| 2008-04-17 16:11:12 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | 1.PROVIDE A ROOF PLAN SHOWING AREA OF REROOF. |
| | |
| | 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| | ADDITION TO THE EVALUATION REPORT SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 3.TWO DIFFERENT NOAS WERE SUBMITTED; POLYGLASS AND |
| | GAF, AND THE APPLICATION STATES YOU ARE USING |
| | POLYGLASS.PROVIDE TWO IDENTICAL SETS OF ONE PRODUCT. |
| | |
| | 4.THE POLYGLASS NOA CONTAINS AN ERROR.THIS NOA HAS |
| | BEEN REPLACED BY ANOTHER NOA; PLEASE SEE |
| | WWW.BUILDINGCODEONLINE.COM OR CONTACT THE MANUFACTURER |
| | FOR MORE INFORMATION.THIS NOA CAN BE USED BUT MUST |
| | INCLUDE THE ENGINEERING WHICH CORRECTS THE FASTENING |
| | ERROR. |
| | |
| | 5.FOR THE FLAT ROOF, SELECT THE APPROVED ASSEMBLY YOU |
| | ARE USING.ALSO INDICATE WHICH FASTENER YOU ARE USING |
| | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| | |
| | 6.FOR THE FLAT ROOF, SPECIFY THE ENHANCED FASTENING |
| | FOR CORNER AND PERIMETER ZONES.THIS IS TO BE EITHER |
| | WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED ON |
| | LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB SHEET). |
| | |
| | 7.PLEASE SEE THE NEW POLYGLASS NOA.THERE IS ONE |
| | ASSEMBLY WHICH MEETS THE PRESSURE FOR CORNER ZONES AND |
| | DOES NOT REQUIRE ENHANCED FASTENING AND ENGINEERING. |
| | OTHER SYSTEMS CAN BE USED, BUT THEN COMMENTS 5 AND 6 |
| | WOULD APPLY.PLEASE SEE THE NEW POLYGLASS NOA, |
| | 07-1030.05. |
| | |