Plan Review Details - Permit 08040475
Plan Review Stops For Permit 08040475
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-16 Cont ID  
Sent By mjacobs Date 2008-06-16 Time 12:24 Rev Time 0.00
Received By mjacobs Date 2008-06-16 Time 11:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-28 Cont ID  
Sent By btrobaug Date 2008-05-28 Time 15:35 Rev Time 0.00
Received By mjacobs Date 2008-05-28 Time 11:52 Sent To PC
Notes
2008-05-28 17:25:263RD
 BUILDING PLAN REVIEW
 PERMIT: 08040475
 ADD: 400 N. FLAGLER DR. #1102
 CONT: OWNER BUILDING ALIANCES INC.
 TEL: (561)433-9020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-28-08
 REVIEW: 3RD
 ACTION: DENIED
  
 1) OK
 2) OK
  
 *NOTED: HOWEVER, LEVEL 2 ALTERATION INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT. THE BUILDING IS ABOUT 23 STORIES HIGH
 THEREFORE THE CONSTRUCTION TYPE CANNOT BE TYPE 111 PER
 TABLE 503.
 3)2004 FBC EXISTING: 301.5 THE DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 *NOTED; HOWEVER, THE UL DESIGN NUMBER AND SYSTEM
 REQUIRED*
 4)THE APPLICATION INDICATES THE CAPPING OF BIDET, THE
 REMOVAL OF AN EXISTING SHOWER AND TUB WHICH WILL
 REQUIRE THE FLOOR TO BE SEAL WITH AN APPROVED
 PENETRATION FIRE STOP SYSTEM WHEN THESE ITEMS ARE
 REMOVED. THE RESPONSE LETTER INDICATES THE REMOVAL OF
 THE BIDET PLUMBING; THEREFORE C-AJ-1090 OR C-AJ-1080
 WILL NOT BE APPLICABLE FOR SEALING THE FLOOR WHEN THE
 PIPE IS REMOVED. CHOOSE A DIFFERENT ASSEMBLE FOR
 PATCHING THE FLOOR.
  
 5)NOTED.
 6)NOTED
  
 *NO RESPONSE NOT ADDRESSED*
 7)A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL WORK ON A
 BUILDING OVER THREE STORIES IN HEIGHT. THE FLOOR
 PENETRATIONS REPAIRS SHALL BE PERFORMED BY A LICENSE
 GENERAL CONTRACTOR OR A LICENSE FIRE PROOFING COMPANY.
 INFORMATION SHALL BE PROVIDED TO THIS OFFICE STATING
 WHO WILL BE RESPONSIBLE FOR ALL STRUCTURAL
 PENETRATIONS. PROVIDE THE UL SYSTEM FOR THE FLOOR
 PENETRATIONS ON THE PLANS. THE LETTER FROM THE
 ARCHITECT, WHICH STATES ?PROVIDE 1 HOUR RATED CALKING
 AT FLOOR PENETRARTIONS IS NOT SUFFICIENT INFORMATION
 FOR THE FLOOR ASSEMBLY. A UL ASSEMBLY IS REQUIRED
 MEETING THE EXISTING FLOOR FIRE RATING. ONCE AGAIN, A
 CBC CONTRACTOR IS NOT ALLOWED TO DO ANY STRUCTURAL WORK
 ON BUILDINGS OVER THREE STORIES.
  
 8)NO NEW WALLS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-30 Cont ID  
Sent By mjacobs Date 2008-04-30 Time 11:02 Rev Time 0.00
Received By mjacobs Date 2008-04-30 Time 08:49 Sent To PC
Notes
2008-04-30 11:02:07 
 BUILDING PLAN REVIEW
 PERMIT: 08040475
 ADD: 400 N. FLAGLER DR. #1102
 CONT: OWNER BUILDING ALIANCES INC.
 TEL: (561)433-9020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-30-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 *NO RESPONSE NOT ADDRESSED*
 2) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT AFTER JULY
 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC BUILDING
 WITH THE 2007 SUPPLEMENTS.
  
 *NO RESPONSE NOT ADDRESSED*
 3)2004 FBC EXISTING
 301.5 THE DESIGN PROFESSIONAL OR AN OWNER MUST ELECT
 ONE OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT
 TO SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 *NOTED; HOWEVER, THE UL DESIGN NUMBER AND SYSTEM
 REQUIRED*
 4)THE APPLICATION INDICATES THE CAPPING OF BIDET, THE
 REMOVAL OF AN EXISTING SHOWER AND TUB WHICH WILL
 REQUIRE THE FLOOR TO BE SEAL WITH AN APPROVED
 PENETRATION FIRE STOP SYSTEM WHEN THESE ITEMS ARE
 REMOVED.
  
 5)NOTED.
  
 *NO RESPONSE NOT ADDRESSED*
 6)712.4.1.2 THROUGH-PENETRATION FIRE STOPS SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER. THE SYSTEM SHALL HAVE AN F RATING AND A T RATING
 OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED
 RATING OF THE FLOOR PENETRATED.
  
 *NO RESPONSE NOT ADDRESSED*
 7)A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL WORK ON A
 BUILDING OVER THREE STORIES IN HEIGHT. THE FLOOR
 PENETRATIONS REPAIRS SHALL BE PERFORMED BY A LICENSE
 GENERAL CONTRACTOR OR A LICENSE FIRE PROOFING COMPANY.
 INFORMATION SHALL BE PROVIDED TO THIS OFFICE STATING
 WHO WILL BE RESPONSIBLE FOR ALL STRUCTURAL
 PENETRATIONS. PROVIDE THE UL SYSTEM FOR THE FLOOR
 PENETRATIONS ON THE PLANS.
  
 *NO RESPONSE NO ADDRESSED*
 8)PROVIDE THE DETAILS FOR THE NEW WALL INDICATING ALL
 THE MATERIALS. ANY PENETRATIONS THROUGH A FIRE WALL
 SHALL REPAIR IN A MANNER WHICH MEETS THE RATING OF THE
 EXISTING WALL. THE UL NUMBER FOR FIRE PARTITION WALL
 NEED TO SHOWN ON THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By mjacobs Date 2008-04-24 Time 07:39 Rev Time 0.00
Received By mjacobs Date 2008-04-23 Time 16:29 Sent To  
Notes
2008-04-24 07:39:07BUILDING PLAN REVIEW
 PERMIT: 08040475
 ADD: 400 N. FLAGLER DR.
 CONT: OWNER BUILDING ALIANCES INC.
 TEL: (561)433-9020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-23-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)THE APPLICATION INDICATES THE CAPPING OF BIDET, THE
 REMOVAL OF AN EXISTING SHOWER AND TUB WHICH WILL
 REQUIRE THE FLOOR TO BE SEAL WITH AN APPROVED
 PENETRATION FIRE STOP SYSTEM WHEN THESE ITEMS ARE
 REMOVED.
  
 5)712.4 PENETRATIONS OF A FLOOR, FLOOR/CEILING
 ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING
 ASSEMBLY SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 707. PENETRATIONS PERMITTED BY EXCEPTIONS 3 AND 4 OF
 SECTION 707.2 SHALL COMPLY WITH SECTIONS 712.4.1
 THROUGH 712.4.4 .
  
 6)712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED
 BY AN APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM
 INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR
 UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL
 OF 0.01 INCH OF WATER. THE SYSTEM SHALL HAVE AN F
 RATING AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT
 LESS THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
  
 7)A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL WORK ON A
 BUILDING OVER THREE STORIES IN HEIGHT. THE FLOOR
 PENETRATIONS REPAIRS SHALL BE PERFORMED BY A LICENSE
 GENERAL CONTRACTOR OR A LICENSE FIRE PROOFING COMPANY.
 INFORMATION SHALL BE PROVIDED TO THIS OFFICE STATING
 WHO WILL BE RESPONSIBLE FOR ALL STRUCTURAL
 PENETRATIONS. PROVIDE THE UL SYSTEM FOR THE FLOOR
 PENETRATIONS ON THE PLANS.
  
 8)PROVIDE THE DETAILS FOR THE NEW WALL INDICATING ALL
 THE MATERIALS. ANY PENETRATIONS THROUGH A FIRE WALL
 SHALL REPAIR IN A MANNER WHICH MEETS THE RATING OF THE
 EXISTING WALL. THE UL NUMBER FOR FIRE PARTITION WALL
 NEED TO SHOWN ON THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-12 Cont ID  
Sent By btrobaug Date 2008-06-12 Time 15:34 Rev Time 0.00
Received By btrobaug Date 2008-06-12 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-21 Cont ID  
Sent By btrobaug Date 2008-04-21 Time 12:56 Rev Time 0.00
Received By btrobaug Date 2008-04-21 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-12 Cont ID  
Sent By btrobaug Date 2008-06-12 Time 15:35 Rev Time 0.00
Received By btrobaug Date 2008-06-09 Time 08:57 Sent To  
Notes
2008-06-09 09:00:24TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 10:49 Sent To B
Notes
2008-05-19 10:49:55TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-25 Cont ID  
Sent By adarroug Date 2008-04-25 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-04-25 Time 11:18 Sent To B
Notes
2008-04-25 11:19:12TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-04-24 Time   Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 12:44 Sent To  
Notes
2008-04-18 12:49:06TO "BOB"#10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-09 Cont ID  
Sent By tgordon Date 2008-06-09 Time 12:24 Rev Time 0.25
Received By tgordon Date 2008-06-09 Time 12:24 Sent To  
Notes
2008-06-09 12:25:52REPLACE EXISTING BATHROOM EXHAUST FAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-04-21 Cont ID  
Sent By tgordon Date 2008-04-21 Time 13:40 Rev Time 0.25
Received By tgordon Date 2008-04-21 Time 13:40 Sent To  
Notes
2008-04-21 13:46:02*** PROVISO ***
 1) 2004 FBC/R R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.279 M 2 ),
 ONE-HALF OF WHICH MUST BE OPENABLE.
  
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A MECHANICAL VENTILATION SYSTEM
 ARE PROVIDED. THE MINIMUM VENTILATION RATES SHALL BE 50
 CFM (23.6 L/S) FOR INTERMITTENT VENTILATION OR 20 CFM
 (9.4 L/S) FOR CONTINUOUS VENTILATION. VENTILATION AIR
 FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTSIDE.
  
 A MECHANICAL PERMIT MAY BE REQUIRED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-18 Cont ID  
Sent By mperson Date 2008-06-18 Time 10:43 Rev Time 0.00
Received By mperson Date 2008-06-18 Time 10:43 Sent To PC
Notes
2008-06-18 10:45:20******PROVISO******
 THE REMOVAL OF THE BIDET AND SHOWER SHALL COMPLY WITH
 THE FOLLOWING.
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-04-21 Cont ID  
Sent By btrobaug Date 2008-06-12 Time 15:35 Rev Time 0.00
Received By mperson Date 2008-04-21 Time 09:16 Sent To  
Notes
2008-04-21 09:24:31****************PROVISO****************
 A} NOTE: THE REMOVAL OF THE BIDET AND SHOWER SHALL
 COMPLY WITH THE FOLLOWING.
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 B} NOTE: THE REPLACEMENT OF THE TUB WITH A NEW SHOWER
 SHALL COMPLY WITH FBC-2004 PLUMBING SECTION 417.5.2
 SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 417.5.2.1 THROUGH 417.5.2.4 . SUCH LINERS
 SHALL TURN UP ON ALL SIDES AT LEAST 2 INCHES (51 MM)
 ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET.
 (INSPECTION REQUIRED)
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-18 Cont ID  
Sent By choops Date 2008-04-18 Time 16:26 Rev Time 0.00
Received By choops Date 2008-04-18 Time 16:26 Sent To  
Notes
2008-04-18 16:26:35*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.