| Notes |
| 2008-04-23 07:36:36 | 2004 FBC W/2007 REVISIONS | | | REPLACE WINDOWS IN HIGH RISE | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT SIGNED AND SEALED ENGINEERED CALCULATIONS | | | USING ASCE 7-02 FOR THE COMPONENT AND CLADDING | | | PRESSURES FOR THE WINDOWS. THE BUILDING IS A HIGH RISE | | | APPROXIMATELY 19 STORIES AND 200 FEET IN HEIGHT LOCATED | | | IN EXPOSURE CATEGORY C WITH A BASIC WIND SPEED OF | | | 140MPH . INDICATE THE LOCATION OF THE OPENINGS IN | | | REGARDS TO INTERIOR AND EDGE ZONES. | | | | | | 2) CIRCLE THE APPROPRIATE WINDOWS AND MULLIONS AND | | | THEIR DESIGN PRESSURES THAT WILL BE INSTALLED ON THE | | | TABLES LOCATED IN THE PRODUCT APPROVALS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
|