| 2008-05-01 15:12:25 | ** DENIEDREVIEW ** |
| | |
| | **** IMPORTANT**** |
| | PLEASE SEE COMMENTS BELOW: AS THERE IS INFORMATION, |
| | DOCUMENTS, PLANS ETC WHICH ARE NOT SUBMITTED SOME ITEMS |
| | FOR CODE COMPLIANCE CAN NOT BE REVIEWED AT THIS TIME. |
| | PLEASE SEE THE LIST OF COMMENT BELOW BASED ON PLANS AND |
| | DOCUMENTS WHICH WERE SUBMITTED. IT IS IMPORTANT TO |
| | UNDERSTAND THAT DUE TO MUCH NEED FOR CHANGES FOR CODE |
| | COMPLIANCE AND ITEMS WHICH CAN NOT BE REVIEWED THERE |
| | MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| | WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS SUBMITTED SHALL CONTAIN |
| | THE LATEST ADOPTED CODES UNDER THE FLORIDA BUILDING |
| | CODE ALONG WITH STATUTORY ADOPTED CODES. PLEASE SEE THE |
| | FOLLOWING SHALL BE STATED ON PLANS. SOME CODES BELOW |
| | ARE BEING REQUESTED TO BE STATED AND SHOWN ON |
| | ELECTRICAL AS WELL AS COVER SHEETS. |
| | 2004 FBC W/2007 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2003 NFPA-20 |
| | 2005 NFPA-70 |
| | |
| | PLEASE KNOW SOME SHEETS REFERENCE A FIRE PUMP AS NOTED |
| | ON E6.05 SEE NOTES WITH RESPECT TO ANY FIRE PUMP. |
| | PLEASE SEE THERE ARE SEVERAL SHEETS IN WHICH CODES ARE |
| | BEING REFLECTED FROM THE 1999 NFPA-70 (NEC). |
| | FOR EXAMPLE: |
| | PLEASE SEE E0.03 AND 0.04, NOTES FOR GROUNDING IS |
| | STATING 250.26 FOR SEPARATELY DERIVED SYSTEMS. THIS |
| | CHANGED IN THE 2002 AND 2005 NEC. |
| | PLEASE SEE THESE SAME SHEETS FOR NOTES ON WIRING WHICH |
| | REFLECTS 370.20/21 HOWEVER THIS IS NO LONGER IN EFFECT |
| | FOR EQUIPMENT AS STATED. THE 2002 AND 2005 WERE BOTH |
| | CHANGED AND THE SECTIONS 370 OF THE NEWER CODES |
| | ACTUALLY REFLECT THE CABLEBUS. |
| | ** THE IS ONLY A COUPLE OF EXAMPLES AND IS NOT AN |
| | EXHAUSTED LIST OF LOCATIONS. THIS IS GIVEN AS A BENEFIT |
| | ONLY AND IS IN NO WAY ALL POSSIBLE LOCATIONS. |
| | |
| | |
| | 2) NOTE: PLEASE BE SURE THE ADDRESS TO THE LOCATION OF |
| | THIS PROJECT IS LISTED ON ALL TITLE BLOCKS ON ALL |
| | SHEETS. |
| | PLEASE SEE FAC 61G1-16.004, 61G15-23.002, FBC ADMIN |
| | SECTION 106.5. |
| | |
| | 3) NOTE: PLEASE SEE THE COLOR CODING SHOWN ON E0.03 |
| | SHALL BE BROWN, PURPLE AND YELLOW FOR 277/480V |
| | SYSTEMS. |
| | ORANGE AS STATED IN NEC 110.15 IS ONLY FOR A |
| | *HIGH-LEG*. THE 277/480V IS NOT A HIGH-LEG. |
| | PLEASE KNOW AS THE NEC DOES NOT PROVIDED COLOR CODING |
| | FOR THIS PARTICULAR SYSTEM THE CITY OF WEST PALM BEACH |
| | ALONG WITH ALL OF PALM BEACH COUNTY HAD TECHNICAL |
| | AMENDMENTS WHICH WERE IN EFFECT FOR MORE THAN 30 YEARS. |
| | EVEN THOUGH THIS TECHNICAL AMENDMENT IS NO LONGER IN |
| | EFFECT IN KEEPING WITH COORDINATION, SAFETY AND |
| | CONTINUITY OF OTHER WIRING WHICH ALREADY EXISTS IN THIS |
| | AHJ PLEASE ADJUST. |
| | 90.4 |
| | |
| | 4) NOTE: PLEASE SEE E6.05 WHICH SHOWS GROUNDING DETAIL |
| | WHICH MENTIONS TO FIRE PUMP YET NO FIRE PUMP, |
| | ELECTRICAL FOR FIRE PUMP ETC WAS LOCATED ON ANY OTHER |
| | SHEET(S). |
| | IF A FIRE PUMP IS INDEED GOING TO BE INSTALLED PLEASE |
| | SUBMIT ALL INFORMATION INCLUDING MANUFACTURES SPECS/CUT |
| | SHEETS FOR SUCH SYSTEM/UNIT. |
| | PLEASE SEE 695 OF NFPA-70 AND ALL OF 2003 NFPA-20. |
| | |
| | 5) NOTE: PLANS ARE SPECIFICALLY CALLING FOR A *LIFE |
| | SAFETY* AND *EMERGENCY* TRANSFER SWITCHES YET THE PLANS |
| | DO NOT SHOW ANY GENERATOR. |
| | THERE IS NO ELECTRICAL ON THE EMERGENCY SIDE ON EITHER |
| | OF THE TRANSFER SWITCHES. IF THIS IS A TRUE LIFE SAFETY |
| | REQUIRED SYSTEM UNDER 700 OR 701, THEN THE GENERATOR |
| | AND ALL OTHER REQUIRED SHALL BE IN THE DESIGN FOR |
| | MINIMUM CODE COMPLIANCE UNDER NFPA-101, 20, 110, 70 |
| | ETC. |
| | PLEASE KNOW AS NO INFORMATION, SPECS, MANUFACTURES CUT |
| | SHEETS, ETC WAS SUBMITTED NO REVIEW OF *MINIMUM* CODE |
| | COMPLIANCE CAN BE DONE AT THIS TIME. IF THERE IS A |
| | LEGALLY REQUIRED SYSTEM OR LIFE SAFETY SYSTEM, PLEASE |
| | IDENTIFY AND INCLUDE ALL FOR MINIMUM CODE COMPLIANCE. |
| | IF LOADS ARE ONLY GOING TO BE OPTION STAND-BY THEN |
| | PLEASE ADJUST ALL PLANS ETC FOR CODE COMPLIANCE. PLEASE |
| | CAREFULLY REVIEW NEC 700,701 AND 702 FOR ACTUAL LOADS. |
| | *** IMPORTANT** |
| | PLEASE KNOW IF A GENERATOR IS GOING TO BE INSTALLED THE |
| | PLANS FOR ALL OTHER TRADES SHALL BE REVISED TO INCLUDE |
| | ANY SUCH UNIT. |
| | PLEASE BE SURE TO INCLUDE ELEVATIONS ON |
| | SITE/BUILDING/STRUCTURAL SHEETS. |
| | PLEASE BE SURE TO INCLUDE ON SITE PLANS FOR |
| | CIVIL/ZONING REVIEWS. |
| | PLEASE BE SURE TO INCLUDE SCREENING AS REQUIRED BY |
| | ZONING. |
| | PLEASE BE SURE TO INCLUDE STRUCTURAL SLAB DETAILS FOR |
| | UNIT, TIE DOWNS ETC. |
| | PLEASE BE SURE TO INCLUDE SIZE OF FUEL TANK AS |
| | DEPENDING ON SIZE THERE MAY BE NEEDS FOR REVIEW AND |
| | STAMP BY DERM. |
| | |
| | THE ITEMS LISTED ABOVE ARE NOT AN EXHAUSTED LIST AS |
| | THERE WILL BE COMMENTS FROM OTHER TRADES. THESE NOTES |
| | WILL BE FORWARDED TO OTHER TRADES. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| | BOTH TRANSFER SWITCHES. 90.7, 110.3, 700, 701, OR 702. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED. |
| | PLEASE KNOW AS THE BUILDING IS NOT BEING DONE AS A |
| | WHOLE BUILDING AND STILL INCLUDED SHELL SPACES METHOD |
| | *A* MAY NOT BE USED. |
| | PLEASE SEE 13-400.3.B, 13-400.3.C, 13-101.1.3, |
| | 13-101.1.6 ETC. |
| | PLEASE KNOW EVEN AS METHOD *A* WAS SUBMITTED IN THE |
| | INFORMATION SHOWN ON THE INPUT DATA REPORT AND |
| | CALCULATIONS DOES NOT CORRELATE WITH PLANS. |
| | PLEASE KNOW THE INPUT DATA REPORT WILL BE NOTED AS IDR |
| | FOR REMAINDER OF THIS COMMENT. |
| | PLEASE KNOW THAT ALL INFORMATION ON PLANS SHALL |
| | COORDINATE WITH THE IDR. ALL COMPONENTS OF THE BUILDING |
| | FOR ENERGY EFFICIENCIES SHALL BE INCLUDED. SOME |
| | EXAMPLES WILL BE GIVEN BELOW FOR ITEMS WHICH ARE |
| | MISSING |
| | FOR EXAMPLE: |
| | PLEASE SEE THE IDR WHICH ONLY SHOWS A TOTAL OF FOUR |
| | LIGHT FIXTURES. HOW IS THIS POSSIBLE WHEN THE IDR |
| | CLEARLY REQUIRES THE TYPES OF LUMINAIRES, THE NUMBER OF |
| | *EACH* OF THOSE LUMINAIRES, THE WATTAGE ON EACH OF |
| | THOSE LUMINAIRIES ETC. |
| | BASED ON THE IDR SUBMITTED THIS DOES NOT MEET THE |
| | *MINIMUM* REQUIRED. |
| | FOR EXAMPLE: |
| | PLEASE ONCE AGAIN SEE THE IDR WHICH SHOWS ONLY 16-42 |
| | WATT FIXTURES. HOW IS THIS POSSIBLE WHEN THE PLANS |
| | CLEARLY SHOW THE *Q* FIXTURE ALONE BEING 75W. PLEASE |
| | KNOW THAT *ALL* EXTERIOR LIGHTING IS REQUIRED BY CODE |
| | TO BE FIGURED INTO THE IDR FOR EXTERIOR CALCULATIONS |
| | AND ALLOWANCES. |
| | THE FIXTURES ON THE FIXTURE LEGEND ALSO INCLUDE OTHER |
| | EXTERIOR LIGHTS HOW THESE ARE NOT SHOWN. |
| | |
| | ** THIS IS ONLY TWO EXAMPLES. ONE FOR INTERIOR AND ONE |
| | FOR EXTERIOR AND THIS IS NOT AN EXHAUSTED LIST. THESE |
| | EXAMPLES ARE GIVEN AS A BENEFIT ONLY AND ARE NO WAY ALL |
| | ITEMS ON THE IDR WHICH DO NOT COORDINATE WITH THE |
| | SUBMITTED PLANS. |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES AS THERE ARE |
| | OTHER BUILDING COMPONENTS WHICH DO NOT COORDINATE. |
| | PLEASE SEE SECTIONS NOTED ABOVE ALONG WITH 13-415.2, |
| | 13-415.2.ABC.1.1, .1.1, AND .1.3. (ETC) |
| | |
| | ** AS THERE ARE SEVERAL ITEMS NOT YET COMPLETE ON PLANS |
| | THERE MAY VERY WELL BE ADDITIONAL COMMENTS ON THE |
| | FOLLOWING REVIEW. |
| | |
| | 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| | .1.4. |
| | PLEASE SUBMIT MORE INFORMATION ON PLANS FOR LIGHTING |
| | CONTROLS. THERE IS A NOTE ON E0.01 WHICH STATES ALL |
| | LIGHTING SHALL MEET CHAPTER 13, HOWEVER QUOTING THE |
| | CODE IN LIEU OF ACTUAL MINIMUM DESIGN IS NOT |
| | PERMITTED. |
| | PLEASE SEE AS NO SITE PARKING LOT LIGHTING WAS SHOWN ON |
| | PLANS COMPLIANCE WITH .1.4 AS NOTED ABOVE CAN NOT |
| | VERIFIED. ONCE PLANS ARE COMPLETE FOR ALL LIGHTING |
| | REVIEW OF ALL SYSTEMS ETC WILL BE REVIEWED. |
| | PLEASE SEE SOME EXAMPLES WILL BE GIVEN BELOW HOWEVER |
| | THESE ARE IN NO WAY AN EXHAUSTED LIST. |
| | FOR EXAMPLE: |
| | PLEASE SEE SEVERAL OUTSIDE OFFICES WHICH APPEAR TO SHOW |
| | A STANDARD LIGHT SWITCH. HOW DOES THIS DEVICE WORK AS |
| | AN OVER RIDE OR WITH THE SYSTEM AS PROPOSED? |
| | FOR EXAMPLE: |
| | PLEASE SEE SECTIONS OF CODES NOTED AS EACH FLOOR IS |
| | REQUIRED TO CONTAIN A SEPARATE SYSTEM IF LIGHTING |
| | CONTROL PANELS ARE TO BE INSTALLED. |
| | FOR EXAMPLE: |
| | PLANS NOTE THAT ALL LIGHTING SHALL BE TURNED OFF AND |
| | CODE DOES REQUIRE THIS. PLEASE VERIFY LIGHTING CONTROLS |
| | IN STAIRS AND OTHER LOCATIONS WHICH DO NOT APPEAR TO |
| | SHOW ANY CONTROLS. |
| | PLEASE SEE LIFE SAFETY CODE 101, 7.8.1.2.2 AND FBC |
| | 1016.1 FOR REQUIRED FAIL SAFE ON FOR EGRESS LIGHTING. |
| | FOR EXAMPLE: |
| | PLEASE KNOW THERE IS NOTHING IN THE CODE WHICH PERMITS |
| | NIGHT LIGHTS. THIS AHJ WILL PERMIT SOME NIGHT LIGHTS |
| | FOR SECURITY AS LONG AS LEVEL DOES NOT EXCEED 1 FT |
| | CANDLE AVG ON EGRESS PATHS. |
| | FOR EXAMPLE: |
| | PLEASE SEE NO OUTSIDE LIGHTING AND CONTROLS SHOWN FOR |
| | OTHER FIXTURES. SOME FIXTURES ON BUILDING ARE NOTED AS |
| | ON PHOTO-SENSOR HOW NOT ALL. THERE IS A LIGHTING |
| | CONTACTOR DETAIL HOWEVER NO ALL LIGHTING LISTED. |
| | |
| | AS NOTED THIS IS NOT AN EXHAUSTED LIST AND IS GIVEN AS |
| | A BENEFIT ONLY. |
| | |
| | 8) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR |
| | PANELS AND SERVICE. |
| | NEC 220, 220.12, 220.14, 220.42, 220.44 ETC |
| | PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT |
| | 125%. 215.3, 230.42 |
| | |
| | 9) NOTE: PLEASE SEE THAT THE LOCATION OF THE MAIN FOR |
| | THE BUILDING IS NOT ACCEPTABLE TO THIS AHJ. THE |
| | LOCATION OF THE MAIN IS NOT LOCATED AT THE NEAREST |
| | POINT OF ENTRANCE IN AN EMERGENCY. FIRE DEPARTMENT |
| | PERSONNEL MUST HAVE A QUICK AND READY ACCESS TO THE |
| | MAIN LOCATION WITHOUT A SUBSTANTIAL TRAVEL DISTANCE |
| | THROUGH A BUILDING WHICH MAY BE ON FIRE. |
| | PLEASE RELOCATED ACCESS, ADD ACCESS, ADD MAIN ETC. THIS |
| | MAY BE GONE OVER WITH THIS AHJ. |
| | 230.70,71, 72, 76, 79 ETC |
| | |
| | 10) NOTE: PLEASE SEE 110.26C2 AS THE DOOR SWING ON THE |
| | MAIN ELECTRICAL ROOM SHALL NOT SWING IN. |
| | THE DOOR IS REQUIRED TO SWING OUT AND IS REQUIRED TO |
| | CONTAIN PANIC HARDWARE ETC. |
| | PLEASE KNOW THE ROOM, EQUIPMENT; DOOR ETC WILL ALL |
| | DEPEND ON DESIGN TO COMPLY WITH NOTE #9 ABOVE. IN ANY |
| | CASE 1200AMP EQUIPMENT WILL BE REQUIRED TO CONTAIN |
| | DOOR(S) WITH OUT-SWING. |
| | |
| | 11) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR |
| | EGRESS STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS. |
| | PLEASE SE NFPA-101 7.8.1.3, 7.9.2.2 |
| | FAC 61G15-33.004 |
| | |
| | 12) NOTE: PLANS CONTAIN A NOTE ON RISER FOR GF |
| | PROTECTION OF MAIN HOWEVER PLEASE BE SURE TO INCLUDE |
| | SPECIFIC INFORMATION ON THE MDP/MAIN. |
| | 240.13, 230.95. |
| | PLEASE KNOW IF THERE ARE ANY REQUIRED LIFE SAFETY |
| | SYSTEMS, SELECTIVE COORDINATION PER 240.13. |
| | |
| | 13) NOTE: PLEASE SEE RISER WHICH SHOWS 800AMP OVER |
| | CURRENT PROTECTION ON PANEL 1-HEQ WHICH IS A 400AMP |
| | PANEL. HOW IS THIS POSSIBLE? |
| | 110.9, 90.4, 240.4 ETC |
| | |
| | 14) NOTE: PLEASE SEE RISER AND PANEL SCHEDULES AS ALL |
| | OF THESE PANELS ON THE SECONDARY SIDE OF THE |
| | TRANSFORMERS REQUIRE MAINS. |
| | THERE ARE SEVERAL CODE SECTIONS AND SOME EXAMPLES OF |
| | WHICH PANELS ARE GIVEN BELOW. |
| | 1L1, |
| | 1LEQ, |
| | 1LLS. ETC |
| | PLEASE SEE 240.21, 240.4, 310.16, 408.36 ETC |
| | THIS IS NOT AN EXHAUSTED EXAMPLE. |
| | |
| | 15) NOTE: PLEASE SEE THAT ALL CONDUCTORS ON THE |
| | SECONDARY SIDE OF TRANSFORMER SHALL TERMINATE IN OVER |
| | CURRENT PROTECTION AS NOTED ABOVE IN NOTE #14. THESE |
| | CONDUCTORS SHALL ALSO BE RATED FOR THAT OCP. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE CONDUCTORS GOING INTO *1L1* WHICH ARE |
| | SHOWN AS 500MCM. THESE CONDUCTORS PER 110.14, 110.3, |
| | AND 310.16 ARE ONLY RATED FOR 380AMPS. |
| | IN THIS PARTICULAR SCENARIO YOU MAY NOT GO TO THE NEXT |
| | SIZE UP WHEN THE OCP LISTED PER 240.6 DOES NOT |
| | COORDINATE WITH THE CONDUCTOR RATING. |
| | MUST MEET OR EXCEED OCP ON THE SECONDARY SIDE. (MIN |
| | 600MCM) |
| | |
| | 16) NOTE: PLEASE BE SURE TO COMPLETE NOTES ON PLANS PER |
| | 13-413.1.ABC.2.1 AND .2.2. |
| | THE NOTES ON ELECTRICAL SHEET COVER PAGE DOES PARTIALLY |
| | LIST THIS HOWEVER NOT ALL. |
| | PLEASE KNOW THIS WAS CONFIRMED WITH DCA/FBC AS THE |
| | EXACT WORDING AS LISTED IN THE CODE WAS THE INTENT TO |
| | HAVE LISTED ON PLANS. |
| | |
| | 17) NOTE: PLEASE SEE PANELS *1L1 AND 1L12* ON RISER |
| | APPEARS TO BE SHOWN AS A TWO SECTION PANEL HOWEVER PER |
| | THE PANEL SCHEDULE THESE ARE TWO SEPARATE PANELS AND |
| | EACH PANEL DOES NOT CONTAIN THE SAME PANEL RATING. ONE |
| | IS LISTED AS 400AMP AND THE OTHER AS 225AMP. PLEASE |
| | COORDINATE AND ADJUST. |
| | 110.3,90.7 ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 18) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR NEW OR |
| | EXISTING SITE LIGHTS. |
| | PLANS MENTION THIS HOWEVER AT THIS TIME THESE CAN NOT |
| | BE CONFIRMED. |
| | PLEASE SEE NOTES ABOVE WITH RESPECT TO LIGHTS, |
| | CALCULATIONS ETC. |
| | FBC 106.3.5.1.2 |
| | |
| | 19) NOTE: PLEASE SEE SITE ELECTRICAL PLANS SPECIFICALLY |
| | CALL FOR A GROUND RING AND TO SEE DETAIL ON E6.05 YET |
| | E6.05 DOES NOT SHOW ANY GROUND RING AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM DETAIL. |
| | PLEASE VERIFY ?? |
| | 250.50 |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 20) NOTE: PLEASE VERIFY SERVER ROOM. IS THIS AN IT ROOM |
| | AS DEFINED IN NFPA-75, NFPA-70? |
| | PLEASE SEE 645.1 AND .4. |
| | PLANS SHOW RATED WALLS, FIRE DAMPERS, A/C , FM 200 |
| | SYSTEM ETC HOWEVER NO SHUT OFF PER 645.10 WAS LOCATED |
| | ON PLANS. |
| | PLEASE KNOW THERE ARE SEVERAL UNANSWERED QUESTIONS WITH |
| | RESPECT TO THIS ROOM. |
| | |
| | 21) NOTE: PLEASE SEE NFPA-70 620.23 FOR REQUIRED |
| | DEDICATED CIRCUITS IN MACHINE ROOM. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE LIGHTING CIRCUIT FEEDING THIS ROOM |
| | CURRENTLY ALSO FEEDS SEVERAL OTHER LIGHTING FIXTURES |
| | OUTSIDE OF THIS ROOM WHICH IS NOT PERMITTED BY CODE. |
| | PLEASE KNOW THIS IS NOT A NEW CODE. PLEASE ADJUST |
| | PLANS. |
| | |
| | 22) NOTE: PLEASE SEE 620.24 WHICH REQUIRE DEDICATED |
| | CIRCUITS FOR PIT/HOIST-WAY LIGHTS AND RECEPTACLES. |
| | PLEASE SEE PLANS AS THE CIRCUIT WHICH FEEDS THE PIT GFI |
| | WHICH IS *1L1-30* ALSO FEEDS MECHANICAL ROOM |
| | RECEPTACLES, RECEPTION AREA ETC. |
| | PLEASE ADJUST; THIS IS NOT A NEW CODE. |
| | |
| | 23) NOTE: PLEASE SEE THE ELEVATOR MACHINE ROOM PER FBC |
| | 3006.2 IS REQUIRED TO CONTAIN SEPARATE CONDITIONING. |
| | PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER AS THIS |
| | WILL AFFECT ELECTRICAL PLANS AS NOTED. |
| | ** THIS IS BEING GIVEN FOR INFORMATION ONLY. |
| | |
| | 24) NOTE: PLEASE SEE CONDUCTORS ON RISER FOR |
| | TRANSFORMER *1TN* WHICH SHOWS 200AMP OCP ON MDP ON 1/0 |
| | CONDUCTORS WHICH ARE ONLY RATED FOR 150AMPS PER |
| | 310.16. |
| | PLEASE CORRECT AND ADJUST. |
| | THIS IS NOT WHAT IS SHOWN ON MDP SCHEDULE. MDP SCHEDULE |
| | INDICATES 150AMP BREAKER AND NOT 200AMP. |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION. |
| | |
| | 25) NOTE: PLEASE BE SURE TO COMPLETE THE CERTIFICATION |
| | SHEETS ON THE SUBMITTED ENERGY CALCULATIONS. |
| | THE COVER SHEET WAS SIGNED, DATED AND SEALED HOWEVER |
| | THIS SHOULD BE ON THE CERTIFICATION SHEETS. |
| | PLEASE ALSO SEE OTHER INFORMATION REQUIRE ON THESE SAME |
| | SHEETS SUCH AS OWNER/AGENT SIGNATURE IS REQUIRED. FBC |
| | 13-103.1.1.1, FAC 61G15-23.002 |
| | |
| | 26) NOTE: PLEASE BE SURE TO STATE ALL MAXIMUM TIMES ON |
| | OVER RIDE DEVICES. PLEASE SEE THE LOCATIONS OF EACH |
| | OVER RIDE SHALL BE LOCATED SO THE OCCUPANT CAN VISUALLY |
| | SEE THE LIGHTING IN WHICH THEY ARE CONTROLLING. THERE |
| | ARE EXCEPTIONS ON THE CODE HOWEVER NO INFORMATION COULD |
| | BE LOCATED ON PLANS ON HOW *PILOTS/INDICATORS LIGHTS* |
| | WILL BE USED OR INSTALLED. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| | |
| | 27) NOTE: PLEASE SEE SYMBOL LEGEND MENTIONS THE USE OF |
| | WHAT APPEARS TO BE A SPRING WOUND TIMER FOR SOME |
| | LOCATIONS. |
| | PLEASE SEE FBC 11-4.27.4 WHICH DOES NOT PERMIT THE USE |
| | OF THESE DEVICES. |
| | THIS MAY ALSO BE LIMITED TO SOME LOCATIONS AS PERMITTED |
| | BY CODE. |
| | |
| | 28) NOTE: PLEASE SUBMIT AND PROVIDE AN ENLARGED |
| | ELECTRICAL ROOM PLAN TO SCALE FOR THE MAIN ELECTRICAL |
| | ROOM. |
| | BASED ON THE EQUIPMENT SHOWN AND MINIMUM CLEARANCES |
| | REQUIRED IN 110.26 THERE IS CONCERN OVER THE SIZE OF |
| | THE ROOM AND EQUIPMENT AS SHOWN. |
| | PLEASE SEE MANUFACTURES MINIMUM CLEARANCE FOR |
| | TRANSFORMER, VENTILATION ETC. |
| | PLEASE SEE 110.26, 450.9, 450.13, 450.21 ETC. |
| | |
| | 29) NOTE: PLEASE SEE SHEET E1.03 WHICH APPEARS TO USE A |
| | SQUARE BOX WITH A C INSIDE AS ONE OF THE SYMBOLS LOCATE |
| | AT DOOR. THIS SYMBOL ON E0.02 MENTIONS THIS IS A |
| | LIGHTING CONTACTOR. WHAT IS THIS? |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 30) NOTE: PLEASE SEE SYMBOLS ON THE SHEET E1.03 AS |
| | THERE ARE DEVICES WHICH APPEAR TO PARTIAL FIRE |
| | DEVICES. |
| | FOR EXAMPLE: |
| | PLEASE SEE STAIR #2 WHICH SHOWS A PARTIAL FIRE DEVICE. |
| | THIS IS ONE EXAMPLE: |
| | |
| | 31) NOTE: PLEASE INCLUDE MAXIMUM HEIGHT FOR ALL DEVICES |
| | PER ADA 11-4.27. |
| | PLEASE PLACE NOTE ON PLANS TO INCLUDE. |
| | |
| | 32) NOTE: PLEASE CLARIFY THE *SPECIAL OUTLET* IN THE |
| | BREAK-ROOM KITCHEN AREA. 1L12, 8, 10,12. |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 33) NOTE: PLEASE PLACE NOTES ON PLANS FOR THE FOLLOWING |
| | PER FBC SECTION 2704.1 WHICH REQUIRES BONDING OF METAL |
| | FRAMING MEMBERS. |
| | METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT |
| | GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE |
| | THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE |
| | NATIONAL ELECTRIC CODE, TABLE 250.122. FOR THE PURPOSE |
| | OF THIS SECTION, A GROUNDED METAL OUTLET BOX ATTACHED |
| | TO THE FRAMING SHALL BE PERMITTED. |
| | |
| | 34) NOTE: PLEASE KNOW DUE TO THE EXTENT OF THE COMMENTS |
| | ABOVE, ONE ROLL OF PLANS ARE BEING RETAINED BY THIS |
| | OFFICE ALONG WITH ONE SET OF ENERGY CALCULATION |
| | SUBMITTED. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |