Plan Review Details - Permit 08040391
Plan Review Stops For Permit 08040391
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-24 Cont ID  
Sent By jwitmer Date 2009-07-24 Time 09:31 Rev Time 0.66
Received By jwitmer Date 2009-07-24 Time 09:31 Sent To PC
Notes
2009-07-24 09:33:33SHEET S-1, REVISION# 1 PLAN DATED : 7/14/09

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-02-04 Cont ID  
Sent By jwitmer Date 2009-02-04 Time 11:12 Rev Time 1.33
Received By jwitmer Date 2009-02-04 Time 11:12 Sent To  
Notes
2009-02-04 11:14:40BUILDING PROVISO: PROVIDE PRODUCT APPROVAL FOR NEW ROOF
 HATCH (96"X72") PER RULE 9B-72(31)(A) & 1609.6.2.2.
 PROVIDE BEFORE FRAMING INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-12-24 Cont ID  
Sent By jwitmer Date 2008-12-24 Time 09:57 Rev Time 2.22
Received By jwitmer Date 2008-12-24 Time 09:57 Sent To  
Notes
2008-12-24 09:58:46BUILDING PLAN REVIEW
 PERMIT: 08040391
 ADD: 1001 OKEECHOBEE BLVD
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 DEC.24/2008
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) THE COMPUTATIONS SUBMITTED PAGE 28 FROM SSMA ARE A
 GENERIC TABLE THEY DO NOT REFLECT THE VALUES OF THE
 SCREW TYPE OF ALLOY, GRADE OF MATERIAL SHOULD BE
 VERIFIED BY THE MANUFACTURER. I'VE SPOKEN WITH FORD
 FASTENERS ABOUT THE 1000 STEEL SELF DRILLING SCREW, NO
 VALUES WOULD BE GIVEN BECAUSE THERE HAS BEEN NO TESTING
 FOR THIS FASTENERS. THE SECOND ISSUE IS THE ALTIMATE
 FAILURE STRENGTH VERSES THE DESIGN LOADS OF THE
 FASTENERS BEING USED.
  
 IN THE TABLE SUBMITTEDON PAGE 28 THE THE LINE FOR 43
 MILS IS CIRCLED TOR THICKNESS OF MATERIAL VERES A # 10
 SCREW. SCREW TABLE NOTES ,WHEN CONNECTING MATERIALS OF
 DIFFERENT STEEL THICKNESS OR TENSILE STRENGTH (FU) THE
 LOWEST APPLICABLE VALUES SHOULD BE USED. THE TENSILE
 STRENGTH INDICATED FY+33KSI SHOUD BE USED NOT THE
 43MIL. THIS REDUCES THE PULLOUT TO 66 AND SHEER TO 140.
  
 THE NEST ISSUE IS THE PULL OUT VALUE IS LISTED AS 109
 FOR A #10 SCREW THE SAFETY FACTOR AND THE SAME WITH
 SHEAR VALUES. THE DESIGNER IS TAKING THE ULTIMATE
 FAILURE PRESSURES BY MULTIPLYING THEMBY THREE
 AND THEN CUTTING THE PRESSRES IN HALF THEN MULTIPLYING
 THEM AGAIN BY 1.33 THERE IS NO SAFETY FACORS BUILT INTO
 THE EQUATION.THE THIRD ISSUE IS 33% INCREASE IS TAKEN
 FOR THE FASTENERS. 1605.3.1.1. PLEASE REVIEW SIMILAR
 PROJECT 08070134 WHERE THE SAME VALUES WERE TAKEN.
 1604.1 GENERAL.
 BUILDING, STRUCTURES AND PARTS THEREOF SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH STRENGTH
 DESIGN, LOAD AND RESISTANCE FACTOR DESIGN, ALLOWABLE
 STRESS DESIGN, EMPIRICAL DESIGN OR CONVENTIONAL
 CONSTRUCTION METHODS, AS PERMITTED BY THE APPLICABLE
 MATERIAL CHAPTERS.
  
 THE DESIGN LOADS ON THE PANELS ARE ACTING THE SAME WAY
 AS SHEAR WALLS ACT, SO THE ALLOWABLE STRESS DESIGN.
 2211.2.1 DESIGN SHEAR DETERMINATION.
 WHERE ALLOWABLE STRESS DESIGN (ASD) IS USED, THE
 ALLOWABLE SHEAR VALUE SHALL BE DETERMINED BY DIVIDING
 THE NOMINAL SHEAR VALUE, SHOWN IN TABLES 2211.2(1) AND
 2211.2(2) BY A FACTOR OF SAFETY (OMEGA) WHICH SHALL BE
 TAKEN AS 2.50. ALSO SEE FOOTNOTEA TABLE 2211.2.1. FOR
 SAFETY FACTORS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 09:26 Rev Time 0.75
Received By jwitmer Date 2008-10-20 Time 09:26 Sent To  
Notes
2008-10-20 09:39:13BUILDING PLAN REVIEW
 PERMIT: 08040391
 ADD: 1001 OKEECHOBEE BLVD
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) THE COMPUTATIONS SUBMITTED DOES NOT PROVIDE THE PULL
 OUT AND SHEER VALUE, TYPE OF MATERIAL NOR SIZE OF
 MACHINE SCREW, PLEASE PROVIDE THE MANUFACTURERS CUT
 SHEET WITH THESE SPECIFICATION REQUIREMENTS. NOTED
 SHEETS 23-25 DO INDICATE A # 10 SCREW BUT THE
 CALCULATION SHEETS DO NOT INDICATE TYPE OF SCREWS TO BE
 INSTALLED. 106.1.2* ADDITIONAL INFORMATION REQUIRED.
 1609.6.2.2 COMPONENTS AND CLADDING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By jwitmer Date 2008-04-28 Time 07:13 Rev Time 2.22
Received By jwitmer Date 2008-04-28 Time 07:13 Sent To  
Notes
2008-04-28 07:47:26BUILDING PLAN REVIEW
 PERMIT: 08040391
 ADD: 1001 OKEECHOBEE BLVD
 CONT: ANDERSON-MOORE
 TEL: (561)753-7400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) PLEASE SEE THE ATTACHED DECLARATORY STATEMENT
 REGAURDING MECHANICAL EQUIPMENT EXPOSED TO WIND
 PRESSURES, CONCLUSION OF LAW. CONCLUSIONOF LAW# 5
 1609.1STRUCTURES AND PARTS THEREOF SHALL BE DESIGNED TO
 WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED HEREIN. THE
 MAIN BUILDING, AND A/C STAND ARE DESIGNED FOR WIND
 PRESSURES BUT NO INFORMATION HAS BEEN PROVIDED FOR THE
 NEW RTU UNIT ( THE CABINET OR SHELL OF THE UNIT) .
 PLEASE PROVIDE TESTING REPORTS OR AN ENGINEER'S
 RATIONAL ANYLISIS. NOTE THIS IS TO BE CONSIDERED
 COMPONENTS AND CLADDING JUST AS A SKYLIGHT, WINDOW OR
 ROOF HATCH, IF BLOWN OFF OF THE ROOF LEAVING A LARGE
 HOLE IN THE ROOF ALLOWING PRESSURES TO BUILD WITHIN THE
 BUILDING WHERE THE BUILDING IS DESIGNED AS A AN
 ENCLOSED STRUCTURE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-08-13 Cont ID  
Sent By btrobaug Date 2009-08-13 Time 07:50 Rev Time 0.00
Received By btrobaug Date 2009-08-13 Time 06:50 Sent To  
Notes
2009-08-13 07:53:56 
  
 TO LUIS OFFICE./WRT.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 11:15 Sent To B
Notes
2009-03-24 11:17:20PLANS ROUTED TO BUILDING AS THE THIRD SET DOES NOT
 CONTAIN ANY BUILDING STAMPS
2009-03-24 11:15:18** PLANS REDLINED **
  
 THE ELECTRICAL SYSTEM/RISER NEEDS TO BE VERIFIED. THE
 ORIGINAL PLANS CALLED FOR A LIFE SAFETY/ EMERGENCY
 TRANSFER SWITCH HOWEVER PER THE ENGINEER MR. LON CARTER
 AND PER PLANS THERE ARE NO EMERGENCY/ 700 SYSTEMS ON
 THE BACK UP GENERATOR. THIS NEEDS TO BE VERIFIED AS
 THIS WILL AFFECT THE SYSTEMS AS SHOWN.
 NEC 700.9 REQUIRES SYSTEMS TO BE SEPARATED.
 IF THERE ARE ANY ITEMS SUCH AS EMERGENCY LIGHTING ON
 THE LEGALLY REQUIRED TRANSFER SWITCH THIS MAKES THIS A
 700 SYSTEM. ADJUSTMENTS MAY BE NEEDED AT A LATER DATE.
 BASED ON PLANS, THERE ARE ONLY 701 AND 702 SYSTEMS ON
 THE GENERATOR. IT IS IMPORTANT THESE ITEMS BE VERIFIED
 FOR CODE COMPLIANCE.
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-02-12 Cont ID  
Sent By dpalmer Date 2009-02-12 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2009-02-12 Time 17:05 Sent To  
Notes
2009-02-12 17:06:06** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE PREVIOUS NOTES. NOT ALL INFORMATION
 ON WHAT PANELS ARE BEING FED FROM THE 700, 701 AND 702
 SYSTEMS.
 THE EMDP AND ATS IS NOW LABELED AS LEGALLY REQUIRED
 HOWEVER BASED ON THE STAIRWELL LIGHTING ALONE THESE ARE
 700 LOADS WHICH ARE EMERGENCY/LIFE SAFETY LOADS.
 PLEASE SEE 700.9 AS 700 SYSTEMS ARE NOT PERMITTED TO BE
 WITH 701 SYSTEMS.
 PLEASE PROVIDE WHAT IS ON ALL PANELS FED FROM ATS-LS.
 TYPICALLY THE LS DESIGNATION IS FOR LIFE SAFETY NOT
 LEGALLY REQUIRED.
 WHAT ARE THE LOADS ON PANELS E-1, E-2 AND E-3.
 PLEASE ALSO SEE THE PANEL SCHEDULES FOR D1B AND D1A.
 WHERE ARE THE PANEL SCHEDULES? WHAT LOADS DO THESE
 PANELS FEED?
  
  
 ** THIS BEING A HIGH RISE BUILDING WHERE ARE THE
 SYSTEMS SUCH AS EXHAUST FANS, STAIR PRESSURIZATION ETC
 FED FROM?
  
 408.4, FBC 106.1.1, 106.1.2, 106.3.5.1.2 FOR CLARITY,
 COORDINATION AND ADDITIONAL INFORMATION NEEDED.
  
 *** THERE IS STILL NOT COMPLETE INFORMATION FOR REVIEW.
 THERE MAY BE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 10:12 Sent To  
Notes
2008-12-26 10:12:40** DENIED**
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW. THE
 RISER IS NOT COMPLETE WITH ALL DEFINED LOADS, LOAD
 SHEDDING, DESIGNATION OF LEGALLY REQUIRED OR OPTIONAL
 STAND-BY SYSTEMS.
 BASED ON THE ITEMS LISTED ON PANEL HEQ ALL OF THESE
 APPEAR TO BE OPTIONAL STAND-BY LOADS.
 WHAT DOES PANEL D-2 FEED?
 WHAT ABOUT LOADS ON T8 TRANSFORMER, ARE THESE LEGALLY
 REQUIRED OR OPTIONAL STAND-BY?
 THE NEXTEL MAY OR MAY NOT BE LEGALLY REQUIRED DEPENDING
 ON THE TIME IN WHICH IT WAS INSTALLED.
  
 PLEASE SEE DIAGRAM IN 700.9B OF THE 2005 NEC HANDBOOK.
  
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 08:12 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 08:12 Sent To  
Notes
2008-10-28 08:13:06 
 ** DENIED 2ND REVIEW**
  
  
 1) NOTE: NEW NOTE WHICH WAS NOT PART OF THE PREVIOUS
 REVIEW.
 PLEASE SEE NEC 700.9B THE AHU MAY NOT BE FED FROM THE
 LIFE SAFETY PANEL OR EQUIPMENT. PLEASE KNOW THIS LOAD
 IS NOT A LIFE SAFETY OR LEGALLY REQUIRED LOAD. PLEASE
 ADJUST RISER TO INCLUDE EQUIPMENT TO CREATE AN
 *OPTIONAL STAND-BY* SYSTEM WHICH STILL MAY BE FED FROM
 THE SAME GENERATOR IF THE LOAD AND SIZE OF GENERATOR
 PERMITS WITHOUT LOAD SHEDDING.
 THIS COMMENT WILL SUBSTANTIALLY CHANGE THE CIRCUITING,
 RISER ETC.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By dpalmer Date 2008-04-25 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2008-04-25 Time 10:51 Sent To  
Notes
2008-04-25 10:52:30** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE ADDRESS ON THE MEP PLANS STATE
 630 CLEARWATER PARK. PLEASE KNOW THE ADDRESS OF THIS
 PROPOSED SCOPE OF WORK IS 1001 OKEECHOBEE BLVD. PLEASE
 ADJUST PLANS/TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002 *** THIS IS REQUIRED TO
 BE CORRECTED ON ALL MEP PLANS WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER TRADE.
 FBC 106.3.5, 106.5
  
 2) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE STATED
 ON PLANS.
 PLEASE SEE THE FOLLOWING WHICH ARE LISTED ON PLANS DO
 NOT SHOW ANY CODES.
 NFPA-70
 NFPA-101
 NFPA-72
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-02-20 Cont ID  
Sent By mawillia Date 2009-02-20 Time 12:25 Rev Time 0.00
Received By mawillia Date 2009-02-20 Time 12:09 Sent To  
Notes
2009-02-20 12:12:13*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEET M0.1 WAS STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-10-29 Cont ID  
Sent By mawillia Date 2008-10-29 Time 15:46 Rev Time 0.00
Received By mawillia Date 2008-10-29 Time 15:21 Sent To  
Notes
2008-10-29 15:36:41*****UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3. ON THE APPROPIATE "M" SHEET(S), INCLUDE VERBAGE
 THAT: DUCT SMOKE DETECTORS SHALL SHALL INITIATE A
 GENERAL FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-05-15 Cont ID  
Sent By mawillia Date 2008-05-15 Time 16:17 Rev Time 0.00
Received By mawillia Date 2008-05-15 Time 15:57 Sent To  
Notes
2008-05-15 16:15:33*****PROVISO*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3. ON THE APPROPIATE "M" SHEET(S), INCLUDE VERBAGE
 THAT: DUCT SMOKE DETECTORS SHALL SHALL INITIATE A
 GENERAL FIRE ALARM.
  
  
 FIRE PLAN REVIEW WILL BE APPROVED ( P STATUS IN THE
 SYSTEM) WHEN THE ABOVE COMMENTS HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-05-04 Cont ID  
Sent By kstevens Date 2009-05-04 Time 16:35 Rev Time 0.00
Received By kstevens Date 2009-05-04 Time 16:35 Sent To  
Notes
2009-05-04 16:36:04TRACPIPE SUBMITTALS OK

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-10-09 Cont ID  
Sent By mperson Date 2008-10-09 Time 08:57 Rev Time 1.30
Received By mperson Date 2008-10-09 Time 08:57 Sent To  
Notes
2008-10-09 09:09:51****************PROVISO****************
 SHEET P2.1 GAS PLAN IS COMPLIANT, HOWEVER TWO COPIES OF
 MANUFACTURE SPECIFICATION SHEETS (THREE COPIES REQUIRED
 IF THIS IS A THRESHOLD BUILDING WITH A THRESHOLD
 INSPECTOR) OF THE VENMAR OARTU-1 UNIT ARE REQUIRED AT
 THE TIME OF GAS PERMIT APPLICATION FOR REVIEW BEFORE
 THE GAS PERMIT WILL BE ISSUED. MANUFACTURE
 SPECIFICATION SHEETS SHALL CLEARLY INDICATE THE UNITS
 MAKE, MODEL NUMBER, GAS BTU LOAD CAPACITY, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 SUCH AS AGA, CSA, OR UL.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-04-18 Cont ID  
Sent By mperson Date 2008-04-18 Time 16:06 Rev Time 0.00
Received By mperson Date 2008-04-18 Time 16:06 Sent To  
Notes
2008-04-18 16:38:20GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 NOTE: SHEET M0.2, M.2.3, AND P2.1 ARE INDICATING 1"
 NATURAL GAS TO THE OARTU-1 CHILLED WATER UNIT.
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 ON THE GAS ISOMETRIC. PER FBC FUEL GAS SECTION 401.1
 SCOPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM
 IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS
 CONNECTING TO.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM
 IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS
 CONNECTING TO.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: IF NATURAL GAS DELIVERY PRESSURE IS 2 PSI OR
 MORE PLEASE PROVIDE TWO COPIES OF THE MP REGULATOR
 MANUFACTURER'S SPECIFICATIONS THAT CLEARLY INDICATE THE
 MAKE MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 *NOTE: PROVIDE TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS OF THE NEW CHILLED WATER OARTU-1
 UNIT THAT CLEARLY INDICATE THE MAKE, MODEL NUMBER, BTU
 CAPCITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-09-01 Cont ID  
Sent By kstevens Date 2009-09-01 Time 14:05 Rev Time 0.00
Received By kstevens Date 2009-09-01 Time 14:05 Sent To  
Notes
2009-09-01 14:07:18SENT TO RREGUEIRO.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-08-12 Cont ID  
Sent By lmartine Date 2009-08-12 Time 08:33 Rev Time 0.00
Received By lmartine Date 2009-08-12 Time 08:33 Sent To  
Notes
2009-08-12 08:42:02GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-07-24 Cont ID  
Sent By jwitmer Date 2009-07-24 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2009-07-22 Time 13:49 Sent To  
Notes
2009-07-22 13:52:22B-1

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-20 Cont ID  
Sent By swurafti Date 2009-04-20 Time 16:44 Rev Time 0.00
Received By swurafti Date 2009-04-20 Time 16:44 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-16 Cont ID  
Sent By adarroug Date 2009-03-16 Time 10:07 Rev Time 0.00
Received By adarroug Date 2009-03-16 Time 10:07 Sent To E
Notes
2009-03-16 10:08:05TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-23 Cont ID  
Sent By adarroug Date 2009-01-23 Time 11:15 Rev Time 0.00
Received By adarroug Date 2009-01-23 Time 11:15 Sent To  
Notes
2009-01-23 11:19:07TO "COMM" BD#35

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-05 Cont ID  
Sent By adarroug Date 2008-12-05 Time 15:37 Rev Time 0.00
Received By adarroug Date 2008-12-05 Time 15:37 Sent To  
Notes
2008-12-05 15:44:25TO "COMM" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 12:57 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 12:57 Sent To  
Notes
2008-10-02 12:59:46TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-15 Cont ID  
Sent By mawillia Date 2008-05-15 Time 15:57 Rev Time 0.00
Received By mawillia Date 2008-04-15 Time 15:11 Sent To  
Notes
2008-04-15 15:14:39TO "COMM" BD#46

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-08-15 Cont ID  
Sent By rregueir Date 2009-08-15 Time 15:43 Rev Time 0.00
Received By rregueir Date 2009-08-15 Time 15:40 Sent To PC
Notes
2009-08-15 15:43:44**PROVISO**
  
 NEW VAV BOXES SHALL BE ACCESSIBLE FOR SERVICE,
 MAINTENANCE OR REPLACEMENT WITHOUT REMOVAL OF OTHER
 PERMANENTLY INSTALLED EQUIPMENT OR ELEMENTS OF
 PERMANENT CONSTRUCTION IN ACCORDANCE WITH FBC-M 306.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-02-21 Cont ID  
Sent By rregueir Date 2009-02-21 Time 17:09 Rev Time 0.00
Received By rregueir Date 2009-02-21 Time 17:09 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-01-11 Cont ID  
Sent By rregueir Date 2009-01-11 Time 12:18 Rev Time 0.00
Received By rregueir Date 2009-01-11 Time 12:16 Sent To PC
Notes
2009-01-11 12:18:41REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 MECHANICAL REVIEW WILL REMAIN IN FAIL STATUS PENDING
 COMPLETED PASSED REVIEW OF WIND LOAD CALCULATIONS FOR
 OARTU1 BY BUILDING PLANS EXAMINER.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-10-25 Cont ID  
Sent By rregueir Date 2008-10-25 Time 15:47 Rev Time 0.00
Received By rregueir Date 2008-10-25 Time 15:43 Sent To  
Notes
2008-10-25 15:47:02REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING DEFICIENCIES REMAIN AND SHALL BE
 ADDRESSED PRIOR TO PERMIT ISSUANCE:
  
 1. ADDRESS BUILDING PLAN REVIEW COMMENTS RELATED TO
 WIND LOAD ANALYSIS FOR OARTU-1.
  
 2. NO LETTER WAS INCLUDED WITH THIS SUBMISSION FROM
 TRANE REGARDING THEIR ACCEPTANCE OF THE PROPOSED
 REDUCED CLEARANCES FOR SERVICE AND REPLACEMENT OF
 COOLING COILS. ONCE SAID LETTER (TWO COPIES) IS
 PROVIDED, A PROVISO WILL BE ISSUED REQUIRING FIELD
 VERIFICATION BY MECHANICAL INSPECTOR THAT SUFFICIENT
 SPACE EXISTS FOR PROPER SERVICE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-05-01 Cont ID  
Sent By rregueir Date 2008-05-01 Time 09:05 Rev Time 0.00
Received By rregueir Date 2008-04-29 Time 18:09 Sent To  
Notes
2008-05-01 09:05:36REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THESE COMMENTS ARE NOT NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS UNDER PERMIT #07030368
  
 1. PAGE S-1 SHOWS THE RTU BEING WELDED TO THE ROOF
 CURB. THIS APPLIANCE SHALL BE ABLE TO BE REPLACED
 WITHOUT REMOVING ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBCM 306.1. WELDING THIS APPLIANCE IN
 PLACE WOULD CONSTITUTE PERMANENT CONSTRUCTION. SHOW HOW
 THIS APPLIANCE IS TO BE ATTACHED TO THE BUILDING
 STRUCTURE IN A WAY WHICH STILL ALLOWS FOR SERVICE AND
 REPLACEMENT WHILE MEETING WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBCM 301.13.
  
 2. PAGE S-2 SHOWS WIND LOAD DESIGN FOR THE BUILDING AND
 ATTACHMENTS OF CURB AND RTU TO THE STRUCTURE BUT NO
 INFORMATION WAS PROVIDED REGARDING DESIGN OF THE RTU TO
 WITHSTAND ANTICIPATED WIND PRESSURES. APPLIANCES
 EXPOSED TO WIND SHALL BE DESIGNED TO RESIST ANTICIPATED
 WIND LOADS IN ACCORDANCE WITH FBCM 301.13. PLEASE
 NOTICE THAT THIS APPLIES TO THE APPLIANCE ITSELF AND
 NOT JUST ATTACHMENTS TO THE STRUCTURE. PLEASE PROVIDE
 DOCUMENTATION SHOWING THIS APPLIANCE IS DESIGNED TO
 WITHSTAND WIND PRESSURES IN ACCORDANCE WITH FBCB
 1609.1.
  
 3. PAGE M.4.1: GENERAL NOTE #5 ON THIS PAGE APPEARS TO
 BE IN CONFLICT WITH GENERAL NOTE #3 ON PAGES M.1.1 AND
 M.1.2. PLEASE COORDINATE NOTES AND PAGES. ALSO, NO
 INFORMATION COULD BE FOUND ON STRUCTURAL PLANS
 REGARDING NEW 92X52 ROOF ACCESS OPENING. PROVIDE
 STRUCTURAL DETAIL WITH ALL RELEVANT WIND RESISTANCE
 DOCUMENTATION FOR BUILDING PLAN REVIEW.
  
 4. PAGE M6.1: THE ROOF CURB DETAIL IS IN CONFLICT WITH
 STRUCTURAL DETAILS. PLEASE SEE COMMENT #1 ABOVE AND
 COORDINATE WITH FUTURE STRUCTURAL DETAIL.
  
 5. PREVIOUS PLAN REVIEW COMMENT(S) #3 UNDER PERMIT
 #07030368 HAS NOT BEEN ADDRESSED.
  
 FIRST REVIEW: M4.1 PLEASE SEE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FOR MINIMUM REQUIREMENTS FOR
 SERVICE ACCESS PER FBC.M 304.1,304.2. EXAMPLE: AHU 3,
 AHU 12 BOTH REQUIRE MIN. 71" ON COIL CONNECTION SIDE OF
 UNIT AND 24" MIN. ON OPPOSITE SIDE. PLAN SHOWS APPROX.
 48" ON COIL SIDE AND 12" ON OPPOSITE SIDE FOR AHU 12.
 THIS UNIT, ONCE IN PLACE, WOULD NOT BE SERVICEABLE.
 MINIMUM SERVICE CLEARANCE FROM ELEMENTS OF PERMANENT
 CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT, IS
 REQUIRED PER FBC,M 306.1.
  
 SECOND REVIEW: REGARDING LETTER FROM TRANE; THIS LETTER
 IS ACCEPTABLE. HOWEVER, PRIOR TO PERMIT ISSUANCE, TWO
 COPIES OF THIS LETTER WITH ORIGINAL SIGNATURE AND SEAL
 OF THE TRANE ENGINEER IS REQUIRED. ALSO, APPROVAL OF
 THE CLEARANCES WILL BE CONDITIONAL PENDING SATISFACTORY
 DEMONSTRATION TO THE FIELD INSPECTOR THAT THE COILS ARE
 IN FACT ABLE TO BE REPLACED AND THE EQUIPMENT IS IN
 FACT ABLE TO BE FULLY SERVICED UNDER ACTUAL FIELD
 CONDITIONS. THIS WILL BE A PROVISO IF AND WHEN PERMIT
 IS APPLIED FOR AND ISSUED.
  
 ***NO LETTER FROM TRANE WAS FOUND IN THIS SUBMITTAL
 PACKAGE. PROVIDE TWO COPIES AS REQUESTED IN PREVIOUS
 REVIEW. THIS WILL FACILITATE PERMIT ISSUANCE WITH
 PROVISO PENDING FIELD VERIFICATION OF SERVICEABILITY OF
 AIR HANDLERS AS INSTALLED. FBCM 306.1.
  
 6. PLEASE CORRECT THE ADDRESS ON MECHANICAL AND
 ELECTRICAL PAGES TO CORRESPOND WITH THE ADDRESS ON THE
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-09 Cont ID  
Sent By mperson Date 2008-10-09 Time 08:49 Rev Time 0.30
Received By mperson Date 2008-10-09 Time 08:49 Sent To G
Notes
2008-10-09 08:56:17****************PROVISO****************
 INFORMATION ONLY, REVISION NOT REQUIRED. PER FBC-2004
 PLUMBING TABLE 308.5 HANGER SPACING: IF CONDENSTE
 PIPING IS PVC PIPE THE MAXIMUM HORIZONTAL SPACING SHALL
 BE 4 FEET.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-04-18 Cont ID  
Sent By mperson Date 2008-04-18 Time 16:01 Rev Time 0.00
Received By mperson Date 2008-04-18 Time 16:01 Sent To G
Notes
2008-04-18 16:05:53NOTE: PLUMBING PLAN REVIEW HAS PASSED, HOWEVER
 SIGNATURE STAMP WILL NOT BE PLACED UNTIL GAS PLAN
 REVIEW ISSUES ARE RESOLVED.

Review Stop Z ZONING
Rev No 4 Status P Date 2009-01-30 Cont ID  
Sent By mflis Date 2009-01-30 Time 08:43 Rev Time 0.00
Received By mflis Date 2009-01-30 Time 08:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-12-09 Cont ID  
Sent By mflis Date 2008-12-09 Time 10:33 Rev Time 0.00
Received By mflis Date 2008-12-09 Time 10:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-03 Cont ID  
Sent By mflis Date 2008-10-03 Time 10:56 Rev Time 0.00
Received By mflis Date 2008-10-03 Time 10:56 Sent To  
Notes
2008-10-03 10:57:23ZONING REVIEW: PASSED
  
 ** HVAC REPLACEMENT ONLY
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-25 Cont ID  
Sent By astelly Date 2008-04-25 Time 16:14 Rev Time 0.00
Received By astelly Date 2008-04-25 Time 16:13 Sent To  
Notes
2008-04-25 16:18:12AMY STELLY
 URBAN DESIGN
 822-1440
  
  
 PLEASE PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED
 WORK.
 PLEASE PROVIDE DRAWINGS SHOWING SCREENING FOR THE
 MECHANICAL EQUIPMENT.
 SCREENING MUST BE ARCHITECTURALLY COMPATIBLE WITH
 EXISTING STRUCTURE.