Plan Review Details - Permit 08040527
Plan Review Stops For Permit 08040527
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By shill Date 2008-04-28 Time 10:27 Rev Time 0.00
Received By shill Date 2008-04-28 Time 10:27 Sent To  
Notes
2008-04-28 10:38:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 2.SEE FBC R 4101.17.ENGINEER SPECIFICIES A CODE
 SECTION, BUT SHOULD PROVIDE DESIGN CRITERIA ON THE PLAN
 (EITHER SPECIFIC TO THIS JOB OR A GENERAL NOTE).
  
 3.IN THE AREA OVER 5' DEEP, SHOW HOW THIS JOB WILL
 COMPLY WITH FBC4101.18.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By btrobaug Date 2008-04-21 Time 15:23 Rev Time 0.00
Received By btrobaug Date 2008-04-21 Time 14:55 Sent To P
Notes
2008-04-21 15:23:05 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} PROVIDE A SCHEMATIC OF THE POOL WIRING AND
 EQUIPMENT.
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.INDICATE THE RATING OF THE EXISTING SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-04-23 Cont ID  
Sent By mperson Date 2008-04-23 Time 15:35 Rev Time 0.00
Received By mperson Date 2008-04-23 Time 15:35 Sent To B
Notes
2008-04-23 15:38:16NOTE: POOL HAS BOTH AN ELECTRIC HEAT PUMP AND A GAS
 POOL HEATER.
  
 CONTRACTOR INFORMATION ONLY
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-04-18 Cont ID  
Sent By swurafti Date 2008-04-18 Time 14:40 Rev Time 0.00
Received By swurafti Date 2008-04-18 Time 14:40 Sent To  
Notes
2008-04-18 14:40:34HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-28 Cont ID  
Sent By shill Date 2008-04-28 Time 10:38 Rev Time 0.00
Received By shill Date 2008-04-18 Time 16:38 Sent To  
Notes
2008-04-18 16:38:36TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-23 Cont ID  
Sent By mperson Date 2008-04-23 Time 15:26 Rev Time 0.00
Received By mperson Date 2008-04-23 Time 15:26 Sent To G
Notes
2008-04-23 15:35:29PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1) FBC-2004 SEC. 424.2.7.1, OR FBCR-2004 SEC.R4101.7.1
 POOL CIRCULATING PUMPS
 SHALL BE EQUIPPED ON THE INLET SIDE WITH
 AN APPROVED TYPE HAIR AND LINT STRAINER
 WHEN USED WITH A PRESSURE FILTER.
 (DETAIL, MANUFACTURE SPEC SHEET OR ADD TO NOTES)
  
 2) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 *THE MANUFACTURER'S SPEC SHEET FOR THE HEAT PUMP ARE
 NOT INDICATING A LISTING AND AN ONLINE SEARCH BY THIS
 PLAN REVIEWER FAILED TO FIND ONE AS WELL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By choops Date 2008-04-21 Time 08:48 Rev Time 0.00
Received By choops Date 2008-04-21 Time 08:48 Sent To E
Notes
2008-04-21 09:01:31***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS OF ALL PROPOSED
 IMPROVEMENTS FROM WATERS' EDGE TO PROPERTY LINES.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 3)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720