Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-14 Cont ID  
Sent By jgomez Date 2008-05-14 Time 10:57 Rev Time 0.00
Received By jgomez Date 2008-05-14 Time 10:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-15 Cont ID  
Sent By jgomez Date 2008-04-14 Time 18:28 Rev Time 0.00
Received By jgomez Date 2008-04-14 Time 18:28 Sent To PC
Notes
2008-04-14 18:30:45RESIDENTIAL (R2) WINDOW CHANGE OUT, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- ACCORDING TO SEC. 1609.4(3) FBC 2004 THE BUILDING IS
 LOCATED IN EXPOSURE "C". THEREFORE, WINDOWS NEED TO
 MEET THE DESIGN PRESSURES FOR EXPOSURE "C" AS PER
 TABLES 1609.6.2.1(2) AND TABLE 1609.6.2.1(4) FBC 2004.
 SPECIFY BUILDING MEAN ROOF HEIGHT AND IF WINDOWS ARE
 LOCATED ON END ZONE OR INTERIOR ZONE TO VERIFY
 COMPLIANCE WITH THE PRODUCT APPROVAL AND DESIGN
 PRESSURES.
  
 2- ACCORDING TO KEY PLAN SUBMITTED, WINDOWS ARE 51-
 3/4" X 52 -7/8".WINDOW SIZE SHOWN ONSHEET 2 OF FOUR
 ARE 53-1/8" X 63".THESE WINDOWS ARE BIGGER THAN THE
 OPENINGS WHERE WINDOWS WILL BE INSTALLED. CONTRACTOR IS
 NOT ALLOWED TO DO STRUCTURAL CHANGES IF HOLDING LICENSE
 U-19530 FOR DOOR AND WINDOW REPLACEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status N Date 2008-04-14 Cont ID  
Sent By jgomez Date 2008-04-14 Time 18:30 Rev Time 0.00
Received By jgomez Date 2008-04-14 Time 18:30 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved