Plan Review Details - Permit 08040435
| Plan Review Stops For Permit 08040435 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-04-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-21 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-21 |
Time |
17:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-04-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-17 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-17 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2008-04-17 17:21:11 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | | | | 1.SEE GENERAL LIMITATION #7.ENHANCED FASTENING IS | | | TO SPECIFIED BY AN ARCHITECT, ENGINEER, OR REGISTERED | | | ROOF CONSULTANT. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-04-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-16 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-16 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2008-04-16 17:00:33 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | | | | 1.TWO DIFFERENT APPROVED ASSEMBLIES WERE INCLUDED; | | | PAGE 6 FOR AN INSULATED SYSTEM, AND 41 FOR A NON | | | INSULATED SYSTEM. PLEASE PROVIDE ONE ASSEMBLY AND | | | SELECT WHICH FASTENING OPTION YOU ARE PROPOSING TO USE. | | | | | | | | | 2.PLEASE REVISE THE ENHANCED FASTENING LETTER TO | | | CLEARLY STATE WHAT THE FASTENING PATTERN IS.IT STATES | | | " . . . AT 4 INCHES ON LAPS AND 6 INCHES IN O.C. OF | | | SHEET, AND 4 INCHES SURROUNDING PERIMETER 4 FEET FROM | | | EAVE."IF YOU DO NOT UNDERSTAND WHAT THE ISSUE IS WITH | | | WHAT YOU HAVE SPECIFIED, PLEASE SEE THE NOA AND PROVIDE | | | LANGUAGE WHICH IS CONSISTENT WITH THE WAY THAT | | | FASTENING PATTERN IS WRITTEN. | | | | | | 3.VALUE HAS BEEN ADJUSTED BASED ON SQUARE FOOT AREA | | | OF ROOF; ADDITIONAL PERMIT FEES DUE. | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-04-16 |
|
|
Cont ID |
|
| Sent By |
swurafti |
Date |
2008-04-16 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
swurafti |
Date |
2008-04-16 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2008-04-16 14:52:35 | HISTORIC APPROVED BY JPAPA |
|
|
|