| 2008-05-14 10:26:27 | GAS PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS GAS PLAN REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | NOTE: DESIGNER'S REPONSES WERE ON THE RESUBMITTAL |
| | FORM. |
| | |
| | 1. "OK" COMMENT ADDRESSED. |
| | |
| | 2. "OK" COMMENT ADDRESSED. |
| | |
| | 3. "OK" COMMENT ADDRESSED. |
| | |
| | 4. NOTE: THE SUBMITTED MANUFACTURER SHEETS FOR THE GAS |
| | REFRIGERATOR/FREEZER ARE FOR PROPANE GAS HOWEVER THE |
| | SUBMITTED GAS DRAWINGS ARE INDICATING NATURAL GAS. |
| | PLEASE CLARIFY. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | **RESPONSE NOTED AS WELL AS INVOICE FROM ERVIN'S |
| | CABINET SHOP INDICATING THAT A NATURAL GAS KIT WAS |
| | INSTALLED IN THE CRYSTAL COLD PROPANE REF., HOWEVER THE |
| | RESUBMITTED MANUFACTURER'S SHEET DO NOT INDICATE A |
| | LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY |
| | THAT THE CONVERSION KIT FROM PROPANE GAS TO NATURAL GAS |
| | IS APPROVED. THE CSA LISTING ON THE SUBMITTED |
| | MANUFACTURER SHEET IS FOR PROPANE GAS ONLY. PLEASE |
| | PROVIDE THIS REQUIRED INFORMATION FROM THE MANUFACTURER |
| | INDICATING THE CONVERSION KIT FROM PROPANE TO NATURAL |
| | GAS IS APPROVED FOR THIS APPLIANCE. PER STANDARDS NFPA |
| | 54, NFPA 58 AND FBC-2004 FUEL GAS SECTION 301.3 LISTED |
| | AND LABELED. |
| | |
| | 5. VALUE FOR THE JOB IS TO LOW. JOB MUST INCLUDE THE |
| | PRICE OF THE GAS REFRIGERATOR/FREEZER. PLEASE SEE A |
| | COPY OF THE APPLIANCE PRICE FROM AN ONLINE SEARCH |
| | INDICATING THE PRICE AS $2363.00 ATTACHED TO THESE |
| | COMMENTS. PLEASE ADJUST THE VALUE AND PAY THE |
| | DIFFERENCE BEFORE RESUBMITTING. |
| | PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | **RESPONSE NOTED, HOWEVER THE VALUE IS THE TOTAL COST |
| | INCLUDING THE PRICE OF THE NEW APPLIANCE. THE VALUE ON |
| | THE PERMIT APPLICATION NEEDS TO BE ADJUSTED TO $3563.00 |
| | AND THE DIFFERENCE PAID BEFORE BEING RESUBMITTED FOR |
| | PLAN REVIEW. PER (W.P.B. AS AMMENDED) SECTION 108.3. |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS** |
| | |
| | 6.PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT |
| | IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE - |
| | 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY., BEFORE A |
| | PERMIT CAN BE ISSUED. PER FS 713.13 (2): IF THE |
| | IMPROVEMENT DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS VOID AND OF NO |
| | FURTHER EFFECT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |