Plan Review Details - Permit 08040545
Plan Review Stops For Permit 08040545
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-04-28 Cont ID  
Sent By mperson Date 2008-04-28 Time 14:12 Rev Time 0.00
Received By mperson Date 2008-04-28 Time 14:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By mperson Date 2008-04-21 Time 15:47 Rev Time 0.00
Received By mperson Date 2008-04-21 Time 15:47 Sent To PC
Notes
2008-04-21 16:15:35GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PERMIT APPLICATION STATES "ADD LINE TO TANKLESS
 W-HTR. AND W-HTR". THIS DOES NOT MAKES ANY SENSE,
 PLEASE CLEARLY INDICATE AND CLARIFY WHAT THE SCOPE OF
 WORK IS ON THE GAS PERMIT APPLICATION. PER (W.P.B.)
 SECTION 105 PERMITS.
  
 2. NOT ALL CORRESPONDING LENGTHS ARE INDICATED FOR ALL
 CUT SECTIONS OF PIPE. REFERENCE THE RED CIRCLED YELLOW
 HIGH LIGHTED CUT SECTIONS AND COMPLY. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 3. THE LONGEST LENGTH IS BEING INDICATED WRONG AS 40'.
 THE ADDED SUM OF THE INDICATED CORRESPONDING LENGTHS OF
 CUT SECTIONS OF PIPE IS 44'. AND THAT NOT ADDING WHAT
 IS BEING ASKED FOR IN COMMENT #1 AND THE GAS PIPING IS
 NOT SIZED RIGHT. PER FBC FUEL GAS SECTION 401.1 SCOPE
 AND TABLE 402.4(2). REFERENCE TABLE 402.4(2) ATTACHED
 TO THESE COMMENTS INDCATING THIS.
  
 4. NOTE: THE SUBMITTED EXISTING GAS SYSTEM DOES NOT
 REFLECT THE CLOSED GAS PERMIT #07010575 WHICH WAS
 FINALED 6/4/07. THAT PERMIT HAD A POOL/HTR., LOG/SET,
 COOKTOP, BBQ GRILL, WATER/HTR AND COLUMN LIGHTS. PLEASE
 KNOW THAT PERMIT DID NOT HAVE A DRYER AND THE BBQ HAD A
 REVISION INDICATING IT AS A FUTURE APPLIANCE. PLEASE
 REFERENCE THE ATTACHED GAS PERMIT INFORMATION OF SAID
 ADDRESS INDICATING THIS. PLEASE CLEARLY INDICATE THE
 CORRECT EXISTING GAS SYSTEM'S BTU LOAD AND LONGEST
 LENGTH. PER (W.P.B.) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND FBC FUEL GAS SECTION 401.1
 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-28 Cont ID  
Sent By mperson Date 2008-04-28 Time 14:13 Rev Time 0.00
Received By mperson Date 2008-04-25 Time 14:12 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-21 Cont ID  
Sent By mperson Date 2008-04-21 Time 16:15 Rev Time 0.00
Received By mperson Date 2008-04-21 Time 15:44 Sent To  
Notes
***NONE***