Plan Review Details - Permit 08040362
Plan Review Stops For Permit 08040362
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-05 Cont ID  
Sent By rmcdouga Date 2008-05-05 Time 17:29 Rev Time 0.00
Received By rmcdouga Date 2008-05-05 Time 17:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-22 Cont ID  
Sent By rmcdouga Date 2008-04-22 Time 16:35 Rev Time 0.00
Received By rmcdouga Date 2008-04-22 Time 14:18 Sent To  
Notes
2008-04-22 16:32:582004 FBC W/2007 REVISIONS
 CHANGE OF OCCUPANCY
 ENCLOSE PORTION OF GARAGE FOR OFFICE
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC 13-600. THE OWNER/AGENT IS REQUIRED TO SIGN THE
 FORMS.
  
 3) PROVIDE A WALL SECTION OF THE NEW INTERIOR WALLS
 INDICATING THE FRAMING MATERIALS, STUD SPACING,
 INSULATION, DRYWALL THICKNESS, ETC.
  
 4) THE WALL ADJACENT TO THE STORAGE AREA IS REQUIRED TO
 BE INSULATED. SPECIFY THE R-VALUE OF THE INSULATION IN
 THE ATTIC, EXTERIOR, COMMON AND ADJACENT WALLS. THE
 DOOR IN THE ADJACENT WALL IS REQUIRED TO COMPLY WITH
 FBC 13-603 AND CAN NOT BE HOLLOW CORE. SEE FBC 13-600.
  
 5) SPECIFY ON THE PLANS WHICH WALLS ARE NEW AND WHICH
 ARE EXISTING.
  
 6) THE PROPOSED OFFICE IS REQUIRED TO COMPLY WITH FAIR
 HOUSING REQUIREMENT 4 FOR ACCESSIBLE ROUTE AND
 REQUIREMENT 3 FOR USABLE DOORS. USABLE DOORS ARE
 REQUIRED TOHAVE A NOMINAL 32" CLEAR OPENING MEASURED
 FROM THE STOP TO THE FACE OF THE DOOR WHEN OPEN 90
 DEGREES. THE FLOOR OF THE OFFICE IS REQUIRED TO BE
 LEVEL WITH THE EXISTING HABITABLE SPACE. SHOW
 COMPLIANCE WITH THESE REQUIREMENTS. SHOW THE LOCATIONS
 OF ANY FLOOR ELEVATION CHANGES ON THE PLANS. THE LIGHT
 SWITCHES, RECEPTACLES AND CONTROLS ARE REQUIRED TO
 COMPLY WITH REQUIREMENT 5. SEE FBC CHAPTER 11 PART B
 FAIR HOUSING.
  
 7) TEST RTW
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-05 Cont ID  
Sent By btrobaug Date 2008-05-05 Time 09:26 Rev Time 0.00
Received By btrobaug Date 2008-05-05 Time 09:26 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By btrobaug Date 2008-04-16 Time 14:39 Rev Time 0.00
Received By btrobaug Date 2008-04-16 Time 14:22 Sent To M
Notes
2008-04-16 14:39:10 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 2} SUBMIT PLANS INDICATING COMPLIANCE WITH SPACING
 REQUIREMENTS FOR OUTLETS, INCLUDING LIGHTING PER
 ARTICLE 210, 2005 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 10:34 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 10:34 Sent To E
Notes
2008-04-30 10:34:59TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-22 Cont ID  
Sent By rmcdouga Date 2008-04-22 Time 16:35 Rev Time 0.00
Received By rmcdouga Date 2008-04-14 Time 15:13 Sent To  
Notes
2008-04-14 15:13:48TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-05-05 Cont ID  
Sent By tgordon Date 2008-05-05 Time 13:54 Rev Time 0.20
Received By tgordon Date 2008-05-05 Time 13:54 Sent To P
Notes
2008-05-05 13:55:49PROPOSED SPACE CHANGED ON PLANS AND PERMIT APPLICATION
 FROM OFFICE TO STORAGE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By tgordon Date 2008-04-16 Time 14:52 Rev Time 0.30
Received By tgordon Date 2008-04-16 Time 14:52 Sent To B
Notes
2008-04-16 15:14:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS THE PROPOSED OFFICE SPACE HAS NO WINDOWS, A MEANS
 OW VENTILATION WILL NEED TO BE PROVIDED, SEE 2004 FBC/R
 R303.1 AND THE EXCEPTIONS. PLEASE CORRECT.
  
 2) PLEASE STATE ON THE PLAN IF THE WATER HEATER IS
 ELECTRIC OR GAS. IF GAS SEE 2004 FBC/R G2407.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-16 Cont ID  
Sent By choops Date 2008-04-16 Time 10:21 Rev Time 0.00
Received By choops Date 2008-04-16 Time 10:21 Sent To E
Notes
2008-04-16 10:22:27INTERIOR WORK ONLY.