| 2008-04-26 08:55:48 | BUILDING PLAN REVIEW |
| | PERMIT: 08040567 |
| | ADD: 2455 SAILFISH COVE DR. |
| | CONT: VINCE LUCAS TRADE MASTER INC. |
| | TEL: (561)493-5011 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4-26-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC RESIDENTIAL WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4)SPECIFY THE APPLICABLE BUILDING CODE AND THE DESIGN |
| | CRITERIA ON THE PLANS. STATE THE BASIC WIND SPEED, THE |
| | EXPOSURE CATEGORY, COMPONENT AND CLADDING PRESSURES FOR |
| | THE DOOR OPENING. SEE R301 FOR MORE INFORMATION. |
| | |
| | 5)PROVIDE THE FASTENING DETAIL FOR THE DOOR BUCK PER |
| | R613.6 AND FBC 106.1.2*. |
| | |
| | 6)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 7)THE PRODUCT APPROVAL FOR THE DOOR SHALL INDICATE |
| | WHICH DOOR WILL BE USED; INDICATE THE DOOR BY CIRCLING |
| | THE ITEM FROM THE PRODUCT APPROVAL. THE DOOR IS |
| | NON-IMPACT; THEREFORE IMPACT PROTECTION WILL BE |
| | REQUIRED. SUBMIT TWO COPIES OF PRODUCT APPROVAL FOR THE |
| | IMPACT APPROVAL. IDENTIFY FROM THE PRODUCT APPROVAL |
| | WHICH SYSTEM WILL BE USED INCLUDING THE FASTENER |
| | SPACING AND THE TYPE OF CONNECTION. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY DCA RYLE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL. FBC 106.3* |
| | |
| | 8)FBC 106.1.1* SPECIFY THE TYPE OF ROOM THE ENCLOSE |
| | PORCH WILL BE ON THE PLANS. THE ENCLOSURE OF THE PORCH |
| | SHALL NOT AFFECT THE EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS OF ANY SLEEPING ROOM AS REQUIRED BY R310. |
| | |
| | 9)R703THE EXTERIOR WALL SECTION SHALL SPECIFY IF |
| | INSULATION WILL BE INSTALLED IN THE NEW WALLS, AND IF |
| | SO, STATE THE R-VALUE OF THE INSULATION. THE DRAWINGS |
| | DO NOT SHOW ANY WEATHER- RESISTANT SHEATHING PAPER FOR |
| | THE PREVENTION OF MOISTURE OR WATER INTRUSION. THE |
| | EXTERIOR WALL ENVELOPE SHALL BE CONSTRUCTED TO PREVENT |
| | THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY |
| | PROVIDING A WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR |
| | VENEER. SEE R703.2. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |