Plan Review Details - Permit 08040192
Plan Review Stops For Permit 08040192
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-19 Cont ID  
Sent By mjacobs Date 2008-04-19 Time 14:41 Rev Time 0.00
Received By mjacobs Date 2008-04-19 Time 14:16 Sent To PC
Notes
2008-04-19 14:41:21 
 BUILDING PLAN REVIEW
 PERMIT: 08040192
 ADD: 1691 FORUM PL #B
 CONT: ABSOLUTE SIGN AND SERVICE
 TEL: (561)744-8030
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)1603.1.4. THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM
 OF THE BUILDING:
 A)BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 B)WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 C)WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED
 D)THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 E)COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF TO BE USED FOR THE SELECTION OF
 EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL. A DESIGN PROFESSIONAL SHALL PROVIDE THE
 INOFRMATION FOR THE FASTNERS AND STRUCTURAL STABILITY
 OF THE SIGN.
  
 2)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By btrobaug Date 2008-04-10 Time 10:55 Rev Time 0.00
Received By btrobaug Date 2008-04-10 Time 10:53 Sent To B
Notes
2008-04-10 10:55:48 
  
 NONCOMPLIANT
  
 1} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-04-19 Time   Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 14:56 Sent To  
Notes
2008-04-08 14:57:05TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By choops Date 2008-04-09 Time 10:23 Rev Time 0.00
Received By choops Date 2008-04-09 Time 10:23 Sent To E
Notes
2008-04-09 10:30:35***FAILED***
  
  
 1)PROPOSED SIGN EXCEEDS ALLOWABLE SQUARE FOOTAGE.
 PURSUANT TO SECTION 94-408(A)(1) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS:MAXIMUM SUM TOTAL
 AREA OF ALL SIGNS MOUNTED ON THE FRONT FACADE OF A
 BUILDING: 75 PERCENT OF THE AREA PERMITTED BY SECTION
 94-409.
  
 THE AREA PERMITTED IN TABLE XIII-1 (SECTION 94-409) IS
 23.70 SQUARE FEET.75% YIELDS A TOTAL ALLOWABLE SQUARE
 FOOTAGE OF 17.78 SQUARE FEET.PLEASE REVISE TO
 COMPLY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720