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL |
| | DUCT DESIGN, PER 2004 FBC/R M1601.1. |
| | |
| | 2) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE |
| | AIR DIFFUSERS SHOWING THEIR FLAME SPREAD RATING AND |
| | SMOKE-DEVELOPED RATING. PER 2004 FBC/R M1601.16 |
| | REGISTERS, GRILLES AND DIFFUSERS. |
| | DUCT REGISTERS, GRILLES AND DIFFUSERS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS, AND SHALL HAVE A FLAME |
| | SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED |
| | PROGRESSIVE COMBUSTION AND A SMOKE-DEVELOPED RATING NOT |
| | OVER 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. |
| | BALANCING DAMPERS OR OTHER MEANS OF SUPPLY AIR |
| | ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR AT |
| | EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER. |
| | |
| | 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR DIFFUSERS, |
| | PER WPB AMEND. 106.3.5.4 (10). |
| | |
| | 4) PLEASE SHOW THE SEER OF THE A/C SYSTEM IN THE |
| | EQUIPMENT SCHEDULE ON THE PLAN. |
| | |
| | 5) A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C EQUIPMENT |
| | SCHEDULE COULD NOT BE FOUND ON THE ARI DIRECTORY |
| | WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE, |
| | SEE 2004 FBC 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |