Plan Review Details - Permit 08040474
Plan Review Stops For Permit 08040474
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By mjacobs Date 2008-04-25 Time 07:31 Rev Time 0.00
Received By mjacobs Date 2008-04-24 Time 09:28 Sent To  
Notes
2008-04-25 07:31:08BUILDING PLAN REVIEW
 PERMIT: 08040474
 ADD: 1411 N. FLAGLER DR. #6400
 CONT: J.P. HURBON INC.
 TEL: (561)575-2461
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-04-21 Cont ID  
Sent By btrobaug Date 2008-04-21 Time 08:56 Rev Time 0.00
Received By btrobaug Date 2008-04-21 Time 08:45 Sent To  
Notes
2008-04-21 08:57:50 
  
 REDLINED 32 AMP PRIMARY ON A 30KVA 480 VOLT XFMR. MUSR
 BE 45 AMPS PER 450.5(A)(2).

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-04-22 Cont ID  
Sent By mwennerg Date 2008-04-22 Time 15:16 Rev Time 0.00
Received By mwennerg Date 2008-04-22 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-25 Cont ID  
Sent By adarroug Date 2008-04-25 Time 12:17 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 10:45 Sent To  
Notes
2008-04-18 10:45:35TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-18 Cont ID  
Sent By mperson Date 2008-04-18 Time 13:43 Rev Time 0.00
Received By mperson Date 2008-04-18 Time 13:43 Sent To  
Notes
2008-04-18 14:37:04PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 IS INDICATING A PROCESSOR AND SHEET P-1
 IS INDICATING THE PROCESSOR BEING TIED INTO THE
 SANITARY SYSTEM. PLEASE KNOW THAT A NEUTRALIZATION TANK
 MAY BE REQUIRED FOR THIS EQUIPMENT PRIOR TO CONNECTION
 TO THE SANITARY SYSTEM.
 PER FBC PLUMBING SECTION 1003.1 WHERE REQUIRED.
 INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO
 PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE BUILDING
 DRAINAGE SYSTEM, THE PUBLIC SEWER, OR SEWAGE TREATMENT
 PLANT OR PROCESSES.
 *PLEASE REFERENCE THE FOLLOWING*
 PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B)
 DISCARGE PROHIBITIONS(20)(D) LOCAL PRETREATMENT
 STANDARDS, TABLE INSET:
 THE PROPOSED PROCESSOR SHALL BE APPROVED BY
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY
 DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: (561)
 822-2272, E-MAIL: [email protected]. THE FAX NUMBER IS
 (561) 822-2287. NOTE: WRITTEN APPROVAL IS REQUIRED OF
 THE PROPOSED PROCESSOR FROM ENVIRONMENTAL COMPLIANCE
 BEFORE A PERMIT CAN BE ISSUED.
 PLEASE PROVIDE TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS OF THE PROCESSOR. CLEARLY
 INDICATING THE MAKE MODEL NUMBER AND A LISTING FROM A
 NATIONALL RECOGNIZED TESTING LABORATORY (THIRD PARTY
 TESTING AND CERTIFICATION). PER FBC PLUMBING SECTION
 303.4.
  
 2. SHEET P-1 IS INDICATING THE PROPOSED PROCESSOR
 BEING TIED INTO THE POTABLE WATER SYSTEM. PROTECTION
 AGAINST CONTAMINATION IS REQUIRED PER FBC PLUMBING
 SECTION 608.3 DEVICES, APPURTENANCES, APPLIANCES AND
 APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER
 SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY
 SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS,
 COMMERCIAL DRINKING WATER DISPENSERS AND ALL OTHER
 APPLIANCES AND DEVICES THAT HANDLE OR TREAT POTABLE
 WATER SHALL BE PROTECTED AGAINST CONTAMINATION.
 PLEASE PROVIDE TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS OF THE PROCESSOR. CLEARLY
 INDICATING THE MAKE MODEL NUMBER AND A LISTING FROM A
 NATIONALL RECOGNIZED TESTING LABORATORY (THIRD PARTY
 TESTING AND CERTIFICATION). PER FBC PLUMBING SECTION
 303.4.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-18 Cont ID  
Sent By choops Date 2008-04-18 Time 16:24 Rev Time 0.00
Received By choops Date 2008-04-18 Time 16:24 Sent To  
Notes
2008-04-18 16:24:42*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.