Plan Review Details - Permit 08040517
Plan Review Stops For Permit 08040517
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-01 Cont ID  
Sent By shill Date 2008-08-01 Time 14:01 Rev Time 0.00
Received By shill Date 2008-08-01 Time 14:01 Sent To  
Notes
2008-08-01 14:24:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THIS IS A PLAN REVIEW ONLY.A PERMIT APPLICATION
 SIGNED BY A CONTRACTOR LICENSED TO PERFORM THE WORK IS
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 2.THE SHELL BUILDING HAS NOT BEEN ISSUED; THIS IS
 REQUIRED FOR A TENANT BUILD OUT PERMIT.
  
 3.THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE
 OF COMPLETION; IF THE CONTRACTOR FOR THIS TENANT SPACE
 IS DIFFERENT FROM THE BASE BUILDING, THEN A LETTER FROM
 THE BASE BUILDING CONTRACTOR ALLOWING THE TENANT
 BUILDOUT CONTRACTOR TO START WORK ON THIS TENANT SPACE
 BEFORE THE C OF C FOR THE BASE BUILDING HAS BEEN ISSUED
 WILL BE REQUIRED.THE DEVELOPER AND BOTH CONTRACTORS
 WILL BE REQUIRED TO SUBMIT A LETTER STATING THAT THEY
 UNDERSTAND THAT ANY DISPUTE OVER RESPONSIBILITY DOES
 NOT RELIEVE THEM FROM THE JOINT RESPONSIBILITY TO
 COMPLY WITH THE BUILDING CODE.
  
 2ND REVIEW, AS A COFC HAS NOT BEEN ISSUED FOR THE BASE
 BUILDING, A REVIEW OF THE PROPOSED TENANT BUILDOUT BY
 THE BASE BUILDING DESIGNER IS REQUIRED.COMPLIANCE CAN
 BE SHOWN BY EITHER A LETTER FROM THE BASE BUILDING
 DESIGNER OR WITH SHOP DRAWING REVEIW STAMPS ON THE
 PLANS.
  
 4-7.)ADDRESSED.
  
 8. THE ARCHITECT'S TITLE BLOCK STATES THAT THE
 PROFESSIONAL OF RECORD IS PRACTICING AS AN INDIVIDUAL.
 ALL INFORMATION REQUIRED BY FAC61G1-15 IS REQUIRED ON
 EACH SHEET (TITLE BLOCK INFORMATION).A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IF CASCO IS PRACTICING
 ARCHITECTURE IN FLORIDA, FS481.
  
 2ND REVEW, THE COMPANY NAME WAS REMOVED FROM THE PLAN
 AND THE RESPONSE LETTER STATES: "WE UNDERSTAND THAT A
 CERTIFICATE OF AUTHORIZATION IS NOT REQUIRED FOR A
 PROFESSIONAL OF RECORD PRACTICING AS AN INDIVIDUAL."
 THIS IS CORRECT; HOWEVER, BASED ON THE COMPANY'S
 WEBSITE AND ON PLANS SUBMITTED FIRST REVIEW, THE
 COMPANY IS PRACTICING ARCHITECTURE AND ENGINEERING IN
 FLORIDA.THEREFORE, A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED FOR BOTH ENGINEERING AND ARCHITECTURE.PLEASE
 APPLY AS REQUIRED BY FS481 AND FS471.IF THE DESIGN
 PROFESSIONAL DISAGREES, PLEASE CONTACT FBPE AND THE
 ATTORNEY FOR FLORIDA BOARD OF ARCHITECTS TO DISCUSS.
 850-521-0500, 850-893-4105.IF I AM INCORRECT, MY
 APOLOGIES, AND PLEASE GET THE NAME AND TELEPHONE NUMBER
 OF THE INDIVIDUAL WITH WHOM YOU SPOKE.A SET HAS BEEN
 RETAINED.PLEASE NOTE THAT THIS PERMIT WILL NOT BE
 DELAYED OVER THIS ISSUE.
  
 9-14.)ADDRESSED.
  
 NEW COMMENT:
  
 15.) CONDIMENT CART SHOPS TO BE SUBMITTED PRIOR TO
 INSTALLATION, FBC11-5.2.
  
 16.)A HOLD HAS BEEN PLACED ON THIS PARCEL BY
 ADDRESSING DEPARTMENT.PLEASE CONTACT LILI URSU,
 561-822-1239.PLANS AND THE APPLICATION MUST MATCH THE
 ASSIGNED ADDRESS (IF NECESSARY, MAY BE CHANGED BY HAND,
 NEW SHEETS NOT REQUIRED).
  
 17.)INFORMATIONAL; ADDITIONAL FEES WILL BE DUE ON
 PERMIT APPLICATION (FIRE, VALUE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-07 Cont ID  
Sent By shill Date 2008-05-07 Time 14:40 Rev Time 0.00
Received By shill Date 2008-05-05 Time 17:57 Sent To  
Notes
2008-05-07 14:42:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THIS IS A PLAN REVIEW ONLY.A PERMIT APPLICATION
 SIGNED BY A CONTRACTOR LICENSED TO PERFORM THE WORK IS
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 2.THE SHELL BUILDING HAS NOT BEEN ISSUED; THIS IS
 REQUIRED FOR A TENANT BUILD OUT PERMIT.
  
 3.THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE
 OF COMPLETION; IF THE CONTRACTOR FOR THIS TENANT SPACE
 IS DIFFERENT FROM THE BASE BUILDING, THEN A LETTER FROM
 THE BASE BUILDING CONTRACTOR ALLOWING THE TENANT
 BUILDOUT CONTRACTOR TO START WORK ON THIS TENANT SPACE
 BEFORE THE C OF C FOR THE BASE BUILDING HAS BEEN ISSUED
 WILL BE REQUIRED.THE DEVELOPER AND BOTH CONTRACTORS
 WILL BE REQUIRED TO SUBMIT A LETTER STATING THAT THEY
 UNDERSTAND THAT ANY DISPUTE OVER RESPONSIBILITY DOES
 NOT RELIEVE THEM FROM THE JOINT RESPONSIBILITY TO
 COMPLY WITH THE BUILDING CODE.
  
 4. G1.0, GOVERNING CODE IS TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.WWW.FLORIDABUILDING.ORG
  
 5. SHOW MANEUVERING CLEARANCE REQUIRED, PULL SIDE,
 MEN?S RESTROOM, FBC FIGURE 11-25.
  
 6. SEE ATTACHED PARKING DETAIL; PLEASE REVISE PLAN.
 C1.1.
  
 7. DECLARE TOTAL NUMBER OF PARKING SPACES AND TOTAL
 NUMBER OF ACCESSIBLE SPACES, FBC11-4.1.2(5).
  
 8. THE ARCHITECT?S TITLE BLOCK STATES THAT THE
 PROFESSIONAL OF RECORD IS PRACTICING AS AN INDIVIDUAL.
 ALL INFORMATION REQUIRED BY FAC61G1-15 IS REQUIRED ON
 EACH SHEET (TITLE BLOCK INFORMATION).A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IF CASCO IS PRACTICING
 ARCHITECTURE IN FLORIDA, FS481.
  
 9. THE ARCHITECT?S SIGNATURE IS TO BE AN ORIGINAL,
 FS481, PER FLORIDA BOARD OF ARCHITECTS.
  
 10. PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 11. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 12. SEPARATE PERMITS WILL BE REQUIRED FOR SIGNS,
 AWNINGS, ETC.INFORMATIONAL ONLY.
  
 13. C1.1 SHOWS A DRIVE THROUGH WINDOW.IS THIS
 INCLUDED ON THE SHELL PERMIT OR IN THIS PERMIT?
 PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL IF
 APPLICABLE.
  
 14. SHEET A6.0, SEE FBC FIGURE 11-29, 11-31, LAVATORY
 CLEARANCES, GRAB BARS AT WATER CLOSETS, AND REVISE
 DETAILS INCLUDING MIRROR, TOILET PAPER DISPENSER, .
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-07 Cont ID  
Sent By dpalmer Date 2008-07-07 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2008-07-07 Time 09:28 Sent To  
Notes
2008-07-07 09:28:47** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THAT SOME COMMENTS ARE THE SAME AS
 PREVIOUS REVIEW. THERE ARE ALSO SOME NEW COMMENTS DUE
 TO NEW DOCUMENTS WHICH WERE NOT SUBMITTED ON PREVIOUS
 REVIEW.
  
  
 **STARBUCKS BLD OUT.
  
 1) NOTE: ** SANE NOTE **
 PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT. EVEN
 ONCE PLANS ARE FOUND TO MEET THE FLORIDA BUILDING CODE
 AND OTHER APPLICABLE LAWS REVIEW WILL STILL NOT SHOW A
 *PASSES* STATUS UNTIL PERMIT IS APPLIED. REVIEW OF
 LICENSING ETC WILL BE REQUIRED AT THAT TIME.
  
 2) NOTE: ** SAME NOTE **
 PLEASE KNOW AS THE PERMIT FOR THE BASE SHELL BUILDING
 HAS NOT YET BEEN ISSUED, ONCE PLANS ARE FOUND TO BE
 CODE COMPLIANT ETC AND PERMIT IS APPLIED, PERMIT MAY
 NOT BE ISSUED UNTIL BASE BUILDING HAS BEEN ISSUED. **
 IMPORTANT** PLEASE KEEP IN MIND IF THE BUILD OUT PERMIT
 IS ISSUED THE BASE BUILDING PLANS WILL BE REQUIRED TO
 BE UPDATED TO SHOW ALL KNOWN UNDER BUILD OUT PLANS
 BEFORE FINALS.
  
 3) NOTE: ** SAME NOTE **
 PLEASE KNOW IF THE BASE BUILDING DOES NOT RECEIVE A
 CERTIFICATE OF COMPLETION BEFORE THE BUILD OUT PERMIT
 IS ISSUED THE PLANS WILL BE REQUIRED TO CONTAIN A
 *REVIEW STAMP* SUCH AS A SHOP DRAWING REVIEW STAMP FROM
 THE BASED BUILDING DESIGNERS ON EACH PAGE FROM THE BASE
 BUILDING DESIGNER FOR THAT TRADE. THE BASE BUILDING IS
 UNDER THE RESPONSIBILITY OF THE BASE BUILDING DESIGN
 TEAM UNTIL SUCH TIME THE C OF C HAS BEEN ISSUED.
 PLEASE ALSO KNOW THAT ALL ITEMS INCORPORATED INTO THE
 BUILD OUT SUCH AS LIGHTING, LOADS, ITEMS FOR ENERGY
 CALCULATIONS ETC WILL ALL BE REQUIRED TO BE REVISED AND
 SUBMITTED ON BASE BUILDING.
  
 ** THIS INFORMATION IS GIVEN AS INFORMATION ONLY AS THE
 BUILD OUT PERMIT IS NOT YET APPLIED FOR. ONCE APPLIED,
 PLEASE MUST BE STAMPED ETC OR PERMITS WILL NOT BE
 ISSUED AS NOTED ABOVE.
  
 4) NOTE: ** SAME NOTE**
 PLEASE ALSO KNOW IF THE BUILD OUT SCOPE OF WORK IS
 APPLIED FOR UNDER A DIFFERENT CONTRACTOR THAN THE BASE
 SHELL BUILDING A LETTER OF UNDERSTANDING WILL BE
 REQUIRED BETWEEN THE TWO CONTRACTORS. THIS IS TO AVOID
 CONFLICT IN THE INSPECTIONS, BUILDING ETC.
  
  
 5) NOTE: NOTES 1-4 OF THE PREVIOUS REVIEW ARE THE SAME.
 THE RESPONSE LETTER MENTIONS THE COMMENTS WERE
 UNDERSTOOD YET NONE OF THE ITEMS PREVIOUSLY NOTED WERE
 ACTUALLY ADDRESSED. AS STATED ON PREVIOUS REVIEW, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES REQUESTED THE
 SUBMISSION OF LIGHTING PERFORMANCE CALCULATIONS TO MEET
 FBC 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE SUBMITTED FLA-COM METHOD *C* CALCULATIONS ARE NOT
 COMPLETE. PLEASE SEE THE INPUT DATA REPORT WHICH IS
 REQUIRED TO BE PART OF THE CALCULATIONS WAS NOT
 SUBMITTED. PLEASE TAKE A LOOK AT SHEET 2 OF 7 WHICH
 SPECIFICALLY STATES THE INPUT DATA REPORT MUST BE
 INCLUDED.
 ** PLEASE SEE THE CERTIFICATION SHEET IS NOT SIGNED,
 DATED OR SEALED BY THE DESIGNER OF RECORD. IN FACT THE
 CERTIFICATION SHEET CONTAINS A PRINTED NAME OTHER THAN
 THE ENGINEER OF ARCHITECT RESPONSIBLE PER FBC 13-103.1,
 FS 471.025, FAC 61G15-23.002.
 THE SHEET WHICH WAS ATTACHED TO THE FRONT OF THE
 CALCULATIONS WHICH WAS SOME SORT OF COVER SHEET IS NOT
 ACCEPTABLE IN LIEU OF SIGNING AND SEALING SAID
 DOCUMENTS.
 ** PLEASE BE SURE ALL INFORMATION ON PLANS FOR SYSTEMS
 AND BUILDING COMPONENTS ARE PLACED INTO THE
 CALCULATIONS CORRECTLY. THE TOTAL WATTAGE AS SHOWN ON
 THE SUMMARY SHEETS OF 1204 IS NOT ACCURATE. THE
 LIGHTING ON SHEET E3.0 IS GREATER THAN SHOWN.
 PLEASE SEE OTHER COMPONENTS SUCH AS PIPING/ HOT WATER
 ETC WHICH WILL BE NOTED BY OTHER TRADES IS BLANK.
  
 7) NOTE: PLANS SHOW A NEW PANEL *C* YET PANEL IS BLANK.
 NO CIRCUITS FOR ANY SPECIFIC ELECTRICAL, NO LOAD ETC.
 PLEASE CLARIFY
 FBC 106.1.1 FOR CLARITY AND ADDITIONAL INFORMATION.
 NEC 408.4, 220, 310.16 ETC
  
  
 8) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.2, .1.3 AND .1.4.
 FOR EXAMPLE:
 PLEASE KNOW THE EXTERIOR LIGHTS SHALL MEET ONE OF TWO
 METHODS OF CONTROL PER 13-415.1.ABC.1.4. AT THIS TIME
 PLANS DO NOT INDICATE HOW THE DRIVE THRU LIGHTS ON
 CIRCUIT A-26 WILL MEET CODE.
 PLEASE KNOW THIS IS ONLY NOTED FOR ONE EXAMPLE AND IS
 NOT AN EXHAUSTED LIST.
 ** THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. THE
 RESPONSE LETTER FROM THE DESIGNER MENTIONS TO SEE THE
 NEW FLA-COM CALCULATIONS FOR COMPLIANCE. THE FLA-COM
 CALCULATIONS DO NOT HAVE ANYTHING TO DO WITH THE
 REQUIRED METHOD OF CONTROL FOR ALL OUTSIDE/EXTERIOR
 LIGHTING. ONCE AGAIN PLEASE SEE THE SECTION OF THE CODE
 ABOVE WITH RESPECT TO CONTROLS.
 THE DETAILS #9 AND #10 ON SHEET E4.0 STILL DOES NOT
 SHOW CIRCUIT A-26 AND ALSO DOES NOT INDICATE THE
 REQUIRED BACK UP FOR ANY ASTRONOMICAL TIME CLOCK.
  
 9) NOTE: PLEASE BE SURE PLANS COORDINATE WITH THE BASE
 BUILDING PLANS FOR DESIGN ETC
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By dpalmer Date 2008-04-28 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2008-04-28 Time 15:01 Sent To  
Notes
2008-04-28 15:04:40** DENIED **
  
 **STARBUCKS BLD OUT.
  
 1) NOTE: PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR
 PLAN REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
 EVEN ONCE PLANS ARE FOUND TO MEET THE FLORIDA BUILDING
 CODE AND OTHER APPLICABLE LAWS REVIEW WILL STILL NOT
 SHOW A *PASSES* STATUS UNTIL PERMIT IS APPLIED. REVIEW
 OF LICENSING ETC WILL BE REQUIRED AT THAT TIME.
  
 2) NOTE: PLEASE KNOW AS THE PERMIT FOR THE BASE SHELL
 BUILDING HAS NOT YET BEEN ISSUED, ONCE PLANS ARE FOUND
 TO BE CODE COMPLIANT ETC AND PERMIT IS APPLIED, PERMIT
 MAY NOT BE ISSUED UNTIL BASE BUILDING HAS BEEN ISSUED.
 ** IMPORTANT** PLEASE KEEP IN MIND IF THE BUILD OUT
 PERMIT IS ISSUED THE BASE BUILDING PLANS WILL BE
 REQUIRED TO BE UPDATED TO SHOW ALL KNOWN UNDER BUILD
 OUT PLANS BEFORE FINALS.
  
 3) NOTE: PLEASE KNOW IF THE BASE BUILDING DOES NOT
 RECEIVE A CERTIFICATE OF COMPLETION BEFORE THE BUILD
 OUT PERMIT IS ISSUED THE PLANS WILL BE REQUIRED TO
 CONTAIN A *REVIEW STAMP* SUCH AS A SHOP DRAWING REVIEW
 STAMP FROM THE BASED BUILDING DESIGNERS ON EACH PAGE
 FROM THE BASE BUILDING DESIGNER FOR THAT TRADE. THE
 BASE BUILDING IS UNDER THE RESPONSIBILITY OF THE BASE
 BUILDING DESIGN TEAM UNTIL SUCH TIME THE C OF C HAS
 BEEN ISSUED.
 PLEASE ALSO KNOW THAT ALL ITEMS INCORPORATED INTO THE
 BUILD OUT SUCH AS LIGHTING, LOADS, ITEMS FOR ENERGY
 CALCULATIONS ETC WILL ALL BE REQUIRED TO BE REVISED AND
 SUBMITTED ON BASE BUILDING.
  
 ** THIS INFORMATION IS GIVEN AS INFORMATION ONLY AS THE
 BUILD OUT PERMIT IS NOT YET APPLIED FOR. ONCE APPLIED,
 PLEASE MUST BE STAMPED ETC OR PERMITS WILL NOT BE
 ISSUED AS NOTED ABOVE.
  
 4) NOTE: PLEASE ALSO KNOW IF THE BUILD OUT SCOPE OF
 WORK IS APPLIED FOR UNDER A DIFFERENT CONTRACTOR THAN
 THE BASE SHELL BUILDING A LETTER OF UNDERSTANDING WILL
 BE REQUIRED BETWEEN THE TWO CONTRACTORS. THIS IS TO
 AVOID CONFLICTS IN THE INSPECTIONS, BUILDING ETC.
  
 5) NOTE: PLEASE SEE THAT BOTH SETS OF PLANS ARE NOT
 SIGNED WITH ORIGINAL SIGNATURES FROM ANY DESIGNER. IN
 FACT BOTH THE ARCHITECTURAL AND MEP PLANS CONTAIN
 RAISED SEALS OVER DIGITAL SIGNATURES. THIS IS NOT
 PERMITTED UNDER FS 471.025, 481.221. THESE SHALLNOT
 BE *RUBBERSTAMPS*, *PHOTO-COPIES* ETCPLEASE ALSO SEE
 FLORIDA ADMINISTRATIVE CODES 61G15-23.002,
 61G1-16.004.
 PLEASE KNOW ONE COMPLETE SET OF PLANS WILL BE RETAINED
 AT THIS TIME. PLANS ARE REQUIRED TO CONTAIN ORIGINAL
 DATE, SIGNATURE AND RAISED SEAL. THIS NOTE IS FOR ALL
 TRADES AND ALL REVIEWS WHETHER OR NOT COMMENT IS MADE
 BY OTHER TRADE REVIEWER(S).
  
 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS. FOR EXAMPLE, THE SHEET G1.0 STATES THE 1999
 NATIONAL ELECTRICAL CODE. PLEASE KNOW THERE HAVE BEEN
 TWO CODE CHANGES SINCE THIS 1999 NFPA-70 HAS BEEN IN
 EFFECT. THE 1999 EDITION IN THE STATE OF FLORIDA WAS NO
 LONGER IN EFFECT AFTER JULY 2003. PLEASE SEE THE LIST
 BELOW.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 ** THESE ARE TO BE STATED ON ELECTRICAL PLANS AS WELL
 AS COVER SHEET. THE 2003 LS CODE IS ALREADY STATED ON
 G1.0.
  
 7) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR THE FIRM CASCO PER FLORIDA STATUTES 481.0219 AND
 471.023. MISSING REQUIRED CERTIFICATE OF AUTHORIZATION
 NUMBER FOR BOTH THE ARCHITECTURAL BUSINESS AND
 ENGINEERING BUSINESS.
 THIS IS REQUIRED FOR BOTH SERVICES BEING OFFERED.
 PLEASE ALSO KNOW THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADE WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 8) NOTE: PLEASE VERIFY LOADS AS THE PLANS ON E2.1 SHOWS
 A LOAD TOTAL OF 316.9 AMPS ON A PANEL *A* WHICH IS ONLY
 RATED 200AMPS.
 PLEASE VERIFY THE SERVICE AS NOTED ABOVE THESE PLANS
 SHOWS A 200AMP SERVICE ON SHEET E2.1 AND SHEET E4.0
 SHOWS AND MENTIONS 400AMP SERVICE. AS THESE DO NOT
 COORDINATE AND THE 200AMP SERVICE AS SHOWN ON E2.1 IS
 NOT SUFFICIENT THESE ITEMS WILL BE REQUIRED TO BE
 ADJUSTED TO MEET MINIMUM CODE COMPLIANCE.
 PLEASE ALSO SUBMIT LOAD CALCULATIONS ON PANEL *B* AS
 THE LOADS IS SHOWN AS 100AMPS ON A 100AMPS BREAKER.
 PLEASE PROVIDE MORE INFORMATION ON LOAD CALCULATIONS
 FOR AL EQUIPMENT. PLEASE VERIFY AND SHOW HEAT LOADS ON
 RT UNITS.
 PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT PROTECTION
 FOR HEAT STRIPS W/ RT UNITS.
 PLEASE SEE NEC 220, 215.3, 215.5, 310.16, 240.4 ETC FBC
 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 9) NOTE: PLEASE SEE NO LIGHTING PERFORMANCE
 CALCULATIONS WERE SUBMITTED AS REQUIRED PER 13-415.2,
 13-415.2.ABC.1.1, .1.2. PLEASE KNOW ANY CHANGES TO
 EXTERIOR LIGHTING SHALL MEET 13-415.2.ABC.1.3. PLEASE
 SUBMIT LP CALCULATIONS. AS NONE WERE SUBMITTED AT THIS
 TIME MINIMUM CODE COMPLIANCE REVIEW FOR THESE CAN NOT
 BE DONE. ** THIS OFFICE CAN NOT EMPHASIZE ENOUGH PLEASE
 BE SURE TO SEE THE CODE SECTIONS AS NOTED ABOVEAND
 PLEASE BE SURE ALL LIGHTING ON PLANS ARE INCLUDED WITH
 THE CALCULATIONS.
  
 10) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.2, .1.3 AND .1.4.
 FOR EXAMPLE:
 PLEASE KNOW THE EXTERIOR LIGHTS SHALL MEET ONE OF TWO
 METHODS OF CONTROL PER 13-415.1.ABC.1.4. AT THIS TIME
 PLANS DO NOT INDICATE HOW THE DRIVE THRU LIGHTS ON
 CIRCUIT A-26 WILL MEET CODE.
 PLEASE KNOW THIS IS ONLY NOTED FOR ONE EXAMPLE AND IS
 NOT AN EXHAUSTED LIST.
  
 11) NOTE: PLEASE SEE NO TRACK LIGHTING LOADS SHWON PER
 220.43B.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-16 Cont ID  
Sent By mwennerg Date 2008-07-16 Time 15:04 Rev Time 0.00
Received By mwennerg Date 2008-07-16 Time 15:04 Sent To  
Notes
2008-07-16 15:21:07***DENIED***
  
 PLANS ARE SUBMITTED FOR PLAN REVIEW ONLY. PLANS WILL
 REMAIN IN FAILED STATUS UNTIL ALL COMMENTS ARE
 ADDRESSED AND PLANS ARE SUBMITTED FOR PERMITTING.
  
 ALL COMMENTS FROM FIRST FIRE REVIEW HAVE BEEN ADDRESSED
 WITH THE EXCEPTION OF THE FOLLOWING:
  
 3) RESPONSE LETTER INDICATES CLASS A AND PLANS SHOW
 CLASS B. PLEASE CLARIFY IF INFORMATION DIFFERS FROM
 DRAWINGS.
  
 4) PLANS DO NOT CLEARLY SHOW ILLUMINATED EXIT SIGNS.
 SHEETS A 3.0 AND E 3.0 ILLUSTRATE EMERGENCY LIGHTING
 FACILITIES ONLY.
  
  
 NEW COMMENT:
  
 1) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED THAT
 SHALL BE MOUNTED NOT TO EXCEED 75' TRAVEL DISTANCE.
 PLEASE ADD TO PLANS OR INDICATE WHERE ON PLANS THIS
 INFORMATION IS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-21 Cont ID  
Sent By mwennerg Date 2008-05-21 Time 11:18 Rev Time 0.00
Received By mwennerg Date 2008-05-21 Time 11:18 Sent To  
Notes
2008-05-21 11:27:02***DENIED***
  
 1) THE ADDRESS ON THE BUILDING IS REQUIRED TO BE A
 MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND CONTRASTING
 WITH THE BACKGROUND. ADDRESS SHALL COMPLY WITH CITY OF
 WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS.
 SHT A-1.0, NOTE 2
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALSS AND CEILING IN TERMS OF CLASS A, B, OR C.
  
 4) AN EXIT SIGN IS SHOWN AT THE VESTIBULE. PLEASE
 EXPLAIN EXITING ARRANGEMENTS AT THAT LOCATION AS IT
 DOES NOT APPEAR CLEAR AND OBVIOUS.
  
 5) DOORS SHALL COMPLY WITH NFPA 101, SECTION 7.2.1.
  
 6) AT THIS TIME, A PERMIT HAS NOT BEEN ISSUED FOR THE
 SHELL BUILDING WHICH IMPACTS THIS REVIEW. PLEASE SEE
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:09 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:09 Sent To  
Notes
2008-06-18 15:57:02TO "COMM" BD#41/PLANS ON RACK/1 ROLL
2008-06-17 16:10:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-21 Cont ID  
Sent By mwennerg Date 2008-05-21 Time 11:27 Rev Time 0.00
Received By mwennerg Date 2008-04-21 Time 10:58 Sent To  
Notes
2008-04-21 10:58:49TO "COMM" BD#50

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-07-08 Cont ID  
Sent By rregueir Date 2008-07-08 Time 09:02 Rev Time 0.00
Received By rregueir Date 2008-07-08 Time 08:48 Sent To  
Notes
2008-07-08 08:49:02REVIEW #: 2ND **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 20076 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENT #1 HAS NOT BEEN ADDRESSED.
  
 COMMENTS 2 THROUGH 5: OK
  
 ENERGY CALCULATIONS CAN NOT BE REVIEWED AT THIS TIME
 FOR THE FOLLOWING REASONS:
  
 - THE INPUT DATA REPORT IS REQUIRED TO BE ATTACHED TO
 THE COMPLIANCE FORM. SEE "IMPORTANT NOTE" ON PAGE 2 OF
 THE FORM.
  
 - COOLING LOAD CALCULATIONS OR SYSTEM SIZING SUMMARY
 SHALL BE ATTACHED TO THE ENERGY CALCULATIONS IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 - THE ENERGY CALCULATIONS SHALL BE PREPARED AND
 CERTIFIED BY A PROFESSIONAL ENGINEER OR ARCHITECT IN
 ACCORDANCE WITH FBCB 13-103.1.1.1 AND FBCB 13-103.2.
 THE PREPARER IS LISTED AS "VINOI SKARIA" AND THIS
 PERSON HAS NOT SIGNED AND SEALED THE PLANS. PAUL HUBER
 HAS SIGNED AND SEALED A COVER SHEET BUT HAS NOT SIGNED
 AND SEALED THE COMPLIANCE FORM ON THE CERTIFICATIONS
 PAGE. MR. HUBER IS NOT LISTED AS THE PREPARER OF THESE
 CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-12 Cont ID  
Sent By rregueir Date 2008-05-12 Time 09:34 Rev Time 0.00
Received By rregueir Date 2008-05-08 Time 13:33 Sent To  
Notes
2008-05-12 09:34:10REVIEW #: 1ST. ***PLAN CHECK ONLY**
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005, 2006 AND 2007 SUPPLEMENTS
  
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THIS APPEARS TO BE A TENANT BUILD-OUT IN A SHELL
 BUILDING. A PERMIT FOR THE SHELL BUILDING HAS NOT BEEN
 ISSUED. THIS PERMIT MAY NOT BE ISSUED PRIOR TO THE
 SHELL BUILDING. IF THIS PERMIT IS APPLIED FOR PRIOR TO
 COMPLETION OF THE SHELL BUILDING, A LETTER FROM THE
 BASE BUILDING CONTRACTOR ALLOWING THE TENANT CONTRACTOR
 TO START WORK PRIOR TO A CERTIFICATE OF COMPLETION WILL
 BE REQUIRED. A JOINT LETTER FROM THE DEVELOPER AND BOTH
 CONTRACTORS WILL ALSO BE REQUIRED ACKNOWLEDGING THAT
 ANY DISPUTE OVER RESPONSIBILITY DOES NOT RELIEVE ANY
 PARTY FROM DEMONSTRATING CODE COMPLIANCE PRIOR TO
 CERTIFICATE OF OCCUPANCY.
  
 2. SIGNED AND SEALED PLANS SHALL CONTAIN THE ORIGINAL
 SIGNATURE OF THE DESIGN PROFESSIONAL. A TITLE BLOCK
 CONFORMING TO FAC RULE 61G15-23.002 IS REQUIRED ON EACH
 SET OF PLANS. IF THE DESIGNER OF RECORD IS PRACTICING
 AS AN INDIVIDUAL, REMOVE THE BUSINESS NAME FROM THE
 ENGINEER?S TITLE BLOCK.
  
 3. PG M2.0: HVAC FLOOR PLAN, MUCH OF THE DUCTWORK IS
 NOT VISIBLE ON PLANS BECAUSE IT BLENDS IN WITH THE
 CEILING GRID. PLEASE SHOW CLEARLY THE LOCATION AND SIZE
 OF ALL DUCTWORK IN ORDER TO FACILITATE A COMPLETE
 REVIEW. DUCTWORK CAN NOT BE REVIEWED AT THIS TIME. FBCM
 603.1, FBCB 106.1.1.
  
 4. PG M2.0: VENTILATION CALCULATIONS SHALL BE BASED ON
 THE 2004 FBCM, NOT THE 2007. THE 2007 FBC WILL NOT BE
 ADOPTED OR ENFORCED PRIOR TO 10/1/2008. THE CURRENT
 MECHANICAL CODE IN EFFECT AT THIS TIME IS THE 2004 FBCM
 WITH 2006 AMENDMENTS.
  
 5. PG M2.0: NO INFORMATION COULD BE FOUND ON PLANS
 REGARDING AMOUNT OF EXHAUST BEING PROVIDED FOR
 RESTROOMS. PROVIDE VENTILATION RATE INFORMATION IN
 ACCORDANCE WITH FBCM TABLE 403.3. ALSO PROVIDE AIR
 BALANCE DATA SHOWING COMPLIANCE WITH FBCB
 13-409.1.ABC.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-07-18 Cont ID  
Sent By kstevens Date 2008-07-18 Time 15:24 Rev Time 0.00
Received By kstevens Date 2008-07-18 Time 15:23 Sent To  
Notes
2008-07-18 15:39:07DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 AMENDMENTS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW;
  
 1. PLANS SUBMITTED FOR PLAN REVIEW ONLY AT THIS TIME.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 15. SHT P1.0 MISC PLUMBING FIXTURES. THE WATER
 FILTRATION SYSTEM SHALL MEET THE REQUIREMENTS OF NSF-42
 OR NSF-58 PER SECTIONS 611.1 OR 611.2. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE.
 ****RESPONSE NOTED, BUT MANUFACTURE SPECIFICATIONS
 SHEETS DO NOT INDICATE THAT THEY MEET THE NSF-58
 REQUIREMENTS. PER SECTION 611.2 THE FILTER MAY MEET
 WATER QUALITY ASSOCIATION STANDARD S-300 AS AN
 ALTERNATIVE BUT SHALL MEET ONE STANDARD OR THE OTHER.
 (IF THIS IS THE ONLY OUTSTANDING COMMENT PLANS CAN BE
 PROVISO'D AND PERMIT ISSUED. REQUIRED INFORMATION CAN
 BE SUBMITTED PRIOR TO FINAL PLUMBING INSPECTION).
  
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-29 Cont ID  
Sent By kstevens Date 2008-04-29 Time 12:16 Rev Time 0.00
Received By kstevens Date 2008-04-29 Time 12:16 Sent To  
Notes
2008-04-29 12:55:37DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 AMENDMENTS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. PLANS SUBMITTED FOR PLAN REVIEW ONLY AT THIS TIME.
  
 2. ALL SHEETS. THE SIGNATURES ON THE SEAL ARE NOT
 ORIGINAL "WET" SEALS, BUT STAMPED OR PHOTO COPIED.
 ORIGINAL SIGNATURES ARE REQUIRED PER FAC 61G15-002(2),
 61G1-16.004(5) & FS 471.025, 481.221.
  
 3. SHT A6.0 DETAIL #5 INDICATES THE BOTTOM OF MIRROR AT
 1'8" ABOVE THE FLOOR. WITH THE CLEARANCES OF THE LAV
 REQUIRED TO BE 29" AND THE RIM OF THE LAV TO BE A
 MINIMUM OF 34" PLEASE EXPLAIN HOW THE MIRROR CAN BE
 THAT LOW. SECTION 11-4.19.2. PER SECTION 11-4.19.6 THE
 BOTTOM OF THE MIRROR SHALL BE MAX 40". PLEASE CLARIFY.
  
 4. SHT A6.0 DETAIL #5 THE GRAB BARS AT THE WATER CLOSET
 ARE SHOWN AT 1'4". THE GRAB BARS SHALL BE 33" - 36" PER
 SECTION 11-4.16..4 & FIG. 11-28.
  
 5. SHT A6.0 DETAIL #5 THE LAV IS INDICATED AS 9" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE. THE LAV
 SHALL BE MINIMUM 15" OFF THE WALL TO BE CENTERED ON THE
 30" DIMENSION OF THE CLEAR FLOOR SPACE REQUIRED BY
 SECTION 11-4.19.3.
  
 6. SHT A6.0 DETAIL #9 INDICATES THE W/C TO BE 9" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE. THE W/C
 SHALL BE 1'6" OFF THE WALL TO THE C/L PER FIG. 11-28.
  
 7. SHT A6.0 DETAIL #9 THE GRAB BARS FOR THE W/C IS
 INDICATED TO BE 1'4" ABOVE THE FLOOR. THE GRAB BARS
 SHALL BE 33" - 36" PER SECTION 11-4.16..4 & FIG.
 11-28.
  
 8. SHT A6.0 DETAIL #9 THE W/C HEIGHT IS INDICATED AS
 9". THE HEIGHT SHALL BE INDICATED AS BETWEEN 17" & 19"
 PER SECTION 11-4.16.3.
  
 9. SHT A6.0 DETAIL #10 HEIGHT OF THE LAV IS INDICATED
 AS 1'5". THE CLEARANCE REQUIRED IS 29". SECTION
 11-4.19.2. PLEASE CLARIFY.
  
 10. SHT A6.0 DETAIL #16 THE GRAB BARS FOR THE W/C IS
 INDICATED TO BE 1'4" ABOVE THE FLOOR. THE GRAB BARS
 SHALL BE 33" - 36" PER SECTION 11-4.16..4 & FIG.
 11-28.
  
 11. SHT A6.0 DETAIL #17 INDICATES THE W/C TO BE 9" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE. THE W/C
 SHALL BE 1'6" OFF THE WALL TO THE C/L PER FIG. 11-28.
  
 12. SHT A6.0 DETAIL #17 INDICATES THE BOTTOM OF MIRROR
 AT 1'8" ABOVE THE FLOOR. WITH THE CLEARANCES OF THE LAV
 REQUIRED TO BE 29" AND THE RIM OF THE LAV TO BE A
 MINIMUM OF 34" PLEASE EXPLAIN HOW THE MIRROR CAN BE
 THAT LOW. SECTION 11-4.19.2. PER SECTION 11-4.19.6 THE
 BOTTOM OF THE MIRROR SHALL BE MAX 40". PLEASE CLARIFY.
  
 13. SHT A6.0 DETAIL #17 THE GRAB BARS FOR THE W/C IS
 INDICATED TO BE 1'4" ABOVE THE FLOOR. THE GRAB BARS
 SHALL BE 33" - 36" PER SECTION 11-4.16..4 & FIG.
 11-28.
  
 14. SHT A6.0 DETAIL #18 THE LAV IS INDICATED AS 1'5" TO
 THE RIM. THE CLEARANCE REQUIRED IS 29". SECTION
 11-4.19.2. PLEASE CLARIFY.
  
 15. SHT P1.0 MISC PLUMBING FIXTURES. THE WATER
 FILTRATION SYSTEM SHALL MEET THE REQUIREMENTS OF NSF-42
 OR NSF-58 PER SECTIONS 611.1 OR 611.2. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE.
  
 16. SHT P1.0 BUILDING CODE NOTES SHALL INCLUDE 2007
 AMENDMENTS. ALSO THE CODE NOTES SHALL STATE CITY OF
 WEST PALM BEACH, NOT CITY OF CAPE CORAL. SECTION
 106.3.5.
  
 17. SHT P2.0 SUPPLY PIPING DIAGRAM SHALL BE SUBMITTED
 IN AN ISOMETRIC FORM TO REFLECT THE FLOOR PLAN AMD
 ACTUAL PIPING INSTALLATION. SECTIONS 106.1.3 &
 106.3.5.1.3. SHOW THE WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9 AT THE DISH WASHER AND AT THE ICE
 MAKER. WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201.
  
 18. SHT P2.0 PLUMBING SCHEDULE. ITEMS P017, P026, P036,
 P068 & P080 SHOW NO WATER SUPPLY. PLEASE CLARIFY.
 SECTION 601.1 & TABLE 604.5.
  
 19. SHT P2.0 PLUMBING SCHEDULE. INTEM P358 OUTDOOR
 SPIGOT INDICATES 3/8" INLET. TABLE 604.5 INDICATES
 MINIMUM SIZE WATER SUPPLY IS 1/2". ALSO 3/4" SUPPLY
 LINE IS SHOWN TO THE SPIGOT/HOSE BIBB. PLEASE CLARIFY.
  
  
 20. SHT P2.0 PLUMBING SCHEDULE. ITEM P360 FAUCET SHOWS
 NO WATER SUPPLY. PLEASE CLARIFY. SECTIONS 106.1.1 &
 106.1.
  
 21. SHT P2.0 PLUMBING SCHEDULE. ITEM P035 INDICATES 3
 FLOOR DRAINS AND REFERS TO SHT P3.0 WHICH ONLY
 INDICATES 2 FLOOR DRAINS ON THE FLOOR PLAN AND PLUMBING
 SCHEDULE. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 22. SHT P2.0 PLUMBING SCHEDULE. ITEM P367 INDICATES QTY
 1 BUT 2 ARE SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 23. SHT P2.0 NOTE #20 INDICATES A WATER SUB METER. THE
 SUB METER WAS NOT FOUND ON THE FLOOR PLAN. PLEASE
 CORRELATE/CLARIFY. SECTION 106.1.1.
  
 24. SHT P2.0 NOTES #21, #29 & #31 WERE NOT FOUND ON THE
 FLOOR PLAN. PLEASE CORRELATE/CLARIFY. SECTION 106.1.1.
  
 25. SHT P3.0 SUBMIT THE SANITARY RISER DIAGRAM IN
 ISOMETRIC FORM THAT REFLECT THE FLOOR PLAN AND ACTUAL
 PIPING INSTALLATION. SECTIONS 106.1.3 & 106.3.5.1.3.
  
 26. SHT P3.0 THE DISHWASHER SHALL CONNECT TO THE
 SANITARY SYSTEM, NOT THE GREASE SYSTEM PER ATRICLE III
 SECTION 90-124(7)(B). PLEASE SHOW ON FLOOR P[LAN AND
 ISOMETRIC RISER DIAGRAM.
  
 27. SHT P3.0 NOTE #4 INDICATES INDIRECT WASTE RECEPTOR,
 BUT THE PLUMBING SCHEDULE INDICATES 2" DIRECT WASTE
 CONNECTION. PLEASE CORRELATE/CLARIFY. PER SECTIONS
 802.1 & 802.1.1 UNLESS THERE IS FOOD HANDLING/STORAGE
 IN THE 3 COMPARTMENT SINK, A DIRECT CONNECTION IS
 APPROVED.
  
 28. SHT P3.0 NOTE #15 CONDENSATE SHALL DRAIN OUT OF THE
 BUILDING SEPARATELY AND CONNECT TO A DRYWELL, CATCH
 BASIN, STORM LINE OR DRAIN TO A PLANTED AREA. IF
 CONNECTING TO A STORM LINE, A RELIEF VENT, (GOOSENECK),
 IS REQUIRED AS THE CONDENSATE EXITS THE BUILDING.
 ARTICLE III SECTION 90-125(5).
  
 29. SHT P4.0 DETAIL #7 INDICATES 1" MINIMUM AIR GAP. 3"
 AIR GAP REQUIRED PER SECTION 802.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2008-06-18 Cont ID  
Sent By adavila Date 2008-06-18 Time 17:51 Rev Time 0.00
Received By adavila Date 2008-06-18 Time 17:51 Sent To  
Notes
2008-06-18 17:53:12PERMIT FOR INTERIOR WORK ONLY.SITE IMPROVEMENTS
 REVISED/APPROVED UNDER PERMIT NUMBER 07120184.
  
 ALL SIGNS, TO INCLUDE THE MENU BOARD, AWNINGS, AND
 WALLS/FENCES SHALL BE APPROVED UNDER A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By adavila Date 2008-04-24 Time 11:29 Rev Time 0.00
Received By adavila Date 2008-04-23 Time 11:29 Sent To  
Notes
2008-04-24 11:29:35PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. SITE LOCATION MAP LABELS PRIVATE DRIVEWAY ALONG EAST
 SIDE OF THE DRIVE-THRU AS OKEECHOBEE ROAD.PLEASE
 REVIEW.
  
 2. SQUARE FOOTAGE OF THE STARBUCK'S BUILDING EXCEEDS
 THE APPROVED SQUARE FOOTAGE PER THE APPROVED SITE PLAN
 AND PALM BEACH COUNTY TRAFFIC LETTER (CONCURRENCY).
 PLEASE REVIEW.
  
 3. PROVIDE LOCATION OF ALL LIGHT POLES SURROUNDING THE
 STRUCTURE AND DRIVE WAYS.PLEASE NOTE THAT THERE
 APPEAR TO BE CONFLICTS BETWEEN THE PROPOSED LOCATION OF
 THE MENU BOARD AND TRASH CONTAINER AT THE END OF THE
 DRIVE-THRU WITH THE APPROVED LOCATIONS OF THE LIGHT
 POLES.
  
 4. PROVIDE DETAIL OF OUTDOOR SEATING AREA WITH
 DIMENSIONS, TO INCLUDE HEIGHT OF THE RAILING.
  
 5. DUMPSTER ENCLOSURE DETAILS DO NOT MATCH THE APPROVED
 DETAILS PER THE APPROVED SITE PLAN.PLEASE REVIEW.
  
 6. PROVIDE ROOF PLAN.
  
 7. PROVIDE LOCATION AND DETAILS OF ALL A/C UNITS AND
 MECHANICAL EQUIPMENT FOR THIS STRUCTURE.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.