Plan Review Details - Permit 08040438
Plan Review Stops For Permit 08040438
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-01-21 Cont ID  
Sent By jwitmer Date 2009-01-21 Time 14:53 Rev Time 3.33
Received By jwitmer Date 2009-01-21 Time 14:53 Sent To  
Notes
2009-01-21 14:54:28REV# 3 , A-3, A-4, A-5 & A-7 & TRUSS DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-11 Cont ID  
Sent By jwitmer Date 2008-08-11 Time 14:31 Rev Time 2.22
Received By jwitmer Date 2008-08-08 Time 14:31 Sent To  
Notes
2008-08-08 14:31:44BUILDING PLAN REVIEW
 PERMIT: 08040438
 ADD: 420 6TH ST
 CONT: BENNARD SIMPSON G C
 TEL: (561) 296-5858
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 AUG.08-08
 3RD REVIEW
 ACTION: 08-11-08 REVIEWED- OK
  
 1-9 COMPLIED.
  
 10) COMPLIED
 11-14) COMPLIED.
  
 15) BUILDING PROVISO:109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-01 Cont ID  
Sent By jwitmer Date 2008-07-01 Time 10:48 Rev Time 4.00
Received By jwitmer Date 2008-07-01 Time 10:48 Sent To  
Notes
2008-08-08 14:24:00BUILDING PLAN REVIEW
 PERMIT: 08040438
 ADD: 420 6TH ST
 CONT: BENNARD SIMPSON G C
 TEL: (561) 296-5858
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 AUG.08-08
 3RD REVIEW
 ACTION: DENIED
  
 1-9 COMPLIED.
  
 10) SECOND REQUEST,FL BLD CODE 1609.1.4:
 COMPONENTS & CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD
 OR RESIDENT INSPECTOR OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
 ROOFING ASSEMBLIES;
 10A) FIRESTONE REPORT NOA05-0830.10-52.5 PSF &
 LIMITATION# 7 ENHANCED FASTENING ALLOWEDBUT NO RAS
 117 CALCULATION PROVIDED.
 10B) POLYGLASS COATING AND MASTICS FL# 10291/
 NOA07-0919.04 REPORTSUBMITTED IS ONLY FOR COATING AND
 MASTICS SUB PARTS OF AN OVER ALL ROOFING ASSEMBLY.
 PRINTED OUT IS A FL COVER SHEET FOR THEPOLYGLASS
 SYSTEMS MODIFIED SYSTEMS AND UNDERLAYMENTS, NOTE, THESE
 SYSTEMS SHOULD NOT BE USED WITH A MODIFIED SYSTEM FROM
 FIRESTONE, POLYGLASS IS NOT PART OF ANY FIRESTONE
 SYSTEM..
  
 11-14) COMPLIED.
  
 15) BUILDING PROVISO:109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2008-07-01 10:52:24BUILDING PLAN REVIEW
 PERMIT: 08040438
 ADD: 420 6TH ST
 CONT: BENNARD SIMPSON G C
 TEL: (561) 296-5858
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A) PLEASE PROVIDE: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B-1E) COMPLIED.
  
 2A-C ) COMPLIED.
 3-5 ) 7-02-08 AS PER CONVERSATION WITH TONY ZIA
 DESIGNER WILL PROVIDE THE AMOUNT OF FLAMMABLE LIQUIDS
 THAT WILL BE STORED ON SITE FIRST FLOOR. THEY WILL
 DETERMINE THAT TIME IF CONTROLED AREAS WILL BE
 NECCESSARY SEE TABLE 307.7(1) FLAMMABLE LIQUIDS AND
 COMBUSTIBLE LIQUIDS. FERTILIZERS MAY ALSO BE A CONCERN
 AS TO CONTROL AREAS. THE SECOND FLOOR OFFICE AND
 WAREHOUSE AREA WILL ALSO NEED TO BE SEPERATED IN
 ACORDANCEWITH 302.2 THE OFFICE AREA BEING OVER THE
 10% ALLOWABLE AREA TO BE CONSIDERED AN ACCESORY USE
 AREA.THE DESIGNERS WILL ALSO NEED TO PROVIDE WHAT
 TYPE GOODS WILL BE STORED IN THE SECOND FLOOR WAREHOUSE
 PORTION DECLARING EITHER A S1 OR S2 STORAGE AND THE
 REQUIRED OCCUPANCY SEPERATION DECLARED IN TABLE
 302.3.2. NOTE THE BUILDING IS FULLY SPRINKLERED AND CAN
 TAKE A 1 HOUR REDUCTION TO THE SAID WALL 302.3.2..
  
 6) COMPLIED
  
 7-9 COMPLIED.
  
 10) SECOND REQUEST,FL BLD CODE 1609.1.4:
 COMPONENTS & CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD
 OR RESIDENT INSPECTOR OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
 ROOFING ASSEMBLIES;
 10A) FIRESTONE REPORT NOA05-0830.10-45 PSF &
 LIMITATION# 9 NO ENHANCED FASTENING ALLOWED
 10B) POLYGLASS COATING AND MASTICS FL# 10291/
 NOA07-0919.04 REPORTSUBMITTED IS ONLY FOR COATING AND
 MASTICS SUB PARTS OF AN OVER ALL ROOFING ASSEMBLY.
 PRINTED OUT IS A FLOVER PRINT OUT OF POLYGLASS SYSTEMS
 MODIFIED SYSTEMS AND UNDERLAYMENTS.
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 12)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) INFORMATIONAL, AWNING PERMITS REQUIRE A SEPERATE
 PERMIT.
  
 14) COMPLIED.
  
 15) BUILDING PROVISO:109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By jwitmer Date 2008-04-24 Time 08:05 Rev Time 5.56
Received By jwitmer Date 2008-04-24 Time 08:05 Sent To  
Notes
2008-04-24 11:27:45BUILDING PLAN REVIEW
 PERMIT: 08040438
 ADD: 420 6TH ST
 CONT: BENNARD SIMPSON G C
 TEL: (561) 296-5858
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)VERTICAL ADDITIONS: PLANS SUBMITTED FOR PERMIT
 (FIRST TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE
 REVIEWED TO THE 2004 FBC BUILDING EXISTING BUILDING
 CODE CHAPTER 9 WITH THE2007 SUPPLEMENTS.
 PLEASE UP DATE CODE SUMMARY SHEET.
  
 2) PLEASE NOTE THIS BUILDING IS TO BE CONSIDERED A
 MIXED OCCUPANCY. PLEASE REVIEW 406.2.7 FBC MIXED
 SEPERATION. PARKING GARAGES SHALL BE SEPERATED FROM
 OTHER OCCUPANCIES IN ACCORDANCE WITH SECTION 302.3.2
 AND TABLE 302.3.2.
  
 2A) 1ST FLOOR ENCLOSED PARKING GARAGE VS OFFICE AREA
 WILL REQUIRE A 2 HR SEPERATION SEE TABLE 302.3.2. THIS
 AREA DOES NOT COUNT AS A INCIDENTAL AREA SINCE THE SQ
 FT AREA IS OVER THE ALLOWED 10% OF THE FIRST FLOOR
 AREA. PLEASE PROVIDE WALL AND OPENING PROTECTIVE
 PROTECTION. NOTE TO TAKE THE 1 HOUR REDUCTION ( TABLE
 302.1.1) ALLOWED IN INCIDENTAL AREAS AGAIN THE OFFICE
 AREA WOULD NEED TO BE LESS THAN10% OF THE FIRST FLOOR
 AREA.
  
 2B) ALSO NOTE THAT THE ENCLOSED PARKING GARARE WILL
 REQUIRE OCCUPANCY SEPERATION FROM THE 2ND FLOOR
 OCCUPANCY PLEASE REVIEW 711.3 FBC. THIS WILL ALSO
 INCLUDE THE COLUMNS HOLDING UP THE SECOND STORY.
 SECTION 302.3.2 EXCEPTION WILL ALLOW FOR A 1HR
 REDUCTION FOR THE BUILDING BEING EQUIPPED WITH A FIRE
 SPRINKLER SYSTEM. PLANS INDICATE THAT THE EXISTING
 BUILDING IS ALREADY FIRE SPRINKLERED AND THE SECOND
 STORY WILL BE FIRE SPRINKLERED,THE DESIGN TO BY
 OTHERS AND NOT PART OF THIS PERMIT. NO HOURLY
 REDUCTIONS CAN BE TAKEN IF THE FIRE SPRINKLER PLANS ARE
 NOT SUBMITTED WITH THE ADDITION PERMIT SET. NOTE THE
 FIRE SPRINKLER PLANS WILL ALSO REQUIRE SEPERATE PERMIT
 WITH THERE OWN PLANS.
  
 2C) THE SECOND STORY OCCUPANCIES, CONSIST OF ALSO MIXED
 USE BEING A OFFICE (BUSSINESS) AND WAREHOUSE (
 OCCUPANCY UNKNOWN). THE OFFICE ALO BEING OVER 10% OF
 THE 2ND FLOOR AREA, (NOT QUALIFYING AS A ANSILLARY USE)
 REQUIRING WALL RATINGS AS PER TABLE 302.3.2.
  
 2D) 2ND STORY WAREHOUSE USE AREA, PLEASE PROVIDE WHAT
 TYPE OF GOODS ARE TO BE STORED AND THE QUANITIES OF
 THESE GOODS. EACH AREA OF A BUILDING WITH MULITPLE USE
 AREAS EACH SHALL BE CLASSIFIED
 ACCORDING TO SECTION 302.3.2. WITH NOT HAVING THE
 WAREHOUSE OCCUPANCY KNOWN WE MAY HAVE ADDITIONAL
 COMMENTS AND OR RATINGS PERTAINING TO THE OCCUPANCNCY
 UES. 106.1.2 ADDITIONAL INFORMATION REQUIRED. PLANS DO
 NOT INDICATE THE STORAGE OF ANY FLAMMABLE LIQUIDS
 (GASOLINE)?
  
 3) THE SECOND FLOOR BEING A WAREHOUSE AND LIVE LOAD OF
 125 LBS- SQ FT LOADING:
 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. IT
 SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F
 OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR
 LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART OF
 A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS
 PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE
 BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVEDOR DEFACED, & IF
 LOST, REMOVED THE OWNER OF THE BUILDING SHALL REPLACE
 THEM.
  
 4) EXISTING BUILDING CODE 906.1 THE MINIMUM
 REQUIREMENTS. ADDITIONS TO EXISTING BUILDING OR
 STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE BUILDING.
 SUBMITTEDARE MANUAL J OR RESIDENTIAL HVAC FOR
 COMMERCIAL PLEASE USE MANUAL N. ADDITIONAL COMMENTS MAY
 APPEAR WITH THE CORRECT VERSION OF ENERGY CALCS.
  
 5)THE FIRST FLOOR IS A ENCLOSED PARKING GARAGE AND
 WILL NEED TO MEET THE REQUIREMENTS OF 406.4
 FBC-MECHANICAL FOR VENTILATION.
  
 6)NEITHER SHEET 3 NOR 3A INDICATES THE USAGE OF THE
 ROOM. 106.1.2. ADDITIONAL INFO. PLANS WILL NEED TO SHOW
 THE HOW MANY SQ FT ARE GOING TO BE OFFICE AND LAYOUT OF
 OFFICE, THIS MAY ENACT
 ACCESSIBILITY ISSUES.
  
 7) SHEET A4 & A5 BOTH INDICATE ROOF PLANS BUT NEITHER
 PLANS INDICATES ROOF DRAINAGE, THE NEW UPPER ROOF RUNS
 OFF ON TO THE LOWER ROOF BUT THE PLANS DO NOT PROVIDE
 HOW THE WATER WILL BE REMOVED FROM THE LOWER ROOF AREA?
 ROOF DRAINS WITH SECONDARY OVER FLOWS OR THROUGH THE
 WALL SCUPPERS? 1504.3.
  
 8) PLEASE PROVIDE INFORMATION ON THE R-VALUE OF
 INSULATION TO BE PLACED AT THE ROOF? DETAIL A OF SHEET
 5 INDICATES A WOD FRAME WALL INSULATED BUT THE AREA
 ABOVE THE CEILING AND BELOW THE INSULATION AT THE ROOF
 LEVEL IS MISSING INSULATION. PLEASE PROVIDE INSULATION
 IN THIS AREA, IT APPEARS TO BE PART OF THE A/C
 SPACE.13-402.1.A
  
 9) . SHEET A5 CUT SECTIONS DIDN'T INDICATE FLOOR
 INSULATION ON THE AIR CONDITIONED SECOND FLOOR, THIS
 WILL NEED TO MEET EITHER 13-405.1.AB.1 WHERE THERE ARE
 TRADE OFFS UNDER THE ENERGY CODE COMPLIANCE FORMS,
 PLEASE UPDATE THE ENERGY FORMS WITH THECOMMERCIAL
 FORM.
  
 10)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOFING ASSEMBLIES
 B) TRUSS ANCHORS AND OR STRAPS
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 12)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 13) CLOTH OR CANVAS AWNINGS: A LETTER FROM THE OWNER
 (NOT TENANT) IS TO ACCOMPANY ALLFABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED
 PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF
 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE
 OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH.
  
 14) GUARDRAILS AT THE PARAPET PLEASE PROVIDE HOW
 ATTACHMENT TO THE EXISTING BUILDING WILL BE COMPLETED
 WITH COMPLIANCE TO: 1607.7.1.1 CONCENTRATED LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST
 A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN),
 APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP,
 AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO
 TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING. THIS LOAD NEED NOT BE ASSUMED
 TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN THE
 PRECEDING PARAGRAPH.
  
 15) BUILDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-02-05 Cont ID  
Sent By dpalmer Date 2009-02-05 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2009-02-05 Time 11:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-02-04 Cont ID  
Sent By dpalmer Date 2009-02-04 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2009-02-04 Time 15:25 Sent To PC
Notes
2009-02-04 15:26:05PLANS AND CALCULATIONS ON HOLD.
 SPOKE TO MECHANICAL CONTRACTOR; HE WILL COME IN TO SIGN
 AS HE IS LISTED AS THE LICENSE HOLDER RESPONSIBLE FOR
 CALCULATIONS. WHEN CALCULATIONS ARE NOT REQUIRED TO BE
 SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER AS NOTED
 IN FBC 13-103.1.1.1 THE ONLY OTHER PERSON PERMITTED IS
 THE LICENSE MECHANICAL CONTRACTOR.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-01-14 Cont ID  
Sent By dpalmer Date 2009-01-14 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2009-01-14 Time 16:00 Sent To  
Notes
2009-01-14 16:00:38** DENIED REVIEW OF REVISIONS**
  
  
 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.4. THE PLANS
 PREVIOUSLY AND STILL CONTAIN NOTES WHICH STATE ALL
 OUTSIDE LIGHTING IS TO BE CONTROLLED VIA PHOTO-SENSOR.
 HOWEVER THE PLANS NOW CONTAIN A TIME CLOCK. IS THE TIME
 CLOCK NOW THE ONLY CONTROL OR IS THE PHOTO-SENSOR ALSO
 PART OF THE TIME CLOCK?
 IF THE TIME CLOCK IS NOW THE ONLY CONTROL, THEN PER
 SECTION ABOVE THIS MUST BE A ASTRONOMICAL TIME CLOCK
 WITH A MINIMUM OF 10HR BATTERY BACK UP. THIS WAS
 BROUGHT UP ON INITIAL REVIEWS OF THE PROJECT HOWEVER
 PLANS WERE REVISED TO NOTE THE PHOTO-SENSORS.
 PLEASE VERIFY HOW THESE ARE INDEED CONNECTED.
  
 2) NOTE: PLEASE SEE 110.26 AS THE DISCONNECT NOW ON THE
 PLANS FOR NEW CONDENSING UNIT DOES NOT MEET MINIMUM
 CLEARANCES.
 NOT THE SAME ON MECHANICAL PLANS.
 3) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS AS
 THERE HAS BEEN AN INCREASE IN LIGHTING FOR EXTERIOR AS
 WELL AS INTERIOR LIGHTING. A REVISE FIXTURE LEGEND
 SPECIFIC TO ALL FIXTURES IS NEEDED.
 THE OTHER ITEM WHICH DOES NOT COORDINATE IS THE
 INTERIOR FLUORESCENT FIXTURES WHICH ARE NOTED AS 8FT ON
 PLANS AND 4FT ON LEGEND.
 PLEASE BE SURE TO SEE 13-415.2,13-415.2.ABC.1.1 AND
 .1.2 FOR INTERIOR LIGHTING.
 PLEASE BE SURE TO SEE 13-415.2, 13-415.2.ABC.1.3 FOR
 EXTERIOR LIGHTING.
  
 ** KEEP IN MIND THE A/C PLANS NOTES THIS SPACE AS
 OFFICE AND OTHER SHEETS STATE WAREHOUSE. THIS DOES
 AFFECT CALCULATIONS FOR PERMITTED LIGHTING LEVELS.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-28 Cont ID  
Sent By dpalmer Date 2008-07-28 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2008-07-28 Time 09:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-20 Cont ID  
Sent By dpalmer Date 2008-06-20 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 15:39 Sent To  
Notes
2008-06-20 15:39:18** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 STATE PREPARED BY MR. AMES BENNETT ARCHITECT HOWEVER
 THE SUBMITTED CALCULATIONS ONLY CONTAIN A SHOP DRAWING
 REVIEW STAMP AND ARE NOT SIGNED, DATED AND SEALED./
 PLEASE SEE13-103.1 FOR RESPONSIBLE DESIGNER WHO SHALL
 SIGN CALCULATIONS AND FOR SCOPE.
  
 ** PLEASE SEE IDR(INPUT DATA REPORT) WHICH HAS LESS
 LIGHTING THAN SHOWN ON PLANS. PLEASE ADJUST.
  
 2) NOTE: PLEASE VERIFY WHERE THE PHOTO-METRICS ARE
 SHOWN FOR NORMAL LEVELS ON STAIRS MEETING THE LIFE
 SAFETY CODE 7.8.1.3, 7.9.2.2. WHERE DID THE WORDING AND
 NUMBERS ADDED CAME FROM WHERE?
  
 ** PLEASE ALSO SEE THE NEW BATTERY BACK UP STAIR LIGHTS
 ARE NOW SHOWING A *10 HOUR* BACK UP.THIS IS NOT A
 CODE VIOLATION ALTHOUGH THE TYPE OF FIXTURES AS STATED
 CAN NOT PRODUCE 10HR BACK UP. THERE WAS NOTHING IN
 PREVIOUS COMMENTS WHICH REQUIRED 10HR BATTERY BACK UP
 FOR THESE STAIR LIGHTS. THE COMMENT HAD TO DO WITH
 10FOOT CANDLES OF LIGHT WHICH WAS REQUIRED.
 PLEASE COORDINATE PLANS, FIXTURES ETC.
  
  
 3) NOTE: PLACED CALL TO MR. TONY ZIA AT 3:18PM ON 6/20
 AND LEFT MESSAGE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By dpalmer Date 2008-04-25 Time 15:09 Rev Time 0.00
Received By dpalmer Date 2008-04-25 Time 15:09 Sent To  
Notes
2008-04-25 15:10:10** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE STATED
 ON PLANS.
 PLEASE SEE THE FOLLOWING WHICH ARE LISTED ARE TO BE
 SHOWN ON ELECTRICAL SHEETS AT A MINIMUM.
 NFPA-70
 NFPA-101
 NFPA-72 (WHERE APPLICABLE)
  
 2) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND ON PLANS
 FOR ALL FIXTURES, TYPES AND INPUT WATTAGES ON PLANS.
 PLEASE BE SURE TO SEE THE FOLLOWING COMMENT WHICH HAS
 DIRECT RELEVANCY.
 FBC 106.1.2, 106.3.5.1.2, FBC CHAPTER 13.
  
 3) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 NEED TO BE COMPLETED AND COORDINATE WITH THE PLANS.
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS REQUIRED. PLEASE SEE 13-415.2.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED AS IDR
 FOR THE REMAINDER OF THIS COMMENT.
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH INDICATES NO EXTERIOR
 LIGHTING. HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY
 SHOW EXTERIOR LIGHTING?
 FOR EXAMPLE:
 PLEASE EXPLAIN WHAT FIXTURES ARE THE 1 WATT FIXTURES AS
 SHOWN ON THE IDR. THE PLANS DO NOT INDICATE THESE 1
 WATT FIXTURES AS ENTERED.
 FOR EXAMPLE:
 PLEASE SEE THE METHOD OF CONTROL ON THE IDR IS SHOWN AS
 *MANUAL ON/OFF*. HOW IS THIS POSSIBLE WHEN THE PLANS
 CLEARLY SHOW THE METHOD OF CONTROL AS AUTOMATED AS
 REQUIRED PER 13-415.1.ABC.1.1, .1.2, AND .1.3.
 PLEASE SEE THE FIXTURES ON PLANS, FIXTURE LEGEND ETC
 AND VERIFY THESE FIXTURES AND WATTAGES AS NOTED ABOVE.
 THIS IS BEING EMPHASIZED ONCE AGAIN AS THIS IS ON OF
 THE LEADING FAILURE ITEMS FOR NON-ISSUANCE OF PERMIT
 FOR CONSTRUCTION.
 PLEASE SEE THE METHOD *A* SUBMITTED IS FOR WHOLE
 BUILDING COMPLIANCE. HOW IS THIS POSSIBLE WHEN ALL
 COMPONENTS ARE NOT ENTERED?
 PLEASE SEE 13-400.3.A, 13-400.3.B AND 13-400.3.C WHICH
 GIVE YOU INFORMATION ON WHICH VERSION MAY BE USED OR
 WHICH VERSION MAY NOT BE USED.
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES
 WITH RESPECT TO METHOD OF CALCULATIONS AND VERSION.
 ** PLEASE BE SURE THE SIGNATURE OF THE RESPONSIBLE
 DESIGNER IS ALSO ON THE CERTIFICATION SHEETS. THE
 INITIALS ARE NOT ACCEPTABLE. FBC 13-101 PLEASE ADJUST.
  
  
 ** THIS ARE SOME EXAMPLES AND IS NOT AN EXHAUSTED LIST
 OF ITEMS ON PLANS NOT COMPLETE AND ITEMS ON PLANS WHICH
 DO NOT COORDINATE WITH THE IDR AND ENERGY
 CALCULATIONS.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 METHOD OF CONTROLS FOR EXTERIOR LIGHTS.
  
 5) NOTE: PLEASE SEE THAT *NO* HAND DRAWN CHANGES ARE
 PERMITTED TO PLANS.
 PLANS ARE ALSO SIGNED DATED AND SEALED BY AN ARCHITECT.
 THE CHANGES MADE TO ALL PANELS IN PEN ARE NOT
 PERMITTED.
 FS 481.221
  
 6) NOTE: PLEASE LABEL ALL PANELS FOR IDENTIFICATION.
 EXAMPLE: PANEL A, B ETC
 PLEASE SEE THE SUB PANEL FED FROM THE PRIMARY PANEL IS
 SHOWN AS 80AMP ON RISER WHICH WAS CHANGED FROM WAS
 PRINTED AS 60AMP. PLEASE ALSO SEE THE PRIMARY PANEL
 SHOWS 60AMP BREAKER.
 PLEASE COORDINATE ALL PANELS.
 230.2E, 408.4 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
  
 7) NOTE: PLEASE SUBMIT AND SHOW PHOTO-METRICS MEETING
 MINIMUM COMPLIANCE WITH THE 2003 LIFE SAFETY CODE/
 NFPA-101 SECTIONS 7.8.1.3 AND 7.9.2.2
  
 8) NOTE: PLEASE BE SURE THE TITLE BLOCKS REFLECT THE
 ADDRESS OF THE PROPOSED SCOPE OF WORK. PLEASE SEE THE
 ADDRESS AS APPLIED IS 420 6TH STREET.
 PLEASE ADJUST
 FBC 106.5, FAC 61G1-16.004
  
 9) NOTE: PLEASE SHOW HOW LIGHTING FROM FIRST FLOOR TO
 SECOND FLOOR WILL BE CONTROLLED.
 LS 101 7.8
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-01-22 Cont ID  
Sent By mwennerg Date 2009-01-22 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2009-01-22 Time 14:12 Sent To  
Notes
2009-01-22 14:13:26REVISION DATED 1/6/09.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-08-12 Cont ID  
Sent By mwennerg Date 2008-08-12 Time 13:28 Rev Time 0.00
Received By mwennerg Date 2008-08-12 Time 13:28 Sent To  
Notes
2008-08-12 13:29:19PLANS RED-LINED REGARDING STAIR COMPLIANCE WITH NFPA
 101, SEC. 7.2.2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-03 Cont ID  
Sent By mwennerg Date 2008-07-03 Time 13:56 Rev Time 0.00
Received By mwennerg Date 2008-07-03 Time 13:56 Sent To  
Notes
2008-07-03 14:09:49***DENIED***
  
 SOME COMMENTS NEED TO BE ADDRESSED OR ACKNOWLEDGED;
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, PARKING
 GARAGES TO COMPLY WITH NFPA 88A WITH REGARD TO (2) HOUR
 SEPARATION TO OTHER AREAS.
  
 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS. PRESSURE APPLIED HORIZONTALLY.
  
 3) OK
  
 4) OK
  
 5) STAIRS TO COMPLY WITH NFPA 101, SECTION 7.2.2.
  
 6) OK
  
 7) OK
  
 8) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL PLEASE INCLUDE LAYOUT WITH THIS
 SUBMITALL.
  
 TO HELP EXPEDITE THE PLAN REVIEW PROCESS, IT WOULD BE
 HELPFUL TO PROVIDE A RESPONSE LETTER INDICATING HOW AND
 WHERE ON THE PLANS THE COMMENT WAS ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-16 Cont ID  
Sent By mwennerg Date 2008-05-16 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2008-05-16 Time 15:30 Sent To  
Notes
2008-05-16 15:43:01***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, PARKING
 GARAGES TO COMPLY WITH THE REQUIREMENTS OF NFPA 88A
 WITH REGARD TO (2) HOUR SEPARATION TO OTHER AREAS.
  
 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) PLEASE IDENTIFY THE OCCUPANCY CLASSIFICATION(S) PER
 NFPA 101.
  
 5) STAIRS TO COMPLY WITH NFPA 101, SECTION 7.2.2.
  
 6) PLEASE SHOW ADRESS NEW, OR EXISTING ON BUILDING THAT
 SHALL BE MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND
 CONTRASTING WITH BACKGROUND. FULL ADDRESS TO BE
 DISPLAYED IN TITLE BLOCK OF EACH SHEET.
  
 7) SHEET E-1 ILLUSTRATES SMOKE DETECTORS, DEVICES THAT
 ARE TIED INTO A FIRE ALARM SYSTEM. IF A FIRE ALARM
 SYSTEM IS PRESENT, PLEASE ADVISE OR CHANGE THE DEVICE
 IDENTIFICATION TO SMOKE ALARMS.
  
 8) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL. AN ATTACHED SHEET WAS NOT FOUND
 SHOWING THE FIRE SPRINKLER LAYOUT AS INDICATED ON SHEET
 2.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-02 Cont ID  
Sent By adarroug Date 2009-02-02 Time 10:38 Rev Time 0.00
Received By adarroug Date 2009-02-02 Time 10:38 Sent To E
Notes
2009-02-02 10:39:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-08 Cont ID  
Sent By adarroug Date 2009-01-08 Time 09:44 Rev Time 0.00
Received By adarroug Date 2009-01-08 Time 09:44 Sent To  
Notes
2009-01-08 09:46:34TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 08:29 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 08:29 Sent To  
Notes
2008-07-17 08:34:16TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 14:15 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 14:15 Sent To  
Notes
2008-06-05 14:15:51TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-16 Cont ID  
Sent By mwennerg Date 2008-05-16 Time 15:49 Rev Time 0.00
Received By mwennerg Date 2008-04-17 Time 14:29 Sent To  
Notes
2008-04-17 14:32:06TO "COMM" BD#52

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-01-29 Cont ID  
Sent By rregueir Date 2009-01-29 Time 18:47 Rev Time 0.00
Received By rregueir Date 2009-01-29 Time 18:47 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-30 Cont ID  
Sent By rregueir Date 2008-06-30 Time 14:21 Rev Time 0.00
Received By rregueir Date 2008-06-30 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-01 Cont ID  
Sent By rregueir Date 2008-05-01 Time 11:13 Rev Time 0.00
Received By rregueir Date 2008-05-01 Time 09:30 Sent To  
Notes
2008-05-01 11:13:13REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS ON PLANS SHOWING
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, VOLUME OF
 OUTSIDE AIR REQUIRED AND VOLUME OF OUTSIDE AIR PROVIDED
 IN ACCORDANCE WITH FBCM TABLE 403.3.
  
 2. A RESIDENTIAL MANUAL J LOAD CALCULATION HAS BEEN
 PROVIDED FOR THIS PROJECT. THIS IS NOT RESIDENTIAL
 CONSTRUCTION. A COOLING LOAD CALCULATION SHALL BE
 PERFORMED FOR NEWLY INSTALLED UNITS AS PER CRITERIA OF
 SECTION 3.1 OF APPENDIX 13-B OF THIS CHAPTER. THIS
 CALCULATION SHALL BE ATTACHED TO THE CODE COMPLIANCE
 FORM SUBMITTED TO THE BUILDING DEPARTMENT WHEN THE
 BUILDING IS PERMITTED IN ACCORDANCE WITH FBCB
 13-407.1.ABC.1. COOLING SYSTEM DESIGN LOADS, FOR THE
 PURPOSE OF SIZING HVAC SYSTEMS AND EQUIPMENT, SHALL BE
 DETERMINED IN ACCORDANCE WITH ONE OF THE PROCEDURES
 DESCRIBED IN CHAPTER 26 OF THE ASHRAE HANDBOOK OF
 FUNDAMENTALS OR ACCA MANUAL N, COMMERCIAL LOAD
 CALCULATION IN ACCORDANCE WITH FBCB CHAPTER 13 APPENDIX
 B SECTION 3.1.1.
  
 3. PAGE 3 SHOWS AN ALUMINUM PRE-ENGINEERED A/C STAND.
 THIS IS A STRUCTURAL COMPONENT AS DEFINED IN FAC RULE
 9B-72. THEREFORE A PRODUCT APPROVAL IS REQUIRED. THE
 PRODUCT APPROVAL SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THIS PROJECT AND
 SUBMITTED TO THIS OFFICE IN ACCORDANCE WITH FBCB
 106.3.3.
  
 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBCM 307.2.1 AND MEANS OF AUXILIARY OR
 SECONDARY DRAIN PROTECTION IN ACCORDANCE WITH FBCM
 307.2.3.
  
 5. PROVIDE SHUTOFF DAMPER CONTROL AT OUTSIDE AIR
 INTAKE. OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE
 IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. A GRAVITY
 OPERATED DAMPER IS ACCEPTABLE IN A SYSTEM WITH A DESIGN
 OUTSIDE AIR INTAKE CAPACITY OF 300 CFM OR LESS IN
 ACCORDANCE WITH EXCEPTION #2 OF THIS SECTION.
  
 6. ENERGY CALCULATIONS: THE CERTIFICATION PAGE IS NOT
 SIGNED BY THE PERSON WHO PREPARED THE ENERGY
 CALCULATIONS. THE PERSON PREPARING THE COMPLIANCE
 CALCULATION SHALL CERTIFY THAT THE PLANS AND
 SPECIFICATIONS COVERED BY THE CALCULATION, OR
 AMENDMENTS THERETO, ARE IN COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BUILDING CODE IN ACCORDANCE WITH FBCB
 13-103.1.1.
  
 7. ENERGY CALCULATIONS: THE BUILDING?S OWNER/AGENT HAS
 NOT SIGNED THE ENERGY CALCULATIONS ON THE
 CERTIFICATIONS PAGE. THE BUILDING?S OWNER, THE OWNER?S
 ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION IN ACCORDANCE WITH
 FBCB 13-103.1.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-24 Cont ID  
Sent By aaponte Date 2008-06-24 Time 13:48 Rev Time 0.00
Received By aaponte Date 2008-06-24 Time 13:48 Sent To  
Notes
2008-06-24 13:50:01PROVISO:
 PARKING SPACES SHALL BE STRIPPED ACCORDING TO CITY'S
 STANDARDS, AND DUMPSTER SHALL BE ENCLOSED ACCORDING TO
 CITY'S STANDARDS. COPY OF DUMPSTER ENCLOSURE
 REQUIREMENTS GIVEN TO THE APPLICANT.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By aaponte Date 2008-04-25 Time 16:25 Rev Time 0.00
Received By aaponte Date 2008-04-25 Time 16:25 Sent To  
Notes
2008-04-25 16:32:001. PLEASE PROVIDE A SURVERYWITH CURRENT SITE
 CONDITIONS.
 2. PLEASE CONTACT URBAN DESIGN STAFF AT 561-8221435 TO
 DISCUSS PROPOSED ADDITION AND INTENDED USE OF THE
 STRUCTURE.