Plan Review Details - Permit 08040541
Plan Review Stops For Permit 08040541
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-09 Cont ID  
Sent By mjacobs Date 2008-06-09 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2008-06-09 Time 13:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-29 Cont ID  
Sent By mjacobs Date 2008-05-29 Time 11:36 Rev Time 0.00
Received By mjacobs Date 2008-05-29 Time 11:02 Sent To PC
Notes
2008-05-29 11:36:21BUILDING PLAN REVIEW
 PERMIT: 08040541
 ADD: 1900 CONSULATE PLACE #403
 CONT: SAARI CONSTRUCTION INC.
 TEL: (561)588-0720
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REV.
 ACTION: DENIED
  
 1)INDICATE ON THE PLANS THE HEIGHT OF THE NEW FURRED
 CEILING IN BOTH AREAS WHERE IT WILL BE CONSTRUCTED. ANY
 ROOM WITH A FURRED CEILING SHALL BE REQUIRED TO HAVE A
 MINIMUM HEIGHT 7 FEET FBC 1208.1. PLEASE ALSO SEE FBC
 SECTION 1208 FOR MORE INFORMATION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-05 Cont ID  
Sent By mjacobs Date 2008-05-05 Time 12:29 Rev Time 0.00
Received By mjacobs Date 2008-05-05 Time 11:54 Sent To PC
Notes
2008-05-05 12:29:04 
 PROVISOR:
 712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN
 APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED
 AND TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479,
 WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01
 INCH OF WATER. THE SYSTEM SHALL HAVE AN F RATING AND A
 T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED. PLEASE
 INDICATE THE UL ASSEMBLY NUMBER FOR THE FLOOR
 PENETRATION WHERE THE PLUMBING PIPES WILL BE REMOVED
 AND CAPED. WHERE ANY PIPES ARE REMOVED FROM THE FLOOR
 CEILING/ASSEMBLY, THE HOLES SHALL BE SEALED WITH A UL
 ASSEMBLY WHICH SHALL MAINTAIN THE FLOOR RATING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-29 Cont ID  
Sent By mjacobs Date 2008-04-29 Time 13:00 Rev Time 0.00
Received By mjacobs Date 2008-04-29 Time 08:17 Sent To PC
Notes
2008-04-29 13:00:23BUILDING PLAN REVIEW
 PERMIT: 08040541
 ADD: 1900 CONSULATE PLACE #406
 CONT: SAARI CONSTRUCTION INC.
 TEL: (561)588-0720
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-29-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 THE DESIGN PROFESSIONAL OR AN OWNER MUST ELECT
 ONE OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT
 TO SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)THE CONTRACTOR ON THE PERMIT APPLICATION IS A CBC
 CONTRACTOR WHO IS NOT ALLOWED TO DO ANY WORK PERTAINING
 TO THE STRUCTURAL WALLS OF THE BUILDING. A CERTIFIED
 GENERAL CONTRACTOR OR A CERTIFIED FIREPROOFING COMPANY
 SHALL APPLY FOR A SEPARATE APPLICATION TO SEAL ALL
 FLOOR/CEILING PENETRATIONS.
  
 4)712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED
 BY AN APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM
 INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR
 UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL
 OF 0.01 INCH OF WATER. THE SYSTEM SHALL HAVE AN F
 RATING AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT
 LESS THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
 PLEASE INDICATE THE UL ASSEMBLY NUMBER FOR THE FLOOR
 PENETRATION WHERE THE PLUMBING PIPES WILL BE REMOVED
 AND CAPED. WHERE ANY PIPES ARE REMOVED FROM THE FLOOR
 CEILING/ASSEMBLY, THE HOLES SHALL BE SEALED WITH A UL
 ASSEMBLY WHICH SHALL MAINTAIN THE FLOOR RATING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-05 Cont ID  
Sent By btrobaug Date 2008-06-05 Time 14:16 Rev Time 0.00
Received By btrobaug Date 2008-06-05 Time 14:16 Sent To  
Notes
2008-06-05 14:17:32 
  
  
 FILE COPY WITH THE REVISION IN BIN #9./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-21 Cont ID  
Sent By btrobaug Date 2008-05-21 Time 16:27 Rev Time 0.00
Received By btrobaug Date 2008-05-21 Time 15:39 Sent To B
Notes
2008-05-21 15:59:34 
  
  
 REVISION DENIED
  
 1} THE REVISION SUBMITTED INDICATES A COMPLETE REWIRE
 OF THE UNIT, IF NOT DIFFERENTIATE NEW FROM EXISTING.
  
 2} THE VALUE MUST INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS AMENDED.ADJUST THE VALUE
 TO INCLUDE ALL ADDED WORK UNDER THIS REVISION AT THE
 PERMIT CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING.
  
 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEE
 COUNTERTOP ADJACENT TO THE "REF/FRZ".\
  
 4} INDICATE IF THE FLOOR RECEPTACLE IN BEDROOM #2 IS
 NEW OR EXISTING. IF NEW THE FLOOR MUST BE X-RAYED PRIOR
 TO MAKING ANY CUTS AND AN ENGINEER MUST VERIFY THE
 INSTALLATION WILL NOT WEAKEN THE STRUCTURAL INTEGRITY
 OR RATING OF THE FLOOR. INDICATE HOW THIS OUTLET WILL
 BE FED, AND FROM WHERE.
  
 PROVIDE A WRITTEN RESPONSE, PROVIDE ONE COPY OF THE
 OLD PLANS WHEN RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-21 Cont ID  
Sent By btrobaug Date 2008-04-21 Time 13:31 Rev Time 0.00
Received By btrobaug Date 2008-04-21 Time 13:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-04-28 Cont ID  
Sent By mwennerg Date 2008-04-28 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2008-04-28 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 10:43 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 10:43 Sent To E
Notes
2008-06-04 10:43:41TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 09:00 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 09:00 Sent To B
Notes
2008-05-20 09:01:13TO "MJACOB" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 14:11 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 14:11 Sent To B
Notes
2008-04-30 14:11:51TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-04-29 Time   Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 12:40 Sent To  
Notes
2008-04-21 12:42:22TO "BOB"#2

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-04-22 Cont ID  
Sent By mperson Date 2008-04-22 Time 16:09 Rev Time 0.00
Received By mperson Date 2008-04-22 Time 16:09 Sent To  
Notes
2008-04-22 16:10:42******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-24 Cont ID  
Sent By choops Date 2008-04-24 Time 11:01 Rev Time 0.00
Received By choops Date 2008-04-24 Time 11:01 Sent To  
Notes
2008-04-24 11:01:25*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.