Plan Review Details - Permit 08040226
Plan Review Stops For Permit 08040226
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-18 Cont ID  
Sent By rmcdouga Date 2008-06-18 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2008-06-18 Time 13:51 Sent To  
Notes
2008-06-18 14:13:422004 W/2007 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE WRONG ENERGY CALCULATION FORM WAS SUBMITTED. THE
 CORRECT ONE IS FORM 600C-04R. SEE ATTACHED.
 THE FORM IS REQUIRED TO SIGNED BY THE PREPARER AND THE
 OWNER/AGENT. TWO COPIES ARE REQUIRED. FBC 13-600.
  
 2) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE PGT
 FRENCH DOOR IS EXPIRED. SUBMIT TWO COPIES OF THE NEW
 NOA 07-0629.10 THAT HAVE BEEN APPROVED BY THE DESIGNER
 OF RECORD. DCA RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-21 Cont ID  
Sent By rmcdouga Date 2008-04-21 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2008-04-21 Time 07:38 Sent To  
Notes
2008-04-21 14:51:442004 FBC W/2007 REVISIONS
 ADDITION AND DECK
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THERE ARE TWO STRUCTURES LOCATED ON THE SAME PARCEL.
 THERE WERE PLANS SUBMITTED FOR A SINGLE STORY BUILDING,
 A TWO STORY STRUCTURE AND A SITE WALL. THE TITLE BLOCK
 ON ALL THREE PLANS ONLY PROVIDE THE OWNER NAME AND
 ADDRESS. IN ORDER TO AVOID CONFUSION, PLEASE SPECIFY
 THE STRUCTURE TO WHICH THE PLANS APPLY IN THE TITLE
 BLOCKS. FBC 106.1* CITY AMENDMENTS.
  
 TWO STORY STRUCTURE
  
 1) ON SHEET A-2 THE SECOND FLOOR FLOOR PLAN SAYS TO SEE
 DETAIL C. THERE DOES NOT APPEAR TO BE A DETAIL C
 PROVIDED. PLEASE CLARIFY.
  
 2) ON SHEET D-1 THE 6 X 6 POSTS IN CONTACT WITH THE
 SOIL ARE NOT SPECIFIED AS BEING PRESSURE TREATED ON
 SHEET D-1.
  
 3) ON SHEET A-2 SECTION A AT THE DECK IS INDICATED ON
 THE SECOND FLOOR PLAN. HOWEVER, THERE DOES NOT APPEAR
 TO BE A SECTION A PROVIDED. PLEASE CLARIFY.
  
 4) SPECIFY HOW THE 2 X 10 FLOOR JOISTS ARE ATTACHED TO
 THE (3) 2 X 10S LOCATED ATOP THE 6 X 6 POSTS. FBC
 106.1.2* CITY AMENDMENTS.
  
 5) THE SECOND FLOOR PLAN ON A-2 SPECIFIES A 4 PLY 2 X
 10 IN ONE LOCATION AT THE 6 X 6 POSTS AND (3) IN THE
 OTHER. PLEASE CLARIFY.
  
 6) ON SHEET D-1 PART OF THE TEXT IS MISSING FROM THE
 NOTES AT THE LEFT SIDE OF THE PAGE.
  
 7) SUBMIT (2)TWO COPIES OF PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD FOR THE PROJECT. FBC 106.3.3* CITY
 AMENDMENTS.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG WINDOWS
 AS REQUIRED BY DCA RULE 9B-72.
  
 ONE STORY STRUCTURE
  
 1) ON SHEET S-1 THE WALL SECTION SHOWS THE STUCCO
 FINISH EXTENDING BELOW GRADE. THIS DOES NOT COMPLY WITH
 SECTION 704 INSPECTION FOR TERMITES. IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM). PLEASE CORRECT.
  
 2) AT THE ADDITION, SHOW COMPLIANCE WITH R408.1
 VENTILATION.
 THE UNDER -FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT OR CELLAR) SHALL BE PROVIDED
 WITH VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION
 OPENINGS SHALL NOT BE LESS THAN 1 SQUARE FOOT FOR EACH
 150 SQUARE FEET (0.67 M 2 FOR EACH 100 M 2 ) OF UNDER
 -FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING SHALL
 BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF SAID
 BUILDING.
 UNDER FLOOR
  
 3) AT THE ADDITION, SHOW COMPLIANCE WITH R408.3 ACCESS
 SHALL BE PROVIDED TO ALL UNDER -FLOOR SPACES. ACCESS
 OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF 18
 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE 16 INCHES BY 24
 INCHES (407 MM BY 610 MM). WHEN ANY PORTION OF THE
 THROUGH WALL ACCESS IS BELOW GRADE, AN AREAWAY OF NOT
 LESS THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM)
 SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY SHALL BE
 BELOW THE THRESHOLD OF THE ACCESS OPENING. THROUGH WALL
 ACCESS OPENINGS SHALL NOT BE LOCATED UNDER A DOOR TO
 THE RESIDENCE. SEE M1305.1.4 FOR ACCESS REQUIREMENTS
 WHERE MECHANICAL EQUIPMENT IS LOCATED UNDER FLOORS.
  
 4) SUBMIT ENERGY CALCULATION FORMS SIGNED BY THE
 OWNER/AGENT AS REQUIRED BY FBC 13-600 FOR THE BATH ROOM
 ADDITION.
  
 5)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 6) SPECIFY THE ATTACHMENT OF THE NEW FOOTER AND WALLS
 TO THE EXISTING STRUCTURE AT THE BATH ROOM ADDITION.
 FBC 106.1.2* CITY AMENDMENTS
  
 7) SPECIFY TERMITE TREATMENT ON THE PLANS AS REQUIRED
 BY SECTION R320.
  
 8) THE MINIMUM INSULATION FOR A RAISED FLOOR SYSTEM IS
 R-11 PER FBC 13-600. SPECIFY THE FLOOR INSULATION ON
 THE PLANS.
  
 9) THE WALL SECTION ON D-1 SPECIFIES THE ROOF SHEATHING
 FASTENERS AS 8D COMMONS. SECTION R803.2.3.1 OF 2006
 REVISIONS TO 2004 FBC RESIDENTIAL CODE REQUIRES 8D RING
 SHANK NAILS.
  
 10)DESIGN DATA NOTE H ON SHEET D-1 FOR THE ONE STORY
 AND A-1 FOR THE SITE WALL INCORRECTLY SPECIFIES THE
 SBCCI. PLEASE REVISE TO REFERENCE THE FBC.
  
 11) SHEET 5 OF 5 APPEARS TO BE MISSING. PLEASE SUBMIT
 MISSING SHEET.
  
 12) PLEASE CLARIFY WHAT IS MEANT BY EXP. B AND EXP. C
 AS SPECIFIED ON THE FLOOR PLAN ON SHEET A-1.
  
 13) SPECIFY THE WINDOW SIZE AND TYPE FOR THE EXISTING
 BATHROOM ON THE FLOOR PLAN ON A-1. FBC 106.1* CITY
 AMENDMENTS
  
 14) SUBMIT (2) TWO COPIES OF THE PRODUCT APPROVALS FOR
 THE ROOF COVERING, SINGLE HUNG WINDOWS AND OUTSWING
 DOORS. SEE DCA RULE 9B-72.
  
 15) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH ONE
 OF THE COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-12 Cont ID  
Sent By btrobaug Date 2008-06-12 Time 08:34 Rev Time 0.00
Received By btrobaug Date 2008-06-12 Time 07:47 Sent To M
Notes
2008-06-12 08:34:05 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FORUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW.
  
 5} INDICATE WHAT THE LOAD CALCULATIONS ARE FOR. IS
 THERE A NEW SERVICE IN THE SCOPE OF THIS APPLICATION?
 CHANGE THE DESCRIPTION ON THE APPLICATION TO INDICATE
 THE SCOPE OF WORK PROPOSED, THERE IS NO MENTION OF
 ELECTRICAL WORK ON THE APPLICATION.*** THE DESCRIPTION
 OF WORK REMAINS THE SAME, NO ELECTRICAL WORK
 INDICATEDON THE APPLICATION.INDICATE IF THE WORK SHOWN
 NEW OR EXISTING OR BOTH.
  
 6} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED** PANEL SCHEDULES HAVE BEEN
 SUBMITTED, INDICATE WHICH PANEL IS FOR WHICH UNIT(S).
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By btrobaug Date 2008-04-11 Time 12:00 Rev Time 0.00
Received By btrobaug Date 2008-04-11 Time 06:55 Sent To P
Notes
2008-04-11 11:55:11 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FORUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} BOTH ELECTRICAL SHEETS ARE NUMBERED E-14 OF 5.
 INDICATE WHICH BUILDING AND UNIT, UPPER OR LOWER, THE
 SHEET IS SUPPOSED TO DEPICT.
  
 3} GFI'S ARE REQUIRED IN THE KITCHEN FOR COUNTERTOPS
 PER 210.8(A)(6).
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED.
  
 5} INDICATE WHAT THE LOAD CALCULATIONS ARE FO. IS THERE
 A NEW SERVICE IN THE SCOPE OF THIS APPLICATION? CHANGE
 THE DESCRIPTION ON THE APPLICATION TO INDICATE THE
 SCOPE OF WORK PROPOSED, THERE IS NO MENTION OF
 ELECTRICAL WORK ON THE APPLICATION.
  
 6} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-04-09 Cont ID  
Sent By swurafti Date 2008-04-09 Time 11:46 Rev Time 0.00
Received By swurafti Date 2008-04-09 Time 11:46 Sent To  
Notes
2008-04-09 11:47:11HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 09:58 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 09:57 Sent To Z
Notes
2008-06-09 09:58:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-21 Cont ID  
Sent By rmcdouga Date 2008-04-21 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2008-04-10 Time 08:57 Sent To  
Notes
2008-04-10 08:58:43TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-06-12 Cont ID  
Sent By tgordon Date 2008-06-12 Time 09:08 Rev Time 0.20
Received By tgordon Date 2008-06-12 Time 09:08 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-04-10 Cont ID  
Sent By tgordon Date 2008-04-10 Time 13:27 Rev Time 0.20
Received By tgordon Date 2008-04-10 Time 13:26 Sent To Z
Notes
2008-04-10 13:27:31NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-13 Cont ID  
Sent By jleech Date 2008-06-13 Time 08:43 Rev Time 0.00
Received By jleech Date 2008-06-13 Time 08:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-15 Cont ID  
Sent By jleech Date 2008-04-15 Time 07:36 Rev Time 0.00
Received By jleech Date 2008-04-15 Time 07:27 Sent To B
Notes
2008-04-15 07:40:33DENIED;
 PLANS ARE TO BE SIGNED AND DATED BY THE PERSON TAKING
 RESPONIBLITY FOR DRAWING PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-10 Cont ID  
Sent By choops Date 2008-06-10 Time 14:00 Rev Time 0.00
Received By choops Date 2008-06-10 Time 14:00 Sent To E
Notes
2008-06-10 14:00:40***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 5)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR, CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
  
 NEW COMMENTS:
  
 1)NEWLY SUBMITTED PLANS SHALL BE RESTAMPED/APPROVED
 BY THE CITY'S HISTORIC PRESERVATION DEPARTMENT (5TH
 FLOOR, CITY HALL).
  
 2)AS ORIGINAL CITY RECORDS (GREENCARD #85-110) SHOWS
 THE ACCESSORY STRUCTURE CONSTRUCTED AS A GARAGE (1ST
 FLOOR) AND A SINGLE APARTMENT (2ND FLOOR), PROVIDE
 PROOF (PERMIT HISTORY OR OTHER) THAT SHOWS THE
 ACCESSORY STRUCTURE BEING CONVERTED TO TWO (2) UNITS OR
 BEING BUILT AS TWO (2) UNITS.NOTE:AS THERE IS NO
 RENTAL LICENSE ON RECORD FOR THIS PROPERTY, NO UNIT MAY
 BE RENTED.
  
  
 FYI:THE "INDEX OF DRAWINGS" ON SHEET A-1 IS
 INCORRECT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By choops Date 2008-04-10 Time 14:04 Rev Time 0.00
Received By choops Date 2008-04-10 Time 14:04 Sent To E
Notes
2008-04-10 14:33:57***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)PROPOSED DRIVEWAY AS SHOWN ON SHEET SP-1 DOES NOT
 APPEAR TO MATCH PROPOSED DRIVEWAY AS SHOWN ON SHEET
 A-1.CLARIFY AND INDICATE SQUARE FOOTAGE OF ALL
 IMPERMEABLE SURFACES LOCATED WITHIN THE FRONT YARD
 (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING
 FACADE).
  
 PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS
 ARTICLE.
  
  
 3)INDICATE SETBACK DIMENSIONS OF PROPOSED BATHROOM
 ADDITION ON MAIN RESIDENCE.ADDITIONALLY, INDICATE
 SETBACK DIMENSIONS FROM FRONT SUNROOM AND COVERED
 ENTRY.
  
 NOTE:ANY NEW CONSTRUCTION SHALL MEET CURRENT SETBACK
 REGULATIONS AS SET FORTH IN SECTION 94-74 OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 4)PROPOSED GATE/FENCE APPEARS TO EXCEED MAXIMUM
 HEIGHT ALLOWABLE.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-302(B)(1): MAXIMUM
 HEIGHT.IN RESIDENTIAL DISTRICTS, NO FENCE OR WALL
 SHALL EXCEED SIX FEET IN HEIGHT WITHIN REQUIRED SIDE
 AND REAR SETBACKS. FENCES OR WALLS SHALL NOT BE IN
 EXCESS OF 48 INCHES IN HEIGHT WITHIN THE REQUIRED FRONT
 SETBACK.
  
 INDICATE HEIGHT OF FENCE FROM GRADE.
  
 5)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - SF RACK
  