Plan Review Details - Permit 08040631
Plan Review Stops For Permit 08040631
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-16 Cont ID  
Sent By mjacobs Date 2008-06-16 Time 14:01 Rev Time 0.00
Received By mjacobs Date 2008-06-16 Time 12:47 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-02 Cont ID  
Sent By mjacobs Date 2008-06-02 Time 07:39 Rev Time 0.00
Received By mjacobs Date 2008-05-30 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-03 Cont ID  
Sent By mjacobs Date 2008-05-03 Time 05:50 Rev Time 0.00
Received By mjacobs Date 2008-05-02 Time 18:06 Sent To PC
Notes
2008-05-03 05:50:00BUILDING PLAN REVIEW5-2-08
 PERMIT: 08040631
 ADD: 2581 METROCENTRE BLVD
 CONT: SISCA CONSTRUCTION SERVICES, LLC
 TEL: (561)686-5545
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2 ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. EPOXY
 PAINT ON DRYWALL DOES NOT MEET THIS REQUIREMENT.
  
 5)IF THE BUILDING HAS A FIRE SPRINKLER SYSTEM, SHOW
 THE LAYOUT OF THE SPRINKLER HEADS IN RELATION TO THE
 RENOVATION OF THE BUILDING.THIS INFORMATION CAN BE
 SHOWN ON THE CEILING PLANS. FBC 106.3.5.1.1(5) AND FS
 553.79(2).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-28 Cont ID  
Sent By btrobaug Date 2008-04-28 Time 14:00 Rev Time 0.00
Received By btrobaug Date 2008-04-28 Time 13:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-09 Cont ID  
Sent By mwennerg Date 2008-06-09 Time 15:37 Rev Time 0.00
Received By mwennerg Date 2008-06-09 Time 15:37 Sent To  
Notes
2008-06-09 15:38:37NEW SHEET A.1 STAMPED, DATED AND SIGNED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-03 Cont ID  
Sent By mawillia Date 2008-06-03 Time 13:30 Rev Time 0.00
Received By mawillia Date 2008-06-03 Time 12:46 Sent To  
Notes
2008-06-03 13:30:08*****APPROVED*****
  
 PLAN SHEETSA.1, A.2, AND E.2 WERE STAMPED, INTIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-30 Cont ID  
Sent By mwennerg Date 2008-04-30 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2008-04-30 Time 14:30 Sent To  
Notes
2008-04-30 14:34:53***DENIED***
  
 1) PLANS APPEAR TO BE CODE COMPLIANT. PROJECT DATA
 INDICATES THAT THE BUILDING IS PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM, HOWEVER SPRINKLER
 NOTES SHOW NOT APPLICABLE. IF FIRE SPRINKLER SYSTEM IS
 PROVIDED, PLEASE SHOW SPRINKLER LAYOUT. ADDITIONALLY,
 SEPARATE SHOP DRAWINGS AND PERMIT ARE REQUIRED FOR
 REMODEL. IF SPRINKLER SYSTEM IS NOT PART OF THIS
 PROJECT, PLEASE REMOVE REFERENCE FROM PROJECT DATA.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 09:54 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 09:53 Sent To P
Notes
2008-06-09 09:54:19TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-29 Cont ID  
Sent By adarroug Date 2008-05-29 Time 10:42 Rev Time 0.00
Received By adarroug Date 2008-05-29 Time 10:42 Sent To  
Notes
2008-05-29 10:42:30TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-05-03 Time   Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 11:01 Sent To  
Notes
2008-04-24 11:01:30TO "BOB"#16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-04-25 Cont ID  
Sent By tgordon Date 2008-04-25 Time 11:50 Rev Time 0.30
Received By tgordon Date 2008-04-25 Time 11:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-09 Cont ID  
Sent By mperson Date 2008-06-09 Time 14:19 Rev Time 0.00
Received By mperson Date 2008-06-09 Time 14:19 Sent To I
Notes
2008-06-09 14:31:49NOTE: NEW A.1 SHEET SUBMITTED THAT NEEDS FIRE AND BLDG
 REVIEW, THIS NEEDS TO BE ON"BOB BOARD".

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-03 Cont ID  
Sent By mperson Date 2008-06-03 Time 10:45 Rev Time 0.00
Received By mperson Date 2008-06-03 Time 10:45 Sent To  
Notes
2008-06-03 11:30:26PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. SHEET P.1 SANITARY RISER DIAGRAM AND PLUMBING PLAN:
 FIXTURE SK-1 MUST DRAIN DOWNSTREAM OF THE WET VENTED
 BATHROOM GROUP IN ROOM #103. PER FBC-2004 PLUMBING
 SECTION 909.1 WET VENT PERMITTED.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED SHEET P.1
 STILL INDICATES FIXTURE SK-1 DRAINING INTO THE WET
 VENTED BATHROOM GROUP (WATER CLOSET AND LAVATORY) OF
 RESTROOM #2. FIXTURE SK-1 NEEDS TO DRAIN DOWNSTREAM OF
 THE WET VENTED BATHROOM. PER FBC-2004 PLUMBING SECTION
 909.1 WET VENT PERMITTED.
  
 2. SHEET A.1 AND P.1 PLEASE CLARIFY IF SINK SK-1 IS A
 WORK RELATED SINK OR IS THIS SINK FOR A BREAK AREA? IF
 THIS SINK IS FOR A BREAK AREA PLEASE PROVIDE THE
 FOLLOWING PER FBC FLORIDA ACCESSIBILITY CODE CHAPTER 11
 SECTIONS 11-4.24.1 THRU 11-4.24.6. WITH AN ELEVATION
 DETAIL. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 106.1.2 ADDITIONAL DATA.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED DETAIL ON
 SHEET A.1 DETAIL 3/A.1 DOES NOT CLEARLY INDICATE THE
 FOLLOWING. THE CLEAR FLOOR SPACE NEEDS TO BE INDICATED
 ON THE FLOOR PLAN ON SHEET A.1.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 3. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By mperson Date 2008-04-29 Time 16:27 Rev Time 0.00
Received By mperson Date 2008-04-28 Time 16:27 Sent To  
Notes
2008-04-28 16:59:32PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P.1 SANITARY RISER DIAGRAM AND PLUMBING PLAN:
 FIXTURE SK-1 MUST DRAIN DOWNSTREAM OF THE WET VENTED
 BATHROOM GROUP IN ROOM #103. PER FBC-2004 PLUMBING
 SECTION 909.1 WET VENT PERMITTED.
  
 2. SHEET A.1 AND P.1 PLEASE CLARIFY IF SINK SK-1 IS A
 WORK RELATED SINK OR IS THIS SINK FOR A BREAK AREA? IF
 THIS SINK IS FOR A BREAK AREA PLEASE PROVIDE THE
 FOLLOWING PER FBC FLORIDA ACCESSIBILITY CODE CHAPTER 11
 SECTIONS 11-4.24.1 THRU 11-4.24.6. WITH AN ELEVATION
 DETAIL. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 106.1.2 ADDITIONAL DATA.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR THE COLD WATER
 INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF
 THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER (CLEARLY
 INDCATE EXISTING) **608, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-24 Cont ID  
Sent By choops Date 2008-04-24 Time 11:05 Rev Time 0.00
Received By choops Date 2008-04-24 Time 11:05 Sent To  
Notes
2008-04-24 11:05:47*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.