Plan Review Details - Permit 08040667
Plan Review Stops For Permit 08040667
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-17 Cont ID  
Sent By shill Date 2008-11-17 Time 10:04 Rev Time 0.00
Received By shill Date 2008-11-17 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-08-18 Cont ID  
Sent By shill Date 2008-08-18 Time 10:10 Rev Time 0.00
Received By shill Date 2008-08-18 Time 10:10 Sent To  
Notes
2008-08-18 10:13:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION
 MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE.
 YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP
 AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION
 SCHEDULE FORM.
  
 2ND REVIEW, PLEASE REVISE SHUTTER CONNECTION MOUNTING
 TYPE TO CORRELATE WITH THE ANCHORS SCHEDULES.FOR THE
 ACCORDIONS, THIS SHOULD BE C1 THROUGH C5.FOR THE
 PANELS, WALL MOUNT 1 THROUGH 13.PLEASE NOTE THAT
 OPENING 1 SPECIFIES TAPCONS, BUT CIRCLED ANCHOR SPACING
 FOR SOLID SET FOR BOTTOM 8 (TAPCONS NOT PERMITTED FOR
 THAT SPAN, SHUTTER CONNECTION MOUNTING TYPE).
  
 3RD REVIEW, INSTALLATION SCHEDULE STATES WALL.THERE
 ARE DIFFERENT TYPES OF WALL MOUNT, EACH WITH DIFFERENT
 ANCHOR SPACING REQUIREMENTS.PLEASE REVISE AS
 REQUESTED.
  
 3.ADDRESSED.
  
 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS
 THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH,
 DEPENDING ON TYPE OF SHUTTER.
  
 2ND REVIEW, THIS WAS NOT ADDRESSED BUT AS VERTICAL WAS
 SPECIFIED, I USED THAT DIMENSION FOR THE REVIEW.
  
 3RD REVIEW, NOT ADDRESSED.PLEASE SPECIFY SPAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-04 Cont ID  
Sent By shill Date 2008-06-04 Time 15:52 Rev Time 0.00
Received By shill Date 2008-06-04 Time 15:52 Sent To  
Notes
2008-06-04 15:59:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION
 MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE.
 YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP
 AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION
 SCHEDULE FORM.
  
 2ND REVIEW, PLEASE REVISE SHUTTER CONNECTION MOUNTING
 TYPE TO CORRELATE WITH THE ANCHORS SCHEDULES.FOR THE
 ACCORDIONS, THIS SHOULD BE C1 THROUGH C5.FOR THE
 PANELS, WALL MOUNT 1 THROUGH 13.PLEASE NOTE THAT
 OPENING 1 SPECIFIES TAPCONS, BUT CIRCLED ANCHOR SPACING
 FOR SOLID SET FOR BOTTOM 8 (TAPCONS NOT PERMITTED FOR
 THAT SPAN, SHUTTER CONNECTION MOUNTING TYPE).
  
 3.ADDRESSED.
  
 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS
 THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH,
 DEPENDING ON TYPE OF SHUTTER.
  
 2ND REVIEW, THIS WAS NOT ADDRESSED BUT AS VERTICAL WAS
 SPECIFIED, I USED THAT DIMENSION FOR THE REVIEW.
  
 NEW COMMENTS:
  
 5.1 3/4" TAPCONS SPECIFIED.THIS IS THE EMBEDMENT
 REQUIREMENT; A LONGER TAPCON IS REQUIRED TO MEET THE
 EMBEDMENT REQUIREMENT (STUCCO, SHUTTER TRACK).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By shill Date 2008-04-28 Time 11:43 Rev Time 0.00
Received By shill Date 2008-04-28 Time 11:43 Sent To  
Notes
2008-04-28 11:55:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE COPY OF THE INSTALLATION SCHEDULE IS NOT
 COMPLETE, OPENING NUMBERS ARE CUT OFF.PLEASE PROVIDE
 A CLEAR COPY.
  
 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION
 MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE.
 YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP
 AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION
 SCHEDULE FORM.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9B72.UNSEALED ENGINEERING WAS PROVIDED WITHOUT THE
 STATE PRODUCT APPROVAL.
  
 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS
 THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH,
 DEPENDING ON TYPE OF SHUTTER.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-31 Cont ID  
Sent By adarroug Date 2008-10-31 Time 15:53 Rev Time 0.00
Received By adarroug Date 2008-10-31 Time 15:53 Sent To B
Notes
2008-10-31 15:54:11TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 13:43 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 13:43 Sent To B
Notes
2008-08-08 13:44:03TO "SHILL" DESK/REUSB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 11:23 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 11:22 Sent To B
Notes
2008-05-30 11:23:57TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-28 Cont ID  
Sent By shill Date 2008-04-28 Time 11:55 Rev Time 0.00
Received By shill Date 2008-04-24 Time 15:59 Sent To  
Notes
2008-04-24 15:59:44TO "MISC" BOX#1