| 2008-04-28 11:45:28 | 2004 FBC W/2007 REVISIONS |
| | ENCLOSE CARPORT |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. HAVE BOTH SETS |
| | OF THE PLANS STAMPED BY PALM BEACH COUNTY FOR IMPACT |
| | FEES. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R SECTION 704 INSPECTION |
| | FOR TERMITES ON THE PLANS. IN ORDER TO PROVIDE FOR |
| | INSPECTION FOR TERMITE INFESTATION, CLEARANCE BETWEEN |
| | EXTERIOR WALL COVERINGS AND FINAL EARTH GRADE ON THE |
| | EXTERIOR OF A BUILDING SHALL NOT BE LESS THAN 6 INCHES |
| | (152 MM). |
| | |
| | 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE. |
| | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| | ELSEWHERE. |
| | |
| | 5) SHOW COMPLIANCE WITH R506.2.3 VAPOR RETARDER. |
| | A 6 MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED |
| | VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6 |
| | INCHES (152 MM) SHALL BE PLACED BETWEEN THE CONCRETE |
| | FLOOR SLAB AND THE BASE COURSE OR THE PREPARED SUBGRADE |
| | WHERE NO BASE COURSE EXISTS. |
| | |
| | 6) SPECIFY HOW THE TOP PLATE OF THE FRAME WALLS WILL BE |
| | ATTACHED TO THE EXISTING CONCRETE LINTELS. 2004 FBC |
| | 106.1.2* CITY AMENDMENTS. |
| | |
| | 7) SPECIFY THE SIZE AND LENGTH OF THE TAP CONS THAT |
| | WERE SPECIFIED TO ATTACH THE NEW WALLS TO THE EXISTING |
| | WALLS. 2004 FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 8) SHOW THE DIFFERENCE IN FINAL FLOOR GRADES ON THE |
| | PLANS BETWEEN THE EXISTING HOUSE AND THE ENCLOSED |
| | CARPORT. 2004 FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 9) PROVIDE DETAILS FOR THE NEW STAIRS. SPECIFY THE RISE |
| | AND RUN, MATERIALS, ETC. OF STAIRS. SHOW COMPLIANCE |
| | WITH R311.5. |
| | |
| | 10) PROVIDE DETAILS FOR GUARDS IF REQUIRED. SEE R312. |
| | |
| | 11)THE EXISTING MASONRY WALLS OF THE ENCLOSED CARPORT |
| | ARE REQUIRED TO BE INSULATED TO A MINIMUM OF R-5 PER |
| | FBC 13-600. REVISE ENERGY CALCULATION FORMS. |
| | |
| | 12) THERE ARE NOT ANY ADJACENT WALLS SHOWN ON THE |
| | PLANS. SEE FBC 13-2 FOR DEFINITION OF ADJACENT WALL IN |
| | TERMS OF ENERGY EFFICIENCY. REVISE ENERGY CALULATION |
| | FORMS. |
| | |
| | 13) THE CEILING TYPE IS INCORRECTLY SPECIFIED AS SINGLE |
| | ASSEMBLY ON THE ENERGY CALCULATION FORMS. THE CEILING |
| | TYPE IS UNDER ATTIC AND THE INSULATION IS REQUIRED TO |
| | BE R-30. PLEASE CORRECT ENERGY FORMS. |
| | |
| | 14) SPECIFY THE CEILING HEIGHT ON THE WALL SECTION ON |
| | THE PLANS FOR THE ENCLOSED CARPORT. 2004 FBC 106.1.2* |
| | CITY AMENDMENTS. |
| | |
| | 15) SPECIFY THE EXISTING CONDITIONED FLOOR AREA AND THE |
| | ADDITIONAL CONDITIONED FLOOR AREA OF THE ENCLOSED |
| | CARPORT ON THE PLANS. 2004 FBC 106.1.1* CITY |
| | AMENDMENTS. |
| | |