| 2008-04-18 14:37:04 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1 IS INDICATING A PROCESSOR AND SHEET P-1 |
| | IS INDICATING THE PROCESSOR BEING TIED INTO THE |
| | SANITARY SYSTEM. PLEASE KNOW THAT A NEUTRALIZATION TANK |
| | MAY BE REQUIRED FOR THIS EQUIPMENT PRIOR TO CONNECTION |
| | TO THE SANITARY SYSTEM. |
| | PER FBC PLUMBING SECTION 1003.1 WHERE REQUIRED. |
| | INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO |
| | PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER |
| | SUBSTANCES HARMFUL OR HAZARDOUS TO THE BUILDING |
| | DRAINAGE SYSTEM, THE PUBLIC SEWER, OR SEWAGE TREATMENT |
| | PLANT OR PROCESSES. |
| | *PLEASE REFERENCE THE FOLLOWING* |
| | PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B) |
| | DISCARGE PROHIBITIONS(20)(D) LOCAL PRETREATMENT |
| | STANDARDS, TABLE INSET: |
| | THE PROPOSED PROCESSOR SHALL BE APPROVED BY |
| | ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY |
| | DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: (561) |
| | 822-2272, E-MAIL: [email protected]. THE FAX NUMBER IS |
| | (561) 822-2287. NOTE: WRITTEN APPROVAL IS REQUIRED OF |
| | THE PROPOSED PROCESSOR FROM ENVIRONMENTAL COMPLIANCE |
| | BEFORE A PERMIT CAN BE ISSUED. |
| | PLEASE PROVIDE TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATION SHEETS OF THE PROCESSOR. CLEARLY |
| | INDICATING THE MAKE MODEL NUMBER AND A LISTING FROM A |
| | NATIONALL RECOGNIZED TESTING LABORATORY (THIRD PARTY |
| | TESTING AND CERTIFICATION). PER FBC PLUMBING SECTION |
| | 303.4. |
| | |
| | 2. SHEET P-1 IS INDICATING THE PROPOSED PROCESSOR |
| | BEING TIED INTO THE POTABLE WATER SYSTEM. PROTECTION |
| | AGAINST CONTAMINATION IS REQUIRED PER FBC PLUMBING |
| | SECTION 608.3 DEVICES, APPURTENANCES, APPLIANCES AND |
| | APPARATUS. |
| | ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS |
| | INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS |
| | STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR |
| | STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER |
| | SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION |
| | AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY |
| | SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS, |
| | COMMERCIAL DRINKING WATER DISPENSERS AND ALL OTHER |
| | APPLIANCES AND DEVICES THAT HANDLE OR TREAT POTABLE |
| | WATER SHALL BE PROTECTED AGAINST CONTAMINATION. |
| | PLEASE PROVIDE TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATION SHEETS OF THE PROCESSOR. CLEARLY |
| | INDICATING THE MAKE MODEL NUMBER AND A LISTING FROM A |
| | NATIONALL RECOGNIZED TESTING LABORATORY (THIRD PARTY |
| | TESTING AND CERTIFICATION). PER FBC PLUMBING SECTION |
| | 303.4. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |