Plan Review Details - Permit 08040245
Plan Review Stops For Permit 08040245
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-27 Cont ID  
Sent By mjacobs Date 2008-05-27 Time 09:15 Rev Time 0.00
Received By mjacobs Date 2008-05-23 Time 15:49 Sent To PC
Notes
2008-05-27 08:24:20PROVISOR:
 PLEASE NOTE SIGNS AND AWNINGS REQUIRE A SEPARATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-17 Cont ID  
Sent By mjacobs Date 2008-04-17 Time 12:38 Rev Time 0.00
Received By mjacobs Date 2008-04-17 Time 06:59 Sent To  
Notes
2008-04-17 12:38:55 
 BUILDING PLAN REVIEW
 PERMIT: 08040245
 ADD: 3501 S. DIXIE HWY
 CONT: VENTURA CONST. CORP
 TEL: (561)586-3801
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-17-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC. THE VALUE SHALL INCLUDE ALL INTERIOR AND
 EXTERIOR WORK.
  
 4)INDICATE THE DESIGN WIND INFORMATION ON THE
 DRAWINGS. THE BASIC WIND SPEED FOR THE CITY OF WEST
 PALM BEACH IS 140 MPH SEE 1603.1.4 AND 1609 FOR MORE
 INFORMATION.
  
 5)THE PRODUCT APPROVALS FOR HARDI PLANK SHALL
 INDICATE WHICH ITEMS OR SYSTEMS WILL BE USE AT THE
 PROJECT OR THE INFORMATION SHALL BE STATED ON THE
 DRAWINGS FOR CLARITY.
  
 6)SHEET A-8 WHICH SHOWS THE NEW PARAPET WALL REQUIRES
 MORE INFORMATION. THE DETAIL NEEDS TO SHOW AND STATE
 ALL MATERIALS WHICH WILL BE USE TO CONSTRUCT THE
 PARAPET, INCLUDE THE GAGE OF THE METAL STUDS OF THE
 TYPE OF WOOD. THE STUD SPACING SHALL BE STATED ON THE
 PLANS FOR THE NEW CONSTRUCTION. PROVIDE ALL THE
 ATTACHMENTS FOR THE PARAPET TO MEET THE WIND LOADS. A
 ROOFING DETAIL LISTING ALL MATERIALS IS REQUIRED
 SHOWING THE PREVENTION OF WATER INTRUSION FOR THE
 BRACING OF THE PARAPET. IS THE EXISTING STRUCTURE
 CONCRETE, METAL STUD WITH PLYWOOD OR CONCRETE BLOCK?
  
 7)1404.2. EXTERIOR WALLS OF FRAME CONSTRUCTION
 RECEIVING A VENEER SHALL BE PROVIDED WITH A
 WATER-RESISTIVE BARRIER. THE WATER RESISTIVE BARRIER
 SHALL BE A MINIMUM OF ONE LAYER OF NO. 15 ASPHALT FELT,
 COMPLYING WITH ASTM D 226 FOR TYPE 1 FELT, SHALL BE
 ATTACHED TO THE SHEATHING, WITH FLASHING AS DESCRIBED
 IN SECTION 1405.3 , IN SUCH A MANNER AS TO PROVIDE A
 CONTINUOUS WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR
 WALL VENEER.
  
 8)FBC 11-7 (2)(I) A PORTION OF THE COUNTER SHALL BE A
 MINIMUM OF 36 INCHES IN LENGTH AND A MAXIMUM HEIGHT OF
 36 INCHES. SHOW THIS INFORMATION THE ELEVATION
 DRAWINGS.ALL DRAWINGS SUBMITTED SHALL BE DIMENSIONED
 AND DRAWN TO A MINIMUM 1/8 INCH SCALE. THE DRAWINGS ARE
 NOT DIMENSIONED.
  
 9)PLEASE NOTE SIGNS AND AWNINGS REQUIRE A SEPARATE
 PERMIT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-22 Cont ID  
Sent By btrobaug Date 2008-05-22 Time 12:49 Rev Time 0.00
Received By btrobaug Date 2008-05-22 Time 12:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-15 Cont ID  
Sent By btrobaug Date 2008-04-15 Time 09:41 Rev Time 0.00
Received By btrobaug Date 2008-04-14 Time 15:45 Sent To  
Notes
2008-04-14 16:58:15 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-1 LIGHTING PERFORMANCE CALCULATIONS INDICATE
 ALL THE LUMINAIRES TO BE 32 VA. THE LIGHTING SCHEDULE
 HAS DIFFERENT WATTAGES INDICATED FOR THE DIFFERENT
 FIXTURE TYPES. CORRELATE SAME TO INDICATE THE PROPOSED
 THE TYPES BEING INSTALLED. RECALCULATE THE DENSITIES.
  
 2} SHEET E-1 HAS TRACK LIGHTING, "C" TYPE FIXTURE IS
 NOT LISTED ON THE LIGHTING SCHEDULE. SEE 13-415.2
 ABC.1.2, 3 AND 4 REGARDING TRACK LIGHTING.
  
 3} SEE 13-415.1ABC.1.2 REGARDING SPACE CONTROLS AND
 INCLUDE LOCATIONS ON PLANS.
  
 4} CIRCUIT NUMBERS AND PANEL DESIGNATIONS ARE REQUIRED
 FOR THE LIGHTING CIRCUITS AND MUST CORRELATE WITH THE
 SCHEDULES.408.4 NEC AND 106.3.5.1.2 FBC AS AMENDED.
  
 5} REGARDING THE BATTERY PACK UNITS, CIRCUIT THEM PER
 700.12(F)(4) NEC.. INDICATE SAME ON THE PLAN.
  
 6} NOTE #5, SHEET E-1 REGARDING RESTROOM LIGHTS IS
 ATTACHED TO THE TRACK LIGHTING?
  
 7} SHEET E-3 RISER DIAGRAM ERRONEOUSLY INDICATES THE
 SERVICE IS A 5 PHASE 120/240 DELTA WITH A HIGH LEG ON
 "C" PHASE.IN VIOLATION OF 408.3(E). THE HIGH LEG IS
 MARKED ON "B" PHASE IN THE PANEL SCHEDULE, WITH SINGLE
 PHASE CIRCUITS ON THAT PHASE. THE DESIGNER SHOULD
 CONTACT FPL FOR THE CORRECT INFORMATION ON THE SERVICE
 AVAILABLE AT THE LOCATION OF THE PROJECT. ALTHOUGH
 HIGHLY UNLIKELY IT WOULD BE A 120/240 DELTA, IF
 CONFIRMED THE PANEL BRANCH CIRCUITS SHALL BE ARRANGED
 ACCORDINGLY.
  
 8} THE PANEL SCHEDULES ON E-3 DO NOT INDICATE
 COMPLIANCE WITH 210.8 (B) FOR GFCI PROTECTION, ALSO NO
 INDICATION ON SHEET E-2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-05-22 Cont ID  
Sent By mwennerg Date 2008-05-22 Time 15:39 Rev Time 0.00
Received By mwennerg Date 2008-05-22 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-18 Cont ID  
Sent By mwennerg Date 2008-04-18 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2008-04-18 Time 11:11 Sent To  
Notes
2008-04-18 11:20:01***DENIED***
  
 1) PLANS INDICATE THAT BUILDING IS PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. PLEASE CLARIFY AND IF
 INFORMATION IS NOT CORRECT, PLEASE CORRECT INFORMATION
 IN PROJECT SUMMARY.
  
 2) AN EXIT SIGN THAT IS LOCATED AT THE WEST END OF THE
 STORE AREA APPEARS TO LEAD PERSONS INTO A ROOM WITH NO
 EXIT DOORS. IF SIGN IS DIRECTIONAL LEADING PERSONS TO
 THE MAIN EXIT, PLEASE ADVISE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 11:33 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 11:33 Sent To  
Notes
2008-05-19 11:34:07TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-18 Cont ID  
Sent By mwennerg Date 2008-04-18 Time 11:21 Rev Time 0.00
Received By mwennerg Date 2008-04-10 Time 12:00 Sent To  
Notes
2008-04-10 12:01:12TO "BOB"#10

Review Stop Z ZONING
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By choops Date 2008-05-20 Time 14:17 Rev Time 0.00
Received By choops Date 2008-05-20 Time 14:17 Sent To  
Notes
2008-05-20 14:14:25***APPROVED - RESUB #1***
  
  
 NOTE:SIGNS, MURALS, AWNINGS, AND AWNING SIGNS REQUIRE
 SEPARATE PERMITS.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By choops Date 2008-04-11 Time 17:02 Rev Time 0.00
Received By choops Date 2008-04-11 Time 17:02 Sent To  
Notes
2008-04-11 17:04:46***FAILED***
  
  
 1)CLARIFY SCOPE OF WORK.PERMIT APPLICATION
 INDICATES ADDITION OF EXTERIOR PARAPET, INDICATE WHAT
 IS EXISTING AND WHAT IS PROPOSED.SHOW HEIGHT OF
 PROPOSED.
  
 2)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE LOCATION OF ANY/ALL EXTERIOR IMPROVEMENTS.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 NOTE:SHOWN AWNINGS, SIGNS, MURALS, AND AWNING SIGNS
 SHALL BE REQUIRED TO OBTAIN SEPARATE PERMITS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  